LG Electronics LSN180HE, LSN090CE, LSU120CE Insert the connecting cable into the indoor unit

Page 23

Insert the connecting cable into the indoor unit.

Don't connect the cable to the indoor unit.

Make a small loop with the cable for easy con- nection later.

Tape the drain hose and the connecting cable.

• Connecting cable

Tape

Connecting pipe

Drain hose

Connecting cable

Indoor unit installation

Hook the indoor unit onto the upper portion of the installation plate.(Engage the three hooks of the rear top and rear lower of the indoor unit with the upper edge and lower edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting cable

Drain hose

Connecting the pipings to the indoor unit and the drain hose to drain pipe.

Put a couple drops of refrigerant oil on the face of the flare before assembling taking care not to add any contaminants

Align the center of the pipings and sufficiently tighten the flare nut by hand.

Indoor unit tubing

Flare nut Pipings

• Tighten the flare nut with a wrench.

 

 

Spanner (fixed)

 

 

Flare nut

Torque wrench

 

Connection pipe

 

 

Indoor unit tubing

 

 

Outside diameter

Torque

Ø6.35

1/4

1.8

Ø9.52

3/8

4.2

Ø12.7

1/2

5.5

Ø15.88

5/8

6.6

Mount the clamp on the boss with a type "B" screw.(SE-H/P: 9k, 12k C/O: 12k)

Type "B" screw

Drain hose

Clamp

 

Boss

 

When extending the drain hose at the indoor unit, install the drain pipe.

Drain hose

Indoor unit drain hose

Adhesive Vinyl tape (narrow)

Wrap the insulation material around the connecting portion.

Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.

Plastic bands Insulation material

Service Manual 23

Image 23
Contents Room Air Conditioner Table of Contents Be sure not to do Be sure to follow the instruction Safety PrecautionsInstallation Do not modify or extend the power cordOperation Moisture may condense and wet or damage furnishings Low refrigerant levels may cause product failure Keep level even when installing the productOn the product. outdoor unit OccupantsSalt spray directly Solvents, etcReplace all the batteries in the remote DisuseDo not drink the water drained from the unit Indoor Unit DimensionsSymbols Used in this Manual Model Btu Series Dimension Mminch 109042.9 30011.8 1787.0 9k, 12k Outdoor UnitDIM 18k, 24kIntroduction FeaturesInstallation Tools InstallationInstallation Parts Bushing-Sleeve Installation MapThis Product Contains R-410A Refrigerant Confirm The RefrigerantOutdoor unit Rooftop InstallationsSelect The Best Location Indoor unitEvap Moz/ft Piping Length And ElevationDrill a Hole In The Wall How To Mount Installation PlatePutting nut on Flaring WorkCut the pipes and the cable Burrs removalIndoor Connecting The PipingIndoor unit installation Tighten the flare nut with a wrench Wrap the insulation material around the connecting portionIndoor unit installation Insert the connecting cable into the indoor unitConnection Indoor Incorrect case Correct caseConnection Of Piping -Outdoor Connection Of The Drain HoseConnection Of The Cable Wiring DiagramRoom Air Conditioner Drain piping Checking The DrainageSeal small openings around pipings with a gum type sealer Forming The PipingLeak test Air PurgingAir purging With Vacuum Pump PreparationFinishing the job EvacuationBtu/h ChargingEvaluation of the performance Prepare remote controlTest Running Settlement of outdoor unitFunction of Controls Cooling Mode OperationHealthy Dehumidification Mode OperationDefrost Control Heating Mode OperationJet Cool Mode Operation H/P Model Sleep Timer OperationChaos Natural Wind Mode Jet Cool Mode Operation C/O ModelProtection of the evaporator pipe from frosting Forced operationTest operation Auto restartHeating Model Display FunctionSelf-diagnosis Function Operation Mode Remote Control OperationsTo remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Cooling & Heating Models Troubleshooting GuideRefrigeration Cycle Diagram Cooling Only ModelsWay Valve Liquid Side Way, 3-way ValvePumping Down ProcedureBalance Refrigerant of the 3-way Valve Vacuum pump After Evacuation Gas ChargingAdditional gas charging Method of using graphMethod of using equation According to Indoor & Outdoor TemperatureTrouble analysis Cycle PartsProduct does not operate at all Electronic Parts 9k modelElectronic Parts 18k model Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive.9k Model Compressor/Outdoor Fan are unable to drive.18k Model Nector When indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit Electric Control Device Schematic DiagramOutdoor 9k, 12k Outdoor 18k, 24k Wiring Diagram Models 9kC/O Models 12kH/P, 12kC/O, H/P Models 18kC/O Models 18kH/P, 24kC/O, H/P Components Location Outdoor9k, 12k Outdoor18k, 24k 6871A20680 6871A20681Cooling Only Product SpecificationsLS090HE LS120HE LS180HE LS240HE Cooling & HeatingExploded View Outdoor Unit 9k, 12k Btu/h Seriess 435512 W0CZZ-2 Outdoor Unit 18kH/P, 24k SeriessParts List Indoor Replacement Parts ListLSN180CE LSU120HE Parts List OutdoorReplacement Parts List LSU240HE No A20462V