Connecting Detection Devices to Panel Zone Inputs

Note

The panel comes with fac- tory programmed onboard hardwire zones. Install

2k-ohm, end of line (EOL) resistors on all unused fac- tory programmed onboard hardwire zones. If you don’t want to install EOL resistors, delete any unused zones from memory. See Table 8 for onboard hardwire zone factory programming.

Connecting Detection Devices to Panel Zone Inputs

Zone inputs 1 through 8 are supervised using included 2k-ohm, end-of-line resistors at the last device on each circuit. All eight zones accept either normally open (N/O) or normally closed (N/ C) detection devices.

Connecting Intrusion Detection Devices

The graphics in Figure 7 show the typical wiring for N/C and N/O door/window intrusion detec- tion and for a Detection Systems model DS922 (part no. 13-082) motion detector. The minimum available panel voltage for hardwired PIR motion detectors is 8.5 VDC (9.5 VDC for UL listed installations).

Note

When using 2-wire smoke detectors on zone 8, the Two-Wire Smoke setting (in program mode) must be turned on before entering the LEARN SENSORS menu. See ONBOARD OPTIONSINPUTSin the section “Programming the Panel” for complete details.

Panel Terminals

+12

Zone

Zone 2 GND Zone 3

BUS

GND 7

 

 

Panel

 

 

4

Terminals

20

21

 

 

 

Normally

 

Motion

Closed

 

Detector

(N/C)

Normally Open

 

Contacts

(N/O) Contacts in

 

In Series

Parallel

 

 

2k Ohm EOL

 

 

Resistor 49-454

-+LP LN

 

 

 

2k Ohm EOL

 

 

Resistor 49-454

2k Ohm EOL Resistor 49-454

 

 

(Locate at Sensor)

Figure 7. Wiring Intrusion Detection

Connecting 2-Wire Smoke Detectors

Zone input 8 can be set up (in program mode) to accept the following 12 VDC, 2-wire smoke detectors:

System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH

ESL models 429AT, 521B, 521BXT—(models 521B and 521BXT require the following dip switch settings: 1-on, 2-off)

!Use only the 2-wire smoke detector models described above. Alarm signals from other detectors may not be processed correctly if the panel has lost AC power and is operat- ing only from the backup battery.

Caution

When set up for 2-wire smoke detectors, zone 8 can handle up to 10 smoke detectors with

120 uA maximum idle current per detector. Maximum total loop current allowed in an alarm con- dition is 100 mA. Connect one or more, 2-wire smoke detectors to the panel as shown in Figure 8.

11

Concord Ultra

Page 16