Emerson UVU-140A-AR Normal Operation, Fire Condition, Current & Relay Output Conditions

Page 18

The UVU-140-A or UVU-140-AR current output will change with the amount of ultraviolet light being detected (see Table 4).

2.Turn off the UV test lamp.

3.Repeat steps 1 & 2 for all detectors in the system.

4.After all detectors have been checked, return the system to the normal operating mode.

5.Restore power to output loads or remove any mechanical blocking devices.

CHAPTER 4 NORMAL OPERATION

Normal Operation

In normal operation the detector outputs 4mA.

Fire Condition

In a fire condition the detector outputs 20mA.

Current & Relay Output Conditions

The 4-20mA DC current output transmits system information to other devices. The current output can only be wired for non-isolated operation. The current output can have a maximum external loop resistance of 600 Ohms at

10.5to 32Vdc. Table 4 shows the current output levels for various conditions.

Table 4 - Current & Relay Output Conditions

Current Output

Situation

0mA

Shorted signal output or loss of power

1mA

Internal power fault or system power out of range. Fault relay

 

activated on UVU-140-AR

2mA

Automatic or manual vi test failure. Fault relay activated on

 

UVU-140-AR

4mA

Normal operation

6mA

Background UV source

10mA

Manual vi test (adequate) clean all optical surfaces.

11mA

Manual vi test (good) optical surfaces are moderately clean

12mA

Manual vi test (excellent) all optical surfaces are clean

16mA

Instant alarm

20mA

Fire condition detected. Fire relay activated on

 

UVU-140-AR

14

Image 18
Contents UVU-140A and UVU-140-AR Unitized Ultraviolet Fire Detector Page Table of Contents Page Introduction FeaturesTechnical Information Spectral Sensitivity RangeSpecifications Operating Voltage Range 24Vdc nominal 10.5 to 32VdcApplications Response TimeInstallation What’s in the packageMounting the Detector False Alarms Position and Density of DetectorsDetector with Swivel Mount Swivel Mount General Wiring Requirements Wiring Diagram for UVU-140-A If the 4-20 mA signal is Detector Settings Coil and Relay SettingsSystem Sensitivity Start UP and Test Start up ProcedureCheck Out Procedure Automatic vi TestManual Check Procedure Manual vi Test ProcedureTest Procedures Fire Condition Normal OperationNormal Operation Current & Relay Output ConditionsTroubleshooting MaintenanceRoutine Maintenance Cleaning Viewing Window and ReflectorDevice Repair and Return B lis h ed in Accordance with E1A standard Appendix B Common Ultra-Violet Absorbing Gases Appendix C Wire Resistance In Ohms