Emerson UVU-140A-AR user manual False Alarms, Position and Density of Detectors

Page 9

between the detector and the sources of potential fires. Small concentrations of these types of gases may not absorb enough UV radiation to cause a problem, but when higher concentrations of these gases are present the detectors may become blind as not enough ultra-violet radiation can reach them to activate an alarm. Moving detectors closer to the probable source of fire and increasing the sensitivity of the detector can help to overcome this problem in some cases. For a list of some common UV absorbing chemical vapours see Appendix B.

False Alarms

Arc Welding, long duration lightning flashes, cracked mercury lamps, cracked halogen lamps, and X-rays may cause false alarms and should be avoided.

NOTE:

Ultraviolet detectors are sensitive to arc welding and if this type of radiation can be expected, nuisance alarms must be controlled through proper application including careful positioning and shielding of the detectors. Some applications may require a UV/IR system.

CAUTION:

Caution must be exercised if the detection system is turned off, as the hazardous area will not be protected. .

Lightning strikes can trigger the detector but this can be solved by pointing the sensor cone of vision below the horizon and setting the time delay to 7 seconds.

Cracked mercury or halogen lamps in the vicinity of the fire detector should be replaced as soon as they are discovered.

UV radiation other than that produced by an actual fire is referred to as “background UV”. An example of a high level of background UV could be a flare stack situated outside of a building. The UV radiation produced by this flare may be detected when a door to the building is opened. Windows or other reflective surfaces may also cause unusually high levels of UV radiation to enter the building from the flare. In a situation like this, the fire detection system response must be carefully checked and the sensitivity level adjusted high enough, so that this “background UV” will not cause false alarms.

UV fire detectors respond to radiation other than ultraviolet. X-rays can activate the detector and are often used in industrial inspection. It may be necessary to disable the system when X-ray is conducted nearby.

Position and Density of Detectors

The UVU-140-A & UVU-140-AR fire detectors have a nominal 120 degree cone of vision when measured in accordance to NFPA 72 guidelines. In an application such as a loading dock with a ceiling height of 25 feet (7.5 metres) where it is desired to have complete detector coverage at floor level and a detector is mounted 2 feet (0.6 metres) from the ceiling and pointed straight down, the distance from the detector to the designated level would be 23 feet (7 metres). The detector has a 120 degree cone of vision and would cover a circular area 80 feet (24 metres) in diameter at floor level. A sketch of the area to be covered will indicate the number of detectors required to monitor the area. Detectors should be placed as close as practical to the expected fire hazard.

NOTE:

Do not mount UV detectors close to the ceiling of enclosed buildings if smoke might accumulate before the break-out of flame. It is preferable to mount the detectors on walls a few feet (about 1

5

Image 9
Contents UVU-140A and UVU-140-AR Unitized Ultraviolet Fire Detector Page Table of Contents Page Technical Information FeaturesIntroduction Spectral Sensitivity RangeOperating Voltage Range 24Vdc nominal 10.5 to 32Vdc SpecificationsResponse Time ApplicationsInstallation What’s in the packageMounting the Detector Position and Density of Detectors False AlarmsDetector with Swivel Mount Swivel Mount General Wiring Requirements Wiring Diagram for UVU-140-A If the 4-20 mA signal is Detector Settings Coil and Relay SettingsSystem Sensitivity Check Out Procedure Start up ProcedureStart UP and Test Automatic vi TestManual Check Procedure Manual vi Test ProcedureTest Procedures Normal Operation Normal OperationFire Condition Current & Relay Output ConditionsRoutine Maintenance MaintenanceTroubleshooting Cleaning Viewing Window and ReflectorDevice Repair and Return B lis h ed in Accordance with E1A standard Appendix B Common Ultra-Violet Absorbing Gases Appendix C Wire Resistance In Ohms