GE 60-960-95 Comm Failure, DTMF Dialing, Dialer Abort Delay, Cancel Message

Models: 60-960-95

1 104
Download 104 pages 42.3 Kb
Page 38
Image 38
Comm Failure (02003)

Comm Failure (02003)

Phone Options-Global (Default = on)

 

 

This setting determines whether the panel activates trouble beeps to alert users on the premises that communication to the central station failed. Failure notification occurs after the third unsuccessful reporting attempt to the central station/pager.

If a Phone Supervision Card (60-789) is installed, failure notification can occur immediately if inadequate phone line voltage is detected upon the initial dialing attempt.

Note

For UL 1635 listed installations, this feature must be turned on.

￿To turn Communication Failure notifi- cation off or on:

1.With the display showing COMM FAIL- URE OFF/ON (current setting), press 1 (off) or 2 (on). The display flashes the entered setting.

2.Press # and the display shows the new setting.

 

DTMF Dialing (02004)

 

 

Phone Options-Global (Default = on)

 

 

 

 

 

This setting determines whether the panel uses

￿To turn DTMF Dialing off or on:

 

DTMF tones (on) or pulse (off) for dialing pro-

1.

With the display showing DTMF DIALING OFF/ON (current setting),

 

grammed phone numbers.

 

press 1 (off) or 2 (on). The display flashes the entered setting.

 

 

2.

Press # and the display shows the new setting.

 

 

 

 

 

 

 

 

 

 

 

Dialer Abort (02005)

 

 

Phone Options-Global (Default = on)

 

 

 

 

 

This setting determines whether or not the user can stop a panel before it sends a false alarm to the central station.

When this feature is on, alarm reports from sensors in groups 00–20, 34, and 35 can be aborted. To abort the dialing attempt, the user must enter 1 + user code within the Dialer Abort Delay time setting (defaulted to 30 sec). Cancel and restoral reports from these sensor groups are aborted at the same time. The following reports can also be aborted.

System Alarm Tamper/Cancel

No Activity Alarm/Cancel

Touchpad Police and Auxiliary Panic/Cancel

Recent Closing and Two Trip Error

￿To turn Dialer Abort off or on:

1.With the display showing DIALER ABORT OFF/ON (current setting), press 1 (off) or 2 (on). The display flashes the entered setting.

2.Press # and the display shows the new setting.

Note

Fire alarm reports to the central station cannot be aborted.

Dialer Abort Delay (02006)

Phone Options-Global (Default = 30 sec.)

 

 

This setting determines how much time the user has to abort a panel report.

Note

For UL Listed systems, the combined time for the Entry Delay (0310/320) and Dialer Abort Delay must not exceed 60 seconds.

￿To change the Dial Abort Delay:

1.With the display showing DIAL ABORT DELAY nn SECS (current setting), enter the desired time (15–45). The display flashes the entered setting.

2.Press # and the display shows the new setting.

Cancel Message (02007)

Phone Options-Global (Default = on)

 

 

This setting determines whether or not the panel displays a cancel message after the user disarms the system to clear an alarm condition.

￿To turn Cancel Message off or on:

1.With the display showing CANCEL MESSAGE OFF/ON (current setting), press 1 (off) or 2 (on). The display flashes the entered setting.

2.Press # and the display shows the new setting.

33

Concord Ultra

Page 38
Image 38
GE 60-960-95 Comm Failure, DTMF Dialing, Dialer Abort Delay, Cancel Message, Phone Options-GlobalDefault = on