Trane XT302C Installer Self-Test Options, Temp, Cooling Equipment Self-Test Time, Day, Copy, Set

Page 9

 

 

 

 

XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

 

 

 

 

 

 

 

 

Table 5. Installer Self-Test Options.

 

 

 

 

 

Key to

Test

 

 

 

Press

Number

Description

 

 

 

 

 

 

 

Heating Equipment Self-Test (10)

 

 

 

 

 

 

Time ▲

10

 

Enter heating equipment self-test.

 

 

 

 

Temp ▲

11

 

First stage heat turns on. When Installer Setup number 2 is 1, the system fan is also energized.

 

 

 

 

 

Temp ▲

12

 

Second stage heat

turns on.

 

 

 

 

 

Temp ▼

11

 

Second stage heat

turns off.

 

 

 

 

Temp ▼

10

 

First stage heat turns off.

 

 

 

 

 

Cooling Equipment Self-Test (30)

 

 

 

 

 

 

Time ▲

30

 

Enter cooling equipment self-test.

 

 

 

 

Temp ▲

31

 

First stage cool and fan turn on.

 

 

 

 

 

Temp ▲

32

 

Second stage cool

turns on.

 

 

 

 

 

Temp ▲

31

 

Second stage cool

turns off.

 

 

 

 

Temp ▼

30

 

First stage cool and fan turn off.

 

 

 

 

 

Fan Equipment Self-Test (40)

 

 

 

 

 

 

Time ▲

40

 

Enter fan equipment self-test.

 

 

 

 

 

 

Temp ▲

41

 

Fan turns on.

 

 

 

 

 

 

 

 

Temp ▼

40

 

Fan turns off.

 

 

 

 

 

 

 

Comfort-R Terminals Self-Test (50)

 

 

 

 

 

 

Temp ▲

50

 

Enter Comfort-R self-test.

 

 

 

 

Temp ▼

51

 

Reads HH terminals. If the terminals are open and Comfort-R is enabled, display reads

 

 

 

% humidity. If the terminals are closed no % humidity displays.

 

 

 

 

 

Keyboard Operation Self-Test (60)

 

 

 

 

 

 

Time ▲

60

7

Enter keyboard operation self-test.

 

 

 

 

Temp ▲

60

9

Increase test number displays.

 

 

 

 

Temp ▼

60

8

Decrease test number displays.

 

 

 

 

Day

60

11

Day test number displays.

 

 

 

 

Copy

60

12

Copy test number displays.

 

 

 

 

System

60

3

System test number displays.

 

 

 

 

Fan

60

10

Fan test number displays.

 

 

 

 

Set

60

1

Set Current Day/Time test number displays.

Current

 

 

 

 

 

Day/Time

 

 

 

 

 

 

 

 

 

Run

60

15

Run Program test number displays.

Program

 

 

 

 

 

 

 

 

 

Daylight

60

19

Daylight Time test number displays.

Time

 

 

 

 

 

 

 

 

 

Heat/ Cool

60

5

Heat/Cool Settings test number displays.

Settings

 

 

 

 

 

 

 

 

 

Wake

60

0

Wake test number displays.

 

 

 

 

Leave

60

14

Leave test number displays.

 

 

 

 

Return

60

16

Return test number displays.

 

 

 

 

Sleep

60

2

Sleep test number displays.

 

 

 

 

Filter

60

17

Filter test number displays.

i60 13 Information test number displays.

Device Information Self-Test (70) - Refer to following section.

Pub. No. 18-HD25D7-5

9

69-1213—1 (T8624)

Image 9
Contents Wallplate Installation InstallationWhen Installing this Thermostat ApplicationMounting Thermostat WiringSettings Using Thermostat KeysSystem and Fan Settings Temperature Settings Installer SetupInstaller Setup Procedure Default Program Settings Heat Cool Fan Period Time SetpointPress Time to Bypass Go directly To setup #42Cph not RecommendedMinimum number of minutes Press Set Current Day/Time Setting Current Day and TimeTests Available In The Installer Self-Test Installer SELF-TESTPress Run Program To start the self-testSettings Wake Installer Self-Test OptionsTemp Cooling Equipment Self-Test TimeSymptom Possible Cause Action Troubleshooting GuideDevice Information SELF-TEST CheckoutTroubleshooting American Standard Inc