Trane Comprehensive Troubleshooting for Your Thermostat

Page 11

 

 

XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

 

 

 

 

TROUBLESHOOTING (Continued).

 

 

 

 

Symptom

Possible Cause

Action

 

 

 

 

 

Heating will not come

No power to the

Check for 24 Vac between R and W terminals.

 

on.

thermostat.

If missing 24 Vac:

 

 

 

Check if the circuit breaker is tripped—reset the circuit breaker.

 

 

 

Check if the system fuse is blown—replace the fuse.

 

 

 

Check if the power switch on the HVAC equipment is in the Off

 

 

 

position—set to the On position.

 

 

 

Check wiring between thermostat and HVAC

 

 

 

equipment—replace any broken wires and tighten any loose

 

 

 

connections.

 

 

 

If 24 Vac is present, proceed with troubleshooting.

 

 

 

 

 

Heating will not come

Thermostat minimum off

Wait up to five minutes for the system to respond.

 

on.

time is activated.

 

 

 

 

 

 

 

System selection is not

Set system selection to Heat.

 

 

set to Heat.

 

 

 

 

 

 

 

Heating setpoint is below

Check heating setpoint. Set heating setpoint to desired temperature.

 

 

room temperature.

 

 

 

 

 

 

Cooling will not come

No power to the

Check for 24 Vac between R and W terminals.

 

on.

thermostat.

If missing 24 Vac:

 

 

 

Check if the circuit breaker is tripped—reset the circuit breaker.

 

 

 

Check if the system fuse is blown—replace the fuse.

 

 

 

Check if the power switch on the HVAC equipment is in the

 

 

 

Off position—set to the On position.

 

 

 

Check wiring between thermostat and HVAC equipment—replace any

 

 

 

broken wires and tighten any loose connections.

 

 

 

If 24 Vac is present, proceed with troubleshooting.

 

 

 

 

 

 

Thermostat minimum off

Wait up to five minutes for the system to respond. Enter Installer Setup

 

 

time is activated.

number 39. Reconfigure minimum off time (if required).

 

 

 

 

 

 

System selection is not

Set system selection to Cool.

 

 

set to Cool.

 

 

 

Cool setpoint is above

Check cooling setpoint. Set cooling setpoint to desired temperature.

 

 

room temperature.

 

 

 

 

 

 

Heating or cooling

Heat or cool circuit is

Add resistor in parallel with load or install interface relay.

 

come on momentarily

opening up or becoming

 

 

and shut off

high impedance.

 

 

 

 

 

 

System on indicator

Heating equipment turns

Wait a minute after seeing the on indicator and then check the registers.

 

(flame=heat,

on the fan when the

 

 

snowflake=cool)

furnace has warmed up

 

 

displays, but no

to a setpoint.

 

 

warm or cool air is

Heating or cooling

Verify operation of heating or cooling equipment in self-test.

 

coming from the

equipment is not

 

 

registers.

operating.

 

 

 

 

 

 

Outdoor temperature

Option not activated.

Enter Installer Setup number 24 and set to 1. Thermostat must have OT

 

not displayed

 

terminals and a TAYSENS100A installed.

 

or is incorrect.

Outdoor sensor is

Refer to TAYSENS100A installation instructions and check wiring

 

 

 

 

connected incorrectly.

between the thermostat and sensor.

 

 

 

 

 

 

Wrong sensor.

Replace sensor with TAYSENS100A sensor.

 

 

 

 

 

 

Filter expired.

Refer to the Filter Indication section in the Owner’s Guide, Pub.

 

 

 

No. 22-5127-04

 

 

 

 

 

System on indicator

Filter expired.

Refer to the Filter Indication section.

 

reads Filter and

 

 

 

backlight is flashing.

 

 

 

 

 

 

 

Time displaying digits

Internal memory failure.

Contact distributor or retailer.

 

as three E’s (EEE).

 

 

 

 

 

 

 

Pub. No. 18-HD25D7-5

11

69-1213—1 (T8624)

Image 11
Contents Application InstallationWallplate Installation When Installing this ThermostatMounting Thermostat WiringSystem and Fan Settings SettingsUsing Thermostat Keys Default Program Settings Heat Cool Fan Period Time Setpoint Installer SetupTemperature Settings Installer Setup ProcedureRecommended Bypass Go directly To setup #42Press Time to Cph notMinimum number of minutes Press Set Current Day/Time Setting Current Day and TimeTo start the self-test Installer SELF-TESTTests Available In The Installer Self-Test Press Run ProgramCooling Equipment Self-Test Time Installer Self-Test OptionsSettings Wake TempCheckout Troubleshooting GuideSymptom Possible Cause Action Device Information SELF-TESTTroubleshooting American Standard Inc