A. Gas Log/Lighter Provision

WARNING! Fire and/or Asphyxiation Risk! Use with solid wood fuel or decorative gas appliance only. Gas fire generates fumes.

DO NOT install unvented gas logs

Damper must be locked fully open when gas logs are installed

A certified gas log lighter or decorative gas log set can be installed in this fireplace.

Maximum input is 100,000 BTU/hr.

Decorative gas appliance must be certified to ANSI Z21.60 “Standard for Decorative Gas Appliances for Installation in Vented Fireplaces”.

Must be installed in accordance with the National Fuel

Gas Code, ANSI Z223.1.

A gas log set must incorporate a gas shutoff.

Gas log set requires the damper to be locked fully open.

A listed automatic damper system with safety interlock may be used in this fireplace with only compatible, listed gas log sets. See damper system manufacturer’s instructions.

Knockouts are provided on both sides of the fireplace and in refractories for 1/2 in. (13 mm) iron pipe.

Seal refractory around pipe with fireplace mortar or a non-combustible sealant.

B. Wood Burning Inserts

WARNING! Risk of Fire! Improper installation of wood in- serts may cause fireplace or chimney system to overheat.

If a wood burning insert is being installed in this fireplace, Hearth & Home Technologies recommends full reline of the chimney.

Cooling air openings at the top of the chimney must not be obstructed in any manner.

Hearth & Home Technologies recommends securing the reline at the top of the flue and using the cap certified for use with this fireplace system.

Firebox

Refractory

Seal with fireplace mortar or non-combust- ible sealant

Outer Shell

of Fireplace

Maintain air clearance to combustibles.

Combustible

Materials

Gas Line

Repack

Insulation

Knockout

Gas Line

4 in. (102 mm)

1 1/2 in. (38 mm) air space around

pipe

Combustible materials may be located at zero clearance to gas line beyond 4 in. (102 mm) from fireplace side.

Figure 12.1 Gas Line Installation

Heatilator • SC60 • 32838 • Rev Y • 11/08 WIP

41

Image 41
Contents Fire Risk Wood Burning FireplaceHot screen/mesh and glass doors will cause burns Number Listing Label Information/LocationGrate User Guide Table of ContentsInstaller Guide CONDITIONS, Exclusions & Limitation of Liability Hearth & Home Technologies Limited WarrantyHeatilator SC60 32838 Rev Y 11/08 WIP Appliance Certification Listing and Code ApprovalsNon-Combustible Materials Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Starting a Fire Seasoned WoodGrate FirescreenVented Gas Log Sets & Gas Log Lighters Glass DoorsOptional Components Clear SpaceWood Fuel Chimney Inspection/Cleaning Maintainance and ServiceDisposal of Ashes Creosote Formation and Need for RemovalCheck Firebrick Glass CleaningInspect Grate Frequency As desiredStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedNegative Pressure Design and Installation ConsiderationsDraft Frequently open doors Central heat outlets or returns Locating Fireplace & ChimneyInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Select Fireplace Location Framing & ClearancesClearances to Combustible Materials ClearancesFrame the Fireplace Sidewalls/SurroundsThings to Consider Installation of FireplacePosition the Fireplace Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet To service or replace the fan kit Install Outside Air KitChimney Assembly Height of Chimney Components Chimney RequirementsExample Using Offsets/ReturnsAssemble Chimney Sections Install Chimney Air KitInstall Ceiling Firestops Prepare Attic Insulation Shield Install Attic Insulation ShieldInstall Flashing Complete InstallationFollowing steps should be skipped if using a chase Cut out Hole in RoofFlat Roofs Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyST375 Square Termination Cap Install Termination CapTS345/TS345P Square Termination Cap Radiation Shield ShroudsField Constructed Shrouds Open Top Shroud TR342 caps require radiation shieldRoofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield required= 1/k x inches of thickness FinishingHearth Extension HX3 or HX4 Hearth Ext or equivilent insulation Finishing MaterialCombustible Mantel 13 Side Brick Installation Firebrick InstallationGas Log/Lighter Provision AccessoriesWood Burning Inserts Gas Code, Ansi Z223.1Fireplace Materials1321 mm 406 mm Catalog # Chimney Components14-1/2 10-7/8 276 mm Part number list on following PartsContact Information