EMI CAC manual Correct Incorrect, Condensate Piping

Page 9

CONDENSATE PIPING

The unit can now be piped up in accor- dance with good refrigeration and/or plumbing practices.

The Cassette is supplied with a 1/2” I.D. fl exible PVC hose for connection to copper or plastic drain pipework. When installing the Cassette the following points should be remembered:

1.Maximum pump lift is 36”.

2.The highest point in the condensate pipework should be as close to the unit as possible. This prevents a large volume of water draining back into the unit when it is switched off.

NOTE: There is a check valve at the pump discharge to prevent water from draining back into the unit. This piping technique will minimize any is- sues should the check valve become stuck open from airborne debris.

Duct collars: Branch duct and fresh air duct collars can be attached to the Cas- sette chassis by following the steps below:

Condensate Drain Connection

1.Locating the knock-out holes.

Branch Duct Knockout

Correct

Incorrect

3.Condensate pipework should slope downwards in the direction of water fl ow with a minimum gradient of (1” per 10’). There must not be any uphill gradients other than in the fi rst 36” of pipework from the Cassette.

4.When multiple Cassettes are connect- ed to a common condensate drain, ensure the drain is large enough to handle the volume of condensate from several Cassettes. It is also rec- ommended to have an air vent in the condensate pipe work to prevent any air locks.

Small Unit

Medium &

Large Units

Fresh Air

Knockout

Notes: The number of knock-outs var- ies depending on unit size.

Branch duct knock-outs are 5¼” round

Fresh air knock-outs are 1¼” x 2½” rectangular on 12k, and 3” square on 24-36k

Recommendation: No more then 10’ of branch duct or fresh air duct should be installed.

CAC Cassette Evaporator

9

www.enviromaster.com

Image 9
Contents Nominal Circuit Capacities INSTALLATION, Operation and Maintenance ManualTo the Installer Safety InstructionsCAC Cassette High Efficiency Evaporator Standard Features Product DescriptionSystem Options CAC Cassette Controls and Components Preparation for InstallationSmall Unit Shown Medium Unit ShownLarge Unit CAC Cassette Preparation and Positioning PISTON/ORIFICE Installation InstructionCeiling opening Mounting the CAC Cassette Ceiling EvaporatorMAX CAC Cassette Chassis Positioning and InstallationCondensate Piping Correct IncorrectPiping DO’S and DON’TS Pipe Installation Notes Refrigeration PipingUse of a larger line can harm Compressor Assembly Instructions CAC Cassette Evaporator Fascia Installation InstructionsCAC Cassette Evaporator Installation Instructions Electrical WiringMake sure power is off Low Volt Interconnect Wiring High Volt Electrical WiringStart -UP for Wall Thermostat Control LOW Voltage Interconnect WiringFigure #4 Refrigerant Processing Important Notes CAC Cassette Evaporator Test Unit Performance Data Test Unit Performance Data SheetMaintenance and Troubleshooting Procedure Power Supply Check Troubleshooting ProcedureLow Volt Controls Cooling Only UnitsElectric Heat How long will the fan run? Frequently Asked QuestionsCAC Performance Data Discharge AIR VolumeSmall Cabinet CAC 9,000 12,000 CAC Cassette DimensionsMedium Cabinet CAC 18,000 24,000 Large Cabinet CAC 30,000 36,000 CAC Cassette System Matches CAC Electrical SpecificationsT2C, T3C & T4C Top Discharge Enviromaster International LLC ALL Product Limited WarrantyHigh Wall Evaporator EMI’S High Efficiency Product LineS1C & S1H Single Zone S2C Dual Zone T2C, T3C & T4C 2, 3 & 4 Zone Top Discharge