T8611G CHRONOTHERM® IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
TROUBLESHOOTING GUIDE
Table 6. Troubleshooting Guide.
Symptom | Possible Cause |
| Action | |
Display will not | Thermostat is not being | • | Check for 24 Vac between R and C terminals. | |
come on. | powered. |
| — If missing 24 Vac: | |
|
|
| — check if the circuit breaker is | |
|
|
| breaker. | |
|
|
| — check if the system fuse is | |
|
|
| — check if the power switch on the HVAC equipment is in | |
|
|
| the Off | |
|
|
| — check wiring between thermostat and HVAC | |
|
|
| ||
|
|
| loose connections. | |
|
|
| — If 24 Vac is present, proceed with troubleshooting | |
Temperature | Room temperature display has | Enter Installer Setup number 37 and reconfigure the display. | ||
display is incorrect. | been reconfigured. |
|
| |
| Thermostat is configured for °F | Enter Installer Setup number 14 and reconfigure the display. | ||
| or °C display. |
|
| |
| Bad thermostat location. | Relocate the thermostat. | ||
|
|
| ||
Temperature | The upper or lower temperature | Check the temperature setpoints: | ||
settings will not | limits were reached. | • | Heating limits are 40 to 90°F (4.5 to 32°C) | |
change. (Example: |
| • | Cooling limits are 48 to 99°F (7 to 37°C) | |
Cannot set the |
|
|
| |
The setpoint temperature range | Check Installer Setup numbers 34 and 35 and reconfigure the | |||
heating higher or | ||||
stops were configured. | setpoint stops. | |||
the cooling lower.) | ||||
|
|
| ||
|
|
|
| |
Heating will not | No power to the thermostat. | • | Check for 24 Vac between R and C terminals. | |
come on. |
|
| — If missing 24 Vac: | |
|
|
| — check if the circuit breaker is | |
|
|
| breaker. | |
|
|
| — check if the system fuse is | |
|
|
| — check if the power switch on the HVAC equipment is in | |
|
|
| the Off | |
|
|
| — check wiring between thermostat and HVAC | |
|
|
| ||
|
|
| loose connections. | |
|
|
| — If 24 Vac is present, proceed with troubleshooting. | |
| Thermostat minimum off time is | Wait up to five minutes for the system to respond. | ||
| activated. |
|
| |
| System selection is not set to | Set system selection to Heat. | ||
| Heat. |
|
| |
| Heating setpoint is below room | Check heating setpoint. Set heating setpoint to desired | ||
| temperature. | temperature. | ||
Cooling will not | No power to the thermostat. | • | Check for 24 Vac between R and C. | |
come on. |
|
| — If missing 24 Vac: | |
|
|
| — check if the circuit breaker is | |
|
|
| breaker. | |
|
|
| — check if the system fuse is | |
|
|
| — check if the power switch on the HVAC equipment is in | |
|
|
| the Off | |
|
|
| — check wiring between thermostat and HVAC | |
|
|
| ||
|
|
| loose connections. | |
|
|
| — If 24 Vac is present, proceed with troubleshooting. | |
| Thermostat minimum off time is | • | Wait up to five minutes for the system to respond. | |
| activated. | • | Enter Installer Setup number 33. Reconfigure minimum off | |
|
|
| time (if required). | |
| System selection is not set to | Set system selection to Cool. | ||
| Cool. |
|
| |
| Cool setpoint is above room | Check cooling setpoint. Set cooling setpoint to desired | ||
| temperature. | temperature. |