Honeywell HA40 technical manual Optional Analog Input PCB

Page 25

HA40 4-Channel Controller

3.1.2 Optional Analog Input PCB

(P/N 10-0221)

Transmitter input PCB option # 10-0298, shown in Figure 3-3, is available for interfacing the HA40 to field transmitters with 4-20mA or voltage outputs (0-2 VDC max). TB1 & TB2 provide Channel 24VDC, HI and LO terminals for receiving analog inputs. R1, R2, R3, & R4 are 100 ohm precision socketed termination resistors connected between each channel’s HI & LO input terminals. These may be removed if voltage inputs are to be applied. Figure 3-4 shows correct wiring for both 2-wire and 3-wire transmitters.

TB3 provides the dedicated failsafe-5 amp-form C common FAULT relay.

Figure 3-4. Wiring for 2- and 3-wire Transmitters

3.1.3 Optional Discrete Relay PCB’s

(P/N 10-0222)

The optional Discrete Relay PCB, shown in Figure 3-5, adds six 5 amp form C relays. Each relay is fully programmable as described in Section 2.3.1. Many HA40 applications utilize the standard equipped Relay 1 / Relay 2 (see Section 2.3.1) and do not require optional discrete relays

Warning

All mechanical (dry contact) relays are rated at 5 Amp for 28 VDC and 250 ~VAC RESISTIVE loads. IMPORTANT: Appropriate diode (DC loads) or MOV (AC loads) snubber devices must be installed with inductive loads to prevent RFI noise spikes.

AC or DC power supplies to relays on the 10-0222 Discrete Relay PCB option must be the same for each relay. Example: 24VDC should not be the power switched by one relay and 115VAC by others.

Figure 3-3. Optional Analog Input PCB (P/N 10-0221)

HA40 Technical Manual

3-4

Revision 1 (08/08)

Image 25 Contents
Technical Manual HA40 4-Channel Controller SafetyTable of Contents Operation Parts List General Description Keypad CAL in Progress General DescriptionData Display Screens SpecificationsRelays Ambient Temperature RangeHumidity Range AltitudeApprovals Housings / Installation CategoriesOperation Operation Setup Menu ConfigurationSetup Configuration Menus Changing Menu Variables Using the KeypadChannel Setup Entry Menu Configure Menu To Define Channel Fault / Alarm 1 / Alarm 2 / Alarm 3 Set-Up MenusName / Eunits Ascii Data Fields Decimal Point ResolutionInput Measurement Range Turning Off Unused ChannelsCalibrate Input Menu Cal Setup MenuStandard / Optional Relay Setup Menus System Configuration MenusComm Port Remote ID Menu Clock / Delays MenuHorn / Acknowledge Menu Analog Setup Menu12. Horn/Acknowledge Menu HA40 System Security MenuHA40 4-Channel Controller Motherboard Interface PCB Shock Hazard Motherboard Interface PCBRS-R85 / Ethernet Option Sensor Input Option Input / Output Optional PCB’sOptional Analog Input PCB Optional 4-20mA Analog Output Board Modbus RS-232 / RS-485 Interface Option Read Only Registers Variable Alias Memory Ascii Strings Enclosures HA40XP Nema 7 Explosion-Proof Wall EnclosuresHA40N4 Nema 4X Wall Mount Enclosure Parts List Base Units Parts ListSpecifications Specifications Warranty Honeywell Analytics Warranty Statement Find out more Customer business center Asia Pacific Americas