Phone Access Key (partition 1: 0216, partition 2: 0226)

Phone Access Key (partition 1: 0216, partition 2: 0226)

Phone Options-Partition 1-2 (Default = #)

 

 

This setting determines which touch-tone phone button is used for system access and control.

If the Local Phone Control feature is enabled, the user can pick up the phone and press # (within 5 seconds) to access the security system. The panel seizes the phone line and waits for the user to enter system com- mands. Phone access can be changed from # to * (see the following note).

Note

Use the default setting (#) to avoid conflicts between the security system and other phone devices and services. Many phone devices (such as answering machines, computer modems, and FAX machines) and services (such as call- waiting, call-forwarding, and some banking transactions) require * to initiate their operation, so using * for this security feature could cause conflicts.

￿To change the Phone Access Key:

1.With the desired partition selected, press A or B until the display shows PHONE ACCESS KEY #/* (current setting).

2.Press 1 (for *) or 2 (for #). The display flashes the entered setting.

3.Press # and the display shows the new setting.

Timers Menu

The TIMERS menu lets you set up the various system feature times that affect the whole system (global) or a specific partition.

The following describes how to program the timer settings that appear under GLOBAL.

 

Supervisory Time (0300)

Timers-Global (Default = random between 01:00 and 04:00)

 

 

 

 

 

This setting determines what time of day the panel

￿To set the Supervisory Time:

 

sends supervisory, low battery, or auto phone test

1. With the display showing SUPERVISORY TIME HH:MM (current

 

reports to the central station.

 

setting), enter the desired 4-digit time value. For example,

 

Note

 

enter 0330 to set the supervisory time for 3:30 A.M. The display

 

The panel clock must be set with the correct time for accu-

 

flashes the entered setting.

 

rate supervisory time reporting. See “Time and Date Menu”. 2. Press # and the display shows the new setting.

 

 

 

 

 

 

RF Tx Timeout (0301)

 

 

Timers-Global (Default = 12 hours)

 

 

 

 

 

This setting determines how many hours (2–24) the

￿To set the RF Tx Timeout:

 

panel has to receive at least one signal from a wireless

1.

With the display showing RF TX TIMEOUT nn HOURS (current

 

sensor (learned into a supervised group). If the panel

 

setting), enter the desired timeout value (2–24). The display

 

does not receive a signal from any supervised wireless

 

flashes the entered setting.

 

sensor within the set time, the panel reports a supervi-

2.

Press # and the display shows the new setting.

 

sory condition to the central station.

 

 

 

 

Note

 

 

 

 

For ULUL 985 & 1635 listed installations, the RF Tx Timeout

 

 

 

 

must be set to 4 hours. For UL 1023 listed installations, the

 

 

 

 

RF Tx Timeout must be set to 24 hours.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phone Test Freq. (0302)

 

 

Timers-Global (Default = 7 days)

 

 

 

 

 

This setting determines how often the panel conducts the auto-

 

￿To set the Phone Test Freq:

 

matic phone test (see “Auto Phone Test” under PHONE

 

 

1. With the display showing PHONE TEST FREQ nnn DAYS

 

OPTIONS—GLOBAL). The system can be set to perform an auto-

 

(current setting), enter the number of days (1–255). The

 

matic phone test anywhere from every day to every 255 days.

 

display flashes the entered setting.

 

Note

 

 

2. Press # and the display shows the new setting.

 

For UL 1635 listed installations, this feature must be set to 1.

 

 

 

 

 

 

 

 

Concord Ultra

36

Page 41
Image 41