Emerson UVU-140A-AR user manual Manual Check Procedure, Manual vi Test Procedure, Test Procedures

Page 17

Manual vi Test Procedure

The detector has a manual vi input. The manual vi test is performed by connecting this input to the system power for the duration of the test. This can be done by connecting a momentary contact pushbutton between system power and the manual vi input, and then holding the pushbutton to perform the test.

NOTE:

The manual vi feature is optional on the UVU-140-A (If not used, leave unconnected or tied to system common).

CAUTION:

The detector will stay in the manual vi test mode as long as the manual vi input is held at the system power voltage. During the manual vi test all other detector functions are disabled. It is therefore imperative that, after this test is performed, the manual vi test input be released.

Test Procedures:

1.Connect the manual vi test input (UVU-140-A) terminal to system power by either a direct connection or a manual push button.

NOTE:

On UVU-140-AR detectors, connect the MVI signal output terminal (on the JBR-T relay box) to system power by either a direct connection or a manual push button.

CAUTION:

DO NOT connect system power to the blue wire on the UVU-140-AR detector. Doing so will damage

the fire detector.

2.Hold the manual vi input at this voltage for at least two seconds.

3.Two seconds after the test has commenced, the detector will have a current output that corresponds to the quality of the vi reading obtained (see Table 4).

4.Release the manual vi test input. The detector will immediately return to normal operation if a vi fault is not present.

5.If a vi fault is present, the current output will indicate 2mA.

Manual Check Procedure

The whole system should be checked periodically with a UV test lamp to make sure that the detectors are not obstructed, that the area ‘seen’ by the detector has not changed and that there is no fault in the vi circuit.

CAUTION:

Secure all output loads connected to the fire detector to prevent unwanted activation.

1.Direct the UV test lamp into the detector viewing window.

13

Image 17
Contents UVU-140A and UVU-140-AR Unitized Ultraviolet Fire Detector Page Table of Contents Page Technical Information FeaturesIntroduction Spectral Sensitivity RangeOperating Voltage Range 24Vdc nominal 10.5 to 32Vdc SpecificationsResponse Time ApplicationsMounting the Detector InstallationWhat’s in the package Position and Density of Detectors False AlarmsDetector with Swivel Mount Swivel Mount General Wiring Requirements Wiring Diagram for UVU-140-A If the 4-20 mA signal is System Sensitivity Detector SettingsCoil and Relay Settings Check Out Procedure Start up ProcedureStart UP and Test Automatic vi TestTest Procedures Manual Check ProcedureManual vi Test Procedure Normal Operation Normal OperationFire Condition Current & Relay Output ConditionsRoutine Maintenance MaintenanceTroubleshooting Cleaning Viewing Window and ReflectorDevice Repair and Return B lis h ed in Accordance with E1A standard Appendix B Common Ultra-Violet Absorbing Gases Appendix C Wire Resistance In Ohms