Honeywell manual IPGSM-4GC Trouble Detection Information, IPGSM-4GC Specifications

Page 15

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide

IPGSM-4GC Trouble Detection Information

Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-4GC, and Telco 2 is used by the IPGSM- 4GC to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if there are no faults in the Communicator.

Fault Condition

Indication to Fire Panel

 

 

PowerBoost1 fault

Telco 2 is cut.

 

 

Communicator fault

 

Failure of the communications path when

Telco 2 is cut.

IP only or GSM only is programmed as a

 

communications path.

 

Failure of both communications paths

Telco 1 and 2 are cut.

when IP&GSM is programmed as a

 

communications path.

 

Dialer Capture Module buffer is full.

Hang up. (Panel will retry, giving the buffer a chance

 

to empty.)

IPGSM-4GC Specifications

ITEM

SPECIFICATION

 

 

Cabinet Dimensions:

Width 12 3/4 inches, Height 14 7/8 inches, Depth 3 inches

 

 

Transformer: 1451-UL9

Primary – 120VAC, 60Hz, 850mA, Secondary – 18VAC, 72VA

 

 

Battery:

12V, 7Ah sealed lead acid type (not supplied)

 

Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.

 

 

Battery Charging Current:

maximum 1A

 

 

Battery Discharge Current:

standby 230mA, active 950mA

 

 

Environment:

Operating temperature: –20º to +55ºC, for ULC installations 0ºC to

 

+49ºC

 

Storage temperature: –40º to +70ºC

 

Humidity: 0 to 95% relative humidity, non-condensing, for ULC

 

installations 0% to 93%

 

Altitude: to 10,000 ft. operating, to 40,000 ft. storage

 

 

Supervision:

The Radio (communicator), battery, and AC power, conditions are

 

monitored by the cabinet indicator LEDs:

 

RADIO TROUBLE lights when any of these conditions exist.

 

Both IP and GSM communication paths are lost.

 

Communicator radio is not registered.

 

Old Alarm Time has been exceeded. (Message has not been

 

delivered within the fixed 10 minute window.)

 

LOW BATTERY lights when the battery voltage is less than 11.5VDC.

 

AC LOSS lights when the AC power is less than 90VAC.

 

 

13

Image 15
Contents IPGSM-4GC Contents Installation General InformationOperation Setup the Customer Account Register the Communicator with AlarmNetDetermine the Signal Strength and Select a Location Mount and Wire PowerBoost1 Wiring for Grounds, Power, and RF Wiring the 659EN Line Fault Monitor Required for ULC 7720P Programmer Program the CommunicatorTest the System Configure the Fire PanelLED Display Information Dialer Capture Module InformationTrouble PowerBoost1 InformationGRN Communicator InformationCentral Station Messages RF SpecificationsIPGSM-4GC Trouble Detection Information IPGSM-4GC SpecificationsPage Page Page Page Page Page Page 1451-UL9 Wired Wiring DiagramÊ800-12458RŠ

IPGSM-4GC specifications

The Honeywell IPGSM-4GC is an advanced cellular communicator designed for security applications, providing reliable communication for alarm systems. This device enhances the ability of security systems to transmit signals to monitoring centers, ensuring that alarms are promptly addressed. With the increasing reliance on cellular technology, the IPGSM-4GC stands out as an essential tool for both residential and commercial security solutions.

One of the main features of the IPGSM-4GC is its dual-path communication capability. It can transmit signals via both Ethernet and cellular networks, providing redundancy that enhances reliability. In the event of an internet outage, the device seamlessly switches to cellular communication, ensuring that the alarm system remains operational at all times. This dual-path feature is particularly valuable in critical security applications where continuous communication is necessary.

The IPGSM-4GC also supports 4G LTE technology, which offers faster response times and improved signal quality compared to previous generation communicators. This technology enables the device to communicate with monitoring stations more efficiently, ensuring that alarm signals are sent and received quickly. Additionally, with 4G LTE being the current standard, the IPGSM-4GC is designed to remain relevant as older technologies are phased out.

Security is further enhanced by the robust encryption protocols employed by the IPGSM-4GC. The device uses advanced AES encryption, protecting sensitive data transmitted over cellular networks from potential interception or unauthorized access. This feature is crucial for users looking to maintain a high level of security in their alarm systems.

Installation and integration of the IPGSM-4GC are simplified thanks to its compatibility with a wide range of Honeywell alarm panels. The device utilizes a straightforward setup process, making it accessible for both professional installers and DIY enthusiasts. The modular design allows for easy updates and maintenance, ensuring longevity in performance.

In summary, the Honeywell IPGSM-4GC is a cutting-edge solution that combines dual-path communication, 4G LTE technology, and advanced encryption to provide a reliable and secure cellular communication option for alarm systems. With its ease of installation and compatibility with various Honeywell panels, it serves as a vital component for modern security solutions, meeting the demands of today’s connected world.