Honeywell IPGSM-DPC manual Wiring the 659EN Line Fault Monitor if required

Page 9

IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide

Wiring the 659EN Line Fault Monitor (if required)

The IPGSM-DPC is compatible with the Honeywell brand FACP’s listed on page 1 when the model 659EN Line Fault Monitor is installed.

1.Refer to the installation guide for the 659EN.

2.Mount the 659EN on the lower left side of the IPGSM-DPC cabinet.

3.DO NOT cut the 659EN’s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold Jumper.

4.Complete the interface wiring as shown below:

YEL

 

to Dialer Capture Module, Terminal, Tip 2

 

ORG

 

 

to Dialer Capture Module, Terminal, Ring 2

 

 

RED

 

to Power Boost 1, Terminal, OUTPUT 1, DC+

 

BLK

 

to Power Boost 1, Terminal, OUTPUT 1, DC-

 

GRN

 

to Power Boost 1, Terminal, ERTH GND

 

659EN

Wire to a

Zone on the Fire Panel

4.7K, 1/2 watt

IPGSM-DPC

IPGSM-DPC-013-V0

Example wiring for an addressable fire control panel:

IPGSM-DPC

Commercial Fire Communicator

 

 

 

 

 

 

 

 

 

YEL

 

 

to Dialer Capture Module, Terminal, Tip 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORG

 

 

to Dialer Capture Module, Terminal, Ring 2

 

 

 

 

 

 

 

 

 

 

RED

 

 

to Power Boost 1, Terminal, OUTPUT 1, DC+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

 

to Power Boost 1, Terminal, OUTPUT 1, DC-

 

 

 

 

 

 

 

 

 

 

GRN

 

 

to Power Boost 1, Terminal, ERTH GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

659EN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.7K, 1/2 watt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIRE LITE Addressable Fire Alarm Control Panel MS-9050UD

 

 

 

 

 

 

- To next device

 

 

 

 

 

 

TOP

 

 

 

 

 

+ on SLC Loop

 

 

 

 

 

 

 

 

 

 

 

MMF-300A

 

 

 

 

 

Braided-shield/Drain

Monitor Module

 

 

 

 

 

Wire

 

 

 

 

 

 

T11

 

 

 

 

 

T10

 

 

 

T1

 

T9

 

 

 

T2

 

T8

 

 

 

T3

 

T7

 

5 6 7 8 9 10

5 6 7 8 9

T4

 

T6

4

11

4

T5

 

3

12

3

 

 

2 1 0 151413

2 1 0

 

 

 

 

TENS

ONES

 

 

LOOP

 

 

 

ADDRESS

 

B+

B-

 

Shield

TB2

 

 

TB5

 

 

B+ A+ B- A- A B

NO NC C

 

 

 

SLC Loop

RELAY 1

 

 

 

ALARM CONTACTS

 

 

 

 

 

IPGSM-DPC-014-V0

7

Image 9
Contents IPGSM-DPC Contents Package Contents General InformationCompatible Fire Panels Operation Setup the Customer Account InstallationRegister the Communications Module with AlarmNet ULC Compliance Mount and Wire Determine the Signal Strength and Select a LocationPowerBoost1 Wiring for Grounds, Power, and RF Wiring the 659EN Line Fault Monitor if required 7720P Programmer Program the Communications ModuleTest the System Configure the Fire PanelLED Display Information Dialer Capture Module InformationTrouble PowerBoost1 Module InformationGRN IGSM Communications Module InformationCentral Station Messages RF SpecificationsIPGSM-DPC Trouble Detection Information IPGSM-DPC SpecificationsPage Page Page Page Page Page Battery Ê800-093708Š