2.Turn off the UV test lamp.
3.Repeat steps 1 & 2 for all detectors in the system.
4.After all detectors have been checked, return the system to the normal operating mode.
5.Restore power to output loads or remove any mechanical blocking devices.
CHAPTER 4 NORMAL OPERATION
Normal Operation
In normal operation the detector outputs 4mA.
Fire Condition
In a fire condition the detector outputs 20mA.
Current & Relay Output Conditions
The
10.5to 32Vdc. Table 4 shows the current output levels for various conditions.
Table 4 - Current & Relay Output Conditions
Current Output | Situation |
0mA | Shorted signal output or loss of power |
1mA | Internal power fault or system power out of range. Fault relay |
| activated on |
2mA | Automatic or manual vi test failure. Fault relay activated on |
| |
4mA | Normal operation |
6mA | Background UV source |
10mA | Manual vi test (adequate) clean all optical surfaces. |
11mA | Manual vi test (good) optical surfaces are moderately clean |
12mA | Manual vi test (excellent) all optical surfaces are clean |
16mA | Instant alarm |
20mA | Fire condition detected. Fire relay activated on |
|