| XT302C DELUXE PROGRAMMABLE | |
|
|
|
|
TROUBLESHOOTING (Continued). | |||
|
|
|
|
Symptom | Possible Cause | Action |
|
|
|
|
|
Heating will not come | No power to the | Check for 24 Vac between R and W terminals. |
|
on. | thermostat. | If missing 24 Vac: |
|
|
| Check if the circuit breaker is |
|
|
| Check if the system fuse is |
|
|
| Check if the power switch on the HVAC equipment is in the Off |
|
|
|
| |
|
| Check wiring between thermostat and HVAC |
|
|
|
| |
|
| connections. |
|
|
| If 24 Vac is present, proceed with troubleshooting. |
|
|
|
|
|
Heating will not come | Thermostat minimum off | Wait up to five minutes for the system to respond. |
|
on. | time is activated. |
|
|
|
|
|
|
| System selection is not | Set system selection to Heat. |
|
| set to Heat. |
|
|
|
|
|
|
| Heating setpoint is below | Check heating setpoint. Set heating setpoint to desired temperature. |
|
| room temperature. |
|
|
|
|
|
|
Cooling will not come | No power to the | Check for 24 Vac between R and W terminals. |
|
on. | thermostat. | If missing 24 Vac: |
|
|
| Check if the circuit breaker is |
|
|
| Check if the system fuse is |
|
|
| Check if the power switch on the HVAC equipment is in the |
|
|
| Off |
|
|
| Check wiring between thermostat and HVAC |
|
|
| broken wires and tighten any loose connections. |
|
|
| If 24 Vac is present, proceed with troubleshooting. |
|
|
|
|
|
| Thermostat minimum off | Wait up to five minutes for the system to respond. Enter Installer Setup |
|
| time is activated. | number 39. Reconfigure minimum off time (if required). |
|
|
|
|
|
| System selection is not | Set system selection to Cool. |
|
| set to Cool. |
|
|
| Cool setpoint is above | Check cooling setpoint. Set cooling setpoint to desired temperature. |
|
| room temperature. |
|
|
|
|
|
|
Heating or cooling | Heat or cool circuit is | Add resistor in parallel with load or install interface relay. |
|
come on momentarily | opening up or becoming |
|
|
and shut off | high impedance. |
|
|
|
|
|
|
System on indicator | Heating equipment turns | Wait a minute after seeing the on indicator and then check the registers. |
|
(flame=heat, | on the fan when the |
|
|
snowflake=cool) | furnace has warmed up |
|
|
displays, but no | to a setpoint. |
|
|
warm or cool air is | Heating or cooling | Verify operation of heating or cooling equipment in |
|
coming from the | equipment is not |
|
|
registers. | operating. |
|
|
|
|
|
|
Outdoor temperature | Option not activated. | Enter Installer Setup number 24 and set to 1. Thermostat must have OT |
|
not displayed |
| terminals and a TAYSENS100A installed. |
|
or is incorrect. | Outdoor sensor is | Refer to TAYSENS100A installation instructions and check wiring |
|
|
| ||
| connected incorrectly. | between the thermostat and sensor. |
|
|
|
|
|
| Wrong sensor. | Replace sensor with TAYSENS100A sensor. |
|
|
|
|
|
| Filter expired. | Refer to the Filter Indication section in the Owner’s Guide, Pub. |
|
|
| No. |
|
|
|
|
|
System on indicator | Filter expired. | Refer to the Filter Indication section. |
|
reads Filter and |
|
|
|
backlight is flashing. |
|
|
|
|
|
|
|
Time displaying digits | Internal memory failure. | Contact distributor or retailer. |
|
as three E’s (EEE). |
|
|
|
|
|
|
|