Honeywell HA40 technical manual Variable Alias

Page 29

HA40 4-Channel Controller

 

CHAN1 FAULT

 

BIT0

 

CHAN1 ALARM1

BIT1

 

CHAN1 ALARM2

BIT2

 

CHAN1 ALARM3

BIT3

 

CHAN2 FAULT

 

BIT4

 

CHAN2 ALARM1

BIT5

 

CHAN2 ALARM2

BIT6

 

CHAN2 ALARM3

BIT7

 

CHAN3 FAULT

 

BIT8

 

CHAN3 ALARM1

BIT9

 

CHAN3 ALARM2

BIT10

 

CHAN3 ALARM3

BIT11

 

CHAN4 FAULT

 

BIT12

 

CHAN4 ALARM1

BIT13

 

CHAN4 ALARM2

BIT14

 

CHAN4 ALARM3

BIT15

 

 

 

 

 

LED Blink Status

31011

 

4

NA

Bit set to 1 = LED Blinking, bit set to 0 = LED is steady ON.

 

 

 

CHAN1 FAULT

 

BIT0

 

CHAN1 ALARM1

BIT1

 

CHAN1 ALARM2

BIT2

 

CHAN1 ALARM3

BIT3

 

CHAN2 FAULT

 

BIT4

 

CHAN2 ALARM1

BIT5

 

CHAN2 ALARM2

BIT6

 

CHAN2 ALARM3

BIT7

 

CHAN3 FAULT

 

BIT8

 

CHAN3 ALARM1

BIT9

 

CHAN3 ALARM2

BIT10

 

CHAN3 ALARM3

BIT11

 

CHAN4 FAULT

 

BIT12

 

CHAN4 ALARM1

BIT13

 

CHAN4 ALARM2

BIT14

 

CHAN4 ALARM3

BIT15

Relay Status

31012

4

NA

 

 

 

 

Bit set to 1 = LED Blinking, bit set to 0 = LED is steady ON.

 

STANDARD RELAY 1

BIT0

 

STANDARD RELAY 2

BIT1

 

OPTION RELAY 1

BIT2

 

OPTION RELAY 2

BIT3

 

OPTION RELAY 3

BIT4

 

OPTION RELAY 4

BIT5

 

OPTION RELAY 5

BIT6

 

OPTION RELAY 6

BIT7

 

INPUT FAULT RELAY

BIT8

 

Reserved

BIT9

 

Reserved

BIT10

 

Reserved

BIT11

 

Reserved

BIT12

 

Reserved

BIT13

 

Reserved

BIT14

 

Reserved

BIT15

 

 

READ

WRITE

VARIABLE

ALIAS

FUNCTION

FUNCTION

 

 

CODE

CODE

Memory Reals:

 

 

 

 

 

 

 

Notes: 41001 – 41040 “Real” represents float value without the decimal point such that 123.4 is returned as 1234. Decimal devisor is returned as 1, 10, 100, or 1000 for decimal position of 1, 2, 3, or 4, where 123.4 would return the devisor value 10.

Chan 1 Zero Real

41001

3

NA

 

 

 

 

 

Chan 1

Zero Divisor

41002

3

NA

Chan 1 Span Real

41003

3

NA

Chan 1

Span Divisor

41004

3

NA

 

 

 

 

Chan 1 Alarm 1 Real

41005

3

NA

 

 

 

 

 

Chan 1

Alarm 1 Divisor

41006

3

NA

 

 

 

 

Chan 1 Alarm 2 Real

41007

3

NA

HA40 Technical Manual

3-8

Revision 1 (08/08)

Image 29 Contents
Technical Manual HA40 4-Channel Controller SafetyTable of Contents Operation Parts List General Description Keypad CAL in Progress General DescriptionData Display Screens SpecificationsRelays Ambient Temperature RangeHumidity Range AltitudeApprovals Housings / Installation CategoriesOperation Operation Setup Menu ConfigurationChannel Setup Entry Menu Changing Menu Variables Using the KeypadSetup Configuration Menus Configure Menu To Define Channel Fault / Alarm 1 / Alarm 2 / Alarm 3 Set-Up MenusName / Eunits Ascii Data Fields Decimal Point ResolutionInput Measurement Range Turning Off Unused ChannelsCalibrate Input Menu Cal Setup MenuStandard / Optional Relay Setup Menus System Configuration MenusComm Port Remote ID Menu Clock / Delays MenuHorn / Acknowledge Menu Analog Setup Menu12. Horn/Acknowledge Menu HA40 System Security MenuHA40 4-Channel Controller Motherboard Interface PCB Shock Hazard Motherboard Interface PCBRS-R85 / Ethernet Option Sensor Input Option Input / Output Optional PCB’sOptional Analog Input PCB Optional 4-20mA Analog Output Board Modbus RS-232 / RS-485 Interface Option Read Only Registers Variable Alias Memory Ascii Strings Enclosures HA40N4 Nema 4X Wall Mount Enclosure EnclosuresHA40XP Nema 7 Explosion-Proof Wall Parts List Base Units Parts ListSpecifications Specifications Warranty Honeywell Analytics Warranty Statement Find out more Customer business center Asia Pacific Americas