Operation

Note

For UL 1635 installations, Entry Delay plus Dialer Abort Delay must not exceed 60 seconds.

Function

Operation

 

 

Cancel Alarm

Enter Code Only (or 1 + CODE)

 

 

Abort Annunciation

Enabled

 

 

Cancel Report Annunciation

Enabled

 

 

UL 1635 Digital Alarm Communicator System

Same as UL 1023 & 985 plus:

AC Failure set to on

Comm Failure set to on

RF Tx Timeout set to 4 hours

Low CPU Battery set to on

Phone Number must be programmed

Next Phone Test set to 1

Phone Test Freq. set to 1

High Level Rpts set to on

Low Level Rpts set to on

Central Station Reporting

The panel has been tested with the following central station receivers using SIA and Contact ID reporting formats:

CS-5000 Central Station Receiver

Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2

UL Canada Listed Installations

This section describes the requirements for CUL (UL Canada) Listed installations.

Canadian Standards CSA Certified Accessories

Residential Burglary Alarm System Unit (ULC-S309)

Basic system as described for “UL 1023 Listed Installations” plus:

Hardwire Magnetic Contact (1035-N or 1075-N) or Wireless Learn Mode Door/Window Sensor (60-362)

Siren Timeout set to 5 minutes or more

Residential Fire Warning System Control Unit (ULC-S545-M89)

Basic system as described for “UL 985 Listed Installations” plus:

Hardwire Smoke Detector: System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH learned into Sensor Group 26, or Sentrol (ESL) models 429AT, 521B, or 521BXT learned into sensor group 26

Wireless Smoke Sensor 60-506-319.5 or 60-848-02-95 learned into sensor group 26

Immediate Beeps set to on

Note

For 24-hour backup, exter- nal power drain is limited to 90 mA (during normal standby condition) using a

4.0AH battery, or 190 mA continuous using a 7.0 AH battery.

RF TX Timeout set to 4 hours (if system includes wireless smoke sensors)

California State Fire Marshall Listed Installations

Same as Household Fire Warning System (UL 985), plus:

SMOKE VERIFY must be set to off

Planning the Installation

This section describes system capabilities to help you get familiar with the system. “Appendix A” provides planning sheets with tables that let you record the hardware and programming con- figuration of the system. Fill in all necessary information ahead of time to help prepare for sys- tem installation.

When planning the installation, keep in mind that the panel has the following capabilities (depen- dent upon devices used):

Up to 16 SuperBus 2000 Devices (maximum of 4 RF receivers)

3

Concord Ultra

Page 8
Image 8
GE 60-960-95 Planning the Installation, Central Station Reporting, UL Canada Listed Installations, Function, Operation