Sinclair ASH-13AK, ASH-09AK service manual Failure and analysis

Page 34

9Failure and analysis

Note: When replacing the controller, make sure insert the wire jumper into the new controller, otherwise, the running indicator off 3s, blink 15 times, (the dual eight will display C5) but cannot turn on the unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The breaker trips at once when it

 

 

 

 

 

 

 

Measure insulation resistance to ground to see

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is set to "ON".

 

 

 

 

 

 

 

if there is any leakage.

 

 

 

 

 

 

 

Trip of breaker or blow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The circuit or the part of the air conditioner has

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

malfunction. They heat and break the insulation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The breaker trips in few minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and lead to short circuit or creepage. Measure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when it is set to "ON"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the insulation resistance or eliminate the malfunc-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion one by one . If the breaker itself has

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

malfunction, then replace the breaker.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No power

 

 

 

 

 

 

 

Check power supply circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power plug is not well plugged in and poor con-

 

 

 

 

 

Check if the plug is properly plugged in and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nection

 

 

 

 

 

 

 

make the loose contact firm.

 

 

start

 

 

 

 

The

air conditioner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

not

 

 

 

 

does not react after

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

it is powered ( after

 

 

 

 

 

Fuse of controller burnt out

 

 

 

 

 

 

 

Change controller fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

can

 

 

 

 

the plug is inserted,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

conditioner

 

 

 

 

the

buzzer does

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The transformer connection is loose or has bad

 

 

 

 

 

 

 

Fasten the wiring; measure the output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

not sound and the

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage of the transformer, if it is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contact or the transformer has malfunction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote startup

has

 

 

 

 

 

 

 

 

 

 

 

 

 

incorrect, change the transformer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

no response)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller is broken

 

 

 

 

 

 

 

Check remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller is short of power

 

 

 

 

 

 

 

Change batteries

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

does not receive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signals

(after

it is

 

 

 

 

 

 

 

Remote controller malfunction

 

 

 

 

 

 

 

First, press the manual switch button AUTO,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

if there is no response,check based on the

 

 

 

 

 

 

powered,

the

buzzer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

above methods. If it runs normally after

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

will

sound, unless it

 

 

 

 

 

Receiver loose or poor connection

 

 

 

 

 

 

 

pressing the button,check again whether the

 

 

 

 

 

 

has

malfunction)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

installation position and the connection wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the reception head is correct. If it is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Receiver is broken

 

 

 

 

 

 

 

correct,then replace the receiver or the re-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power voltage is too low

 

 

 

heck the voltage. If it is lower than 10£¥ of the rated voltage, check the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cause, improve the power supply condition and add the stabilized voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

powersupply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller

malfunction (IC2003 broken,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

creepage of

 

parallel capacitor of relay loop,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Change controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relay is broken etc.)

 

 

 

 

 

In cool, heat mode,the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor

 

 

 

 

 

 

Wire loose or wrong connection

 

 

 

Correctly wire according to the drawing

 

 

 

unit and compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

will not run.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Improper setting of temperature

 

 

Adjust setting temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 34
Contents ASH-09AK, ASH-13AK Page 1Ph 220~240V 50Hz R410aTechnical specifications Highly Indoor unit Outdoor unitOutline and installation dimension Outline and installation dimensions of outdoor unit Electrical circuit diagram 2Basic Functions Protection Other controls Page Manual 2 of functions of remote controller RunStop Noise Silencing Protection Turbo function Disassemble the guide louver Disassemble the front panel, filterDisassemble the front case Disassemble the electric box Disassemble the electric coverDisassemble water tray Disassembling the evaporator Disassembling motor and cross flow fanDisassemble the front panel, filter Support Disassembling the evaporator Conventional 09 Disassembly procedures for indoor unit Disassemble the electric box cover Disassembling the evaporator Conventional 12 Disassembly procedures for indoor unit Disassemble the Light Board and electric cover Disassembling the evaporator Disassemble Top Cover Disassemble Big HandleDisassemble Rear Grill Disassemble Right Side Plate Disassemble Front PanelDisassemble Electric Box Disassemble Motor and Motor Support Disassemble Axial Flow FanDisassemble Four-way Valve Disassemble Gas and Liquid Valves Disassemble CapillaryDisassemble Compressor Failure and analysis Is good. Heat insulation must also be provided for Wrong connection Re-wrap and make it tight Page King Series Page Contents ASH-09AK ASH-09AK Indoor Unit ASH-13AK ASH-13AK Indoor Unit Explosive view and spare parts list of outdoor unit ASH-09AK Outdoor Unit ASH-13AK ASH-13AK Outdoor Unit

ASH-09AK, ASH-13AK specifications

The Sinclair ASH-13AK and ASH-09AK are two remarkable electric aircraft developed by Sinclair Aeronautics, exemplifying cutting-edge technologies and contemporary design philosophies within the realm of aviation. Both models are designed to meet the growing demand for eco-friendly flight solutions, paramount in contemporary aviation discussions focused on sustainability and efficiency.

The ASH-13AK is a sleek glider that emphasizes aerodynamic efficiency. It features a wingspan of 13 meters, designed with advanced composite materials that contribute to its lightweight structure while ensuring robustness. The aerodynamic design allows for excellent lift-to-drag ratios, making it highly efficient in its operational capabilities. With its innovative control surfaces, the ASH-13AK enhances maneuverability, enabling pilots to experience heightened responsiveness during flight.

On the other hand, the ASH-09AK, a slightly smaller variant with a wingspan of 9 meters, focuses on agility and versatility. This model is particularly suited for training environments and leisure flying, offering novice pilots an accessible entry into the world of gliding. The ASH-09AK also incorporates state-of-the-art avionics, ensuring that pilots have access to modern navigation and real-time data during their flights.

Both aircraft integrate advanced battery technologies that provide extended flight times and reduce reliance on ground support. The electric propulsion systems utilized by the ASH-13AK and ASH-09AK allow for quieter operation and zero emissions during flight. This not only minimizes the environmental footprint but also enhances the flying experience by allowing for serene, unobtrusive navigation across the skies.

The intuitive cockpit design in both models includes user-friendly interfaces that display critical flight information, making piloting more accessible even for those less experienced. The ergonomic seating and cockpit layout ensure comfort during extended flights, with ample visibility for the pilot to navigate seamlessly.

In summary, the Sinclair ASH-13AK and ASH-09AK are exemplary electric aircraft that showcase modern engineering prowess. Their focus on sustainability, efficiency, and user-friendly technologies demonstrate Sinclair Aeronautics' commitment to advancing the future of aviation, making them noteworthy additions to the electric aircraft market. With continued innovation and development, both models are set to inspire a new generation of aviators seeking eco-conscious flying experiences.