BRK electronic HD6135FB user manual Locking Features, To Lock the Battery Compartment

Page 3

SPECIAL REQUIREMENTS FOR INTERCONNECTED HEAT ALARMS

Failure to meet any of these requirements could damage the units and cause them to malfunction, removing your protection.

Interconnected units can provide earlier warning of fire than stand-alone units, especially if a fire starts in a remote area of the dwelling. If any unit in the series senses heat, all units will alarm.

Interconnect units within a single family residence only. Otherwise all households will experience unwanted alarms when you test any unit in the series. Interconnected units will only work if they are wired to compatible units and all requirements are met. This unit is designed to be compatible with:

First Alert® Smoke Alarm Models SA4120, SA4121B, SA4919B, SA100B and BRK Electronics® Smoke Alarm Models 100S, 2002RAC, 4120, 4120B, 4120SB, 4919, 5919, 5919TH; BRK Electronics® Smoke/CO Alarm Model SC6120B.

Interconnected units must meet ALL of the following requirements:

A maximum of 18 compatible Smoke, Heat or CO Alarms may be interconnected. To comply with NFPA limits, no more than 12 of the 18 alarms may be Smoke Alarms.

The same fuse or circuit breaker must power all interconnected units.

All wiring must conform to all local electrical codes and Article 760 of the National Electrical Code. Refer to NFPA, Chapter 2 and/or your local building code for further connection requirements.

A}

6

} B

7

 

8

 

5

5

 

4

4

 

3

3

 

2

 

 

1

1

 

A. Unswitched 120VAC B. To additional units; Maximum = 18 total

 

60 Hz source

 

(Maximum 12 Smoke Alarms)

 

 

 

 

 

 

1.

Heat Alarm

4.

Wire Nut

7.

Interconnect Wire

2.

Ceiling or Wall

5.

Junction Box

 

(Orange)

8.

Hot Wire (Blk)

3. Power Connector

6. Neutral Wire (Wht)

 

 

 

 

 

 

 

 

LOCKING FEATURES

The locking features are designed to discourage unauthorized removal of the battery or alarm. It is not necessary to activate the locks in single-family households where unauthorized battery or alarm removal is not a concern.

These Heat Alarms have two separate locking features: one to lock the battery

compartment, and the other to lock the Heat Alarm to the mounting bracket. Locking Pin You can choose to use either feature independently, or use them both.

Tools you will need: Needle-nose pliers or utility knife

Standard/Flathead screwdriver.

Both locking features use locking pins, which are molded into the mounting bracket. Using needle nose pliers or a utility knife, remove one or both pins from the mounting bracket, depending on how many locking features you want to use.

To permanently remove either lock insert a flathead screwdriver between the locking pin and the lock, and pry the pin out of the lock.

TO LOCK THE BATTERY COMPARTMENT

Do not lock the battery compartment until you have activated the battery and tested the battery back-up.

1. Activate the battery back-up by removing the “Pull to Activate Battery Back-Up” tab.

DO NOT remove the battery activation until AC power is turned on to conserve battery power.

2.Press the Test/Silence button until you hear a brief acknowledge (or feedback) chirp. The alarm will sound: 3 beeps, pause, 3 beeps, pause.

If the unit does not alarm during testing, DO NOT lock the battery compartment! Install a new battery and test again. If the Heat Alarm still does not alarm, replace it immediately.

3. Using needle-nose pliers or a utility knife, detach one locking pin from the mounting bracket.

4. Push the locking pin through the black dot on the label on the back of the Heat Alarm.

TO UNLOCK THE BATTERY COMPARTMENT

Once the Heat Alarm is installed, you must disconnect it from the AC power before unlocking the battery compartment.

ELECTRICAL SHOCK HAZARD. Turn off the power to the area where the Heat Alarm is installed before removing it from the mounting bracket. Failure to turn off the power first may result in serious electrical shock, injury or death.

Turn off the AC power at the circuit breaker or fuse box.

1.Remove the Heat Alarm from the mounting bracket. If the unit is locked to the bracket, see the section “To Unlock the Mounting Bracket.”

2.Disconnect the power connector by gently prying it away from the back of the Heat Alarm.

3.Insert a flathead screwdriver under the head of the locking pin,

and gently pry it out of the battery compartment lock. (If you plan to relock the battery compartment, save the locking pin.)

4. To relock the battery compartment, close the battery door and reinsert locking pin in lock.

5. Reconnect the power connector to the back of the Alarm, reattach the Heat Alarm to the mounting bracket, and restore the power.

When replacing the battery, always test the Heat Alarm before relocking the battery compartment.

3

Image 3
Contents Before YOU Install this Heat Alarm Table of ContentsBasic Features Fire Safety TipsParts of this Heat Alarm HOW this Heat Alarm WorksHOW to Install this Heat Alarm Follow These Installation StepsSpecial Requirements for Interconnected Heat Alarms Locking FeaturesTo Lock the Battery Compartment To Unlock the Battery CompartmentIf YOU Suspect a Problem Weekly TestingIf this Heat Alarm Sounds Avoiding Dead AIR Spaces Recommended Locations for Heat AlarmsLocations to Avoid for Heat Alarms Single-Family ResidencesLimitations of Heat Alarms Limited WarrantySpecial Compliance Considerations

HD6135FB specifications

The BRK electronic HD6135FB is an advanced electronic smoke and carbon monoxide alarm designed to provide reliable safety and peace of mind to households and businesses. This state-of-the-art device combines innovative technology with user-friendly features ensuring enhanced protection against deadly smoke and toxic gases.

One of the standout features of the HD6135FB is its dual sensor technology, which utilizes both photoelectric and ionization sensors. This combination allows for improved detection of different types of fires, including smoldering fires and fast-flaming fires. The photoelectric sensor effectively identifies slow-burning fires that produce large amounts of smoke, while the ionization sensor is quick to respond to fast-flaming fires. This integrated approach significantly increases the overall effectiveness and reliability of the alarm.

In addition to fire detection, the HD6135FB excels in carbon monoxide detection. CO is often referred to as the silent killer, as it is colorless and odorless, making it undetectable without a proper alarm system. The HD6135FB is equipped with a sensitive electrochemical sensor that identifies dangerous levels of carbon monoxide, ensuring timely alerts to occupants.

The alarm is designed with user convenience in mind. It features a built-in voice alarm that announces the type of danger detected, whether it’s smoke or carbon monoxide. This feature helps users swiftly identify the source of danger without confusion. Additionally, the alarm is equipped with a lithium battery backup, ensuring continuous operation during power outages and enhancing its reliability.

Installation of the HD6135FB is straightforward, with the option to be mounted on walls or ceilings. Its sleek design ensures that it blends seamlessly into any environment. The device also includes a test button for regular function checks, providing peace of mind that the unit is working correctly.

Furthermore, the HD6135FB has an advanced LED indicator that displays the status of the alarm. A green light indicates normal operation, while a red light alerts users to an active alarm condition. This visual feedback is crucial for quickly assessing the status of the device.

In summary, the BRK electronic HD6135FB smoke and carbon monoxide alarm combines dual sensor technology, reliable monitoring, and user-friendly features. Its robust design and advanced alert systems make it an essential addition to any safety plan, helping to protect lives and property from the dangers of fire and carbon monoxide exposure.