Trane XT302C manual Device Information SELF-TEST, Checkout, Troubleshooting Guide

Page 10

XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

DEVICE INFORMATION

SELF-TEST (70)

1. Press Temp ▲ and ▼ keys simultaneously, then press Time ▼ to access the thermostat information.

M4934

2. Press Increase ▲ to display the production date code

in a 3-digit format. The first two digits represent the month and the third digit represents the last digit of the year (Example: 128=December 1998).

M17112

3. Press Increase ▲ again to display the software identification code.

(Example: 200 = software ID code 200)

M17113

4. Press Increase ▲ again to display the software revision number (Example: 001=Revision number 1).

M10229

5. Press the Increase ▲ again to display the model identification number. (Example: 314 = Model ID 314)

M4933A

6. Press Run Program to exit the self-test. The self-test

mode times out 5 minutes after the last key press.

CHECKOUT

Outdoor Temperature Sensor (optional accessory)

Expose the outdoor temperature to outdoor air for a minimum of five minutes before reading.

TROUBLESHOOTING GUIDE

Symptom

Possible Cause

Action

 

 

 

Display will not come

Thermostat is not being

Check for 24 Vac between R and W terminals.

on.

powered.

Check if the circuit breaker is tripped—reset the circuit breaker.

 

 

Check if the system fuse is blown—replace the fuse.

 

 

Check if the power switch on the HVAC equipment is in the

 

 

Off position—set to the On position.

 

 

Check wiring between thermostat and HVAC equipment—replace any

 

 

broken wires and tighten any loose connections.

 

 

If 24 Vac is present, proceed with troubleshooting.

 

 

 

Temperature display is

Room temperature

Enter Installer Setup number 37 and reconfigure the display.

incorrect.

display has been

 

 

reconfigured.

 

 

 

 

 

Thermostat is configured

Enter Installer Setup number 14 and reconfigure the display.

 

for °F or °C display.

 

 

Bad thermostat location.

Relocate the thermostat.

 

 

 

Temperature

Internal temperature

Contact distributor or retailer.

displaying digits as

measurement failure.

 

dashes (---).

 

 

 

 

 

Temperature settings

The upper or lower

Check the temperature setpoints:

will not change.

temperature limits were

Heating limits are 55 to 85°F (13 to 29°C).

(Example:

reached.

Cooling limits are 65 to 99°F (18 to 37°C).

Cannot set the

The setpoint temperature

Check Installer Setup numbers 34 and 35 and reconfigure the

heating higher or the

range stops were

setpoint stops.

cooling lower.)

configured.

 

 

 

 

 

 

 

 

(continued)

Pub. No. 18-HD25D7-5

 

 

69-1213—1 (T8624)

10

Image 10
Contents When Installing this Thermostat InstallationWallplate Installation ApplicationWiring Mounting ThermostatUsing Thermostat Keys SettingsSystem and Fan Settings Installer Setup Procedure Installer SetupTemperature Settings Default Program Settings Heat Cool Fan Period Time SetpointCph not Bypass Go directly To setup #42Press Time to RecommendedMinimum number of minutes Setting Current Day and Time Press Set Current Day/TimePress Run Program Installer SELF-TESTTests Available In The Installer Self-Test To start the self-testTemp Installer Self-Test OptionsSettings Wake Cooling Equipment Self-Test TimeDevice Information SELF-TEST Troubleshooting GuideSymptom Possible Cause Action CheckoutTroubleshooting American Standard Inc