Smoke Verify (1100)
Concord Ultra

 

Smoke Verify (1100)

 

Onboard Options-Inputs (Default = off)

 

 

 

 

 

This setting controls the number of sensor group 26 (fire) zone

￿To turn Smoke Verify off or on:

 

trips needed to report a fire alarm.

 

1. With the display showing ONBOARD OPTIONS, press #

 

Hardwire Smokes: will determine whether or not the panel

twice. The display shows SMOKE VERIFY OFF/ON (cur-

 

requires two alarm signals within five minutes (on) from 2-

rent setting).

 

wire smoke detectors connected to panel zone input 6 and/

2. Press 1 (off) or 2 (on). The display flashes the entered

 

or SnapCard zone inputs or any other hardwire zone learned

number.

 

into group 26 (fire) before activating system sirens and

3. Press # and the display shows the new setting.

 

reporting to a central station (or pager).

 

Note

 

Wireless Smokes: the first trip of a group 26 RF sensor will

For California State Fire Marshall Listed installations, this feature

 

must be off.

 

cause a local fire alarm. The second trip of any group 26

 

 

 

zone within the siren timeout will cause that fire alarm to be

 

 

reported to the central station.

 

 

 

Note

 

 

 

RF smoke detectors repeat the alarm transmission every 60 sec-

 

 

onds as long as they are detecting smoke. This repeated transmis-

 

 

sion will serve as the second zone trip, causing the alarm to be

 

 

reported.

 

 

 

 

 

 

 

 

 

 

 

Two Wire Smoke (1101)

 

Onboard Options-Inputs (Default = off)

 

 

 

 

This setting determines how onboard hardwire zone 8

￿To turn Two Wire Smoke off or on:

 

is configured. When this setting is on, zone 8 will be

1. With the display showing ONBOARD OPTIONS, press # twice. The

 

configured for two wire smoke detectors. When off, it

display shows SMOKE VERIFY OFF/ON (current setting).

 

will be configured for a normal hardwire input.

2. Press A or B until the display shows TWO WIRE SMOKE ON/OFF

 

 

(current setting).

 

 

3. Press 1 (off) or 2 (on). The display flashes the entered number.

 

 

4. Press # and the display shows the new setting.

 

 

 

The following sections describe the settings that appear under ONBOARD OPTIONS—OUTPUT PRO-

 

GRAMMING.

 

 

Output 1, 2 (Output 1: partition assign-11100, configu-

Onboard Options-Output-Programming (Defaults:

ration-11101

Output 1= Ptn. 1, 01614; Output 2=Ptn. 1, 01710)

Output 2: partition assign-11110, configuration-11111)

 

 

 

This setting lets you assign the partition and the 5-digit configuration number. The configuration number determines

￿To set up onboard Output 1 & 2 partition and con- figuration assignments:

• which system event activates the selected output, and

1.

With the display showing ONBOARD OPTIONS,

 

press # + B. The display shows OUTPUT PRO-

• the duration or time the output is activated.

 

 

GRAMMING.

 

 

The first three digits represent the trigger number of an event (such as

2.

Press # and the display shows OUTPUT 1. Press B

triggering an alarm, opening a sensor, or arming the system). The last

 

to select OUTPUT 2.

two digits represent how the output responds (such as momentary

3.

Press # and the display shows PARTITION ASSIGN n

switching, maintained (or latched) switching, or switching for a preset

 

(current setting).

time).

4.

Press 1 or 2 to assign the output to the desired par-

Note

 

tition, then press #. The display shows PARTITION

 

ASSIGN (new setting).

If you want to configure an output for user Output Control you must use the

 

5.

Press B and the display shows CONFIGURATION

Output Text feature to name the output. If no Output Text is programmed,

Output Control will not function for that output.

 

tttrr (current setting).

Use the system event trigger and response numbers listed in Appen-

6.

Enter the desired configuration number. The dis-

 

play flashes the entered number. Press # and the

dix B: Reference Tables.

 

 

display shows the new setting.

 

 

 

7.

Press # and repeat steps 2 through 6 until all out-

 

 

puts are programmed.