Honeywell HA40 technical manual General Description, Keypad CAL in Progress

Page 7

HA40 4-Channel Controller

1 General Description

The Honeywell Analytics HA40 Quad Channel Controller is designed

HA40 Display & Alarm Controller

Quad Channel

to display, and control alarm event switching for four inputs. Inputs are typically voltage or 4-20mA current from transmitters, monitors or other analog output devices. The HA40 is equipped with a Fault and three alarm levels per channel with features such as ON / OFF delays, latching relays and alarm Acknowledge. A dedicated horn driver circuit for a local audible annunciator is also standard. Two standard 5-amp

COMMON

LEVEL

ALARMS

ALARM 1

ALARM 2

ALARM 3

219995

STATUS

LED's

KEYPAD

CAL IN PROGRESS

FAULT ALARM

Magnetic

Next Edit Alarm Keypad

Reset (Keypad buttons

behind door)

Power = 100-240 V~, 50/60 Hz, .45 A

 

or 10-30 VDC @ 3 WATTS

S/N 90-

Classified to CSA C22.2 NO. 152 for combustibles

 

detection. Class I, DIV.2, Groups A,B,C,D

 

READ & UNDERSTAND MANUAL!

 

alarm relays are configurable via the “alarm voting” menu to make relays trip based on various alarm combinations. A real-Time Clock and Calendar are also standard. Options such as 4-20mA outputs, discrete relays for each alarm and audible annunciators are easily added. RS-485 (Modbus RTU) or Ethernet (Modbus TCP) ports are also available for sending data to PC’s, PLC’s, DCS’s, or other Honeywell Analytics controllers.

A 128 x 64 pixel graphic LCD readout displays monitored data as bar graphs, 30-minute trends and engineering units. System configuration is via user friendly menus and all configuration data is retained in non- volatile memory during power interruptions. The HA40 front panel is shown in Figure 1-1 displaying the bar graph data screen. The five keypad symbols below the display are magnetically activated using the supplied magnetic wand without opening the enclosure. Opening the enclosure door provides access to the keypad buttons as shown in Figure 1-2.

Figure 1-1. Front Panel

 

 

 

 

Piezo

Common Alarm

 

 

 

LED Indicators

Level LEDs

 

 

 

Alarm 1 LED

 

 

 

KEYPAD

Alarm 2 LED

 

 

 

CAL IN PROGRESS

Alarm 3 LED

 

 

 

FAULT ALARM

LCD readout contrast

 

 

 

 

adjustment

 

 

 

 

UP

DOWN

NEXT

EDIT

RESET

SW1-SW5 are the magnetic keypad allowing operator

interface w/o opening the enclosure. Touch key access requires

opening the enclosure.

Figure 1-2. Front Panel Display (open enclosure)

HA40 Technical Manual

1-2

Revision 1 (08/08)

Image 7 Contents
Technical Manual HA40 4-Channel Controller SafetyTable of Contents Operation Parts List General Description Keypad CAL in Progress General DescriptionData Display Screens SpecificationsAltitude Ambient Temperature RangeRelays Humidity RangeApprovals Housings / Installation CategoriesOperation Operation Setup Menu ConfigurationSetup Configuration Menus Changing Menu Variables Using the KeypadChannel Setup Entry Menu Configure Menu To Define Channel Fault / Alarm 1 / Alarm 2 / Alarm 3 Set-Up MenusTurning Off Unused Channels Decimal Point ResolutionName / Eunits Ascii Data Fields Input Measurement RangeCalibrate Input Menu Cal Setup MenuStandard / Optional Relay Setup Menus System Configuration MenusComm Port Remote ID Menu Clock / Delays MenuHorn / Acknowledge Menu Analog Setup Menu12. Horn/Acknowledge Menu HA40 System Security MenuHA40 4-Channel Controller Motherboard Interface PCB Shock Hazard Motherboard Interface PCBRS-R85 / Ethernet Option Sensor Input Option Input / Output Optional PCB’sOptional Analog Input PCB Optional 4-20mA Analog Output Board Modbus RS-232 / RS-485 Interface Option Read Only Registers Variable Alias Memory Ascii Strings Enclosures HA40XP Nema 7 Explosion-Proof Wall EnclosuresHA40N4 Nema 4X Wall Mount Enclosure Parts List Base Units Parts ListSpecifications Specifications Warranty Honeywell Analytics Warranty Statement Find out more Customer business center Asia Pacific Americas