Test run

Error display (AHU)

‘##’ refers to the address information of the communication PCB.

Display

Error item

Cause of error

Cause or error

number

 

 

 

CH

2

##

Temperature sensor

Communication PCB

Temperature sensor disconnection or short circuit at pipe inlet

 

 

 

error at pipe inlet of

rotary switch number

of indoor unit

 

 

 

indoor unit

##

 

CH

3

00

Communication error

 

No communication signal for more than 3 minutes from wired

 

 

 

between wired remote

-

remote controller to the AHU controller

 

 

 

controller and AHU

 

 

 

 

 

controller

 

 

CH

4

##

Communication error

Communication PCB

No communication signal for more than 3 minutes from

 

 

 

between AHU

rotary switch number

communication PCB to AHU controller

 

 

 

controller and

##

 

 

 

 

communication PCB

 

 

CH

5

##

Communication error

Communication PCB

No communication signal for 5 minutes continuously from

 

 

 

between

rotary switch number

communication PCB to outdoor unit

 

 

 

communication PCB

##

 

 

 

 

and outdoor unit

 

 

CH

6

##

Temperature sensor

Communication PCB

Temperature sensor disconnection or short circuit on pipe

 

 

 

error on pipe outlet of

rotary switch number

outlet of indoor unit

 

 

 

indoor unit

##

 

CH

8

00

Emergency operation

-

The operating status of the smoke control mode through smoke detector is displayed

CH

13

01

Temperature sensor

RA

Temperature sensor (RA/SA/Mixing) disconnection/short

 

 

 

error

 

circuit/misconnection or when the sensor value is in the error

 

 

02

 

SA

range

 

 

04

 

Mixing

 

CH

14

01

Humidity sensor error

RA

Humidity sensor (RA/SA/OA) disconnection/short

 

 

02

 

SA

circuit/misconnection or when the sensor value is in the error

 

 

03

 

OA

range

CH

15

00

CO2 sensor error

-

CO2 sensor disconnection/short circuit/misconnection or when

 

 

 

 

 

the sensor value is in the error range

CH

16

05

Pressure sensor error

Differential pressure

Pressure sensor (Differential pressure, static pressure) disconnection/short

 

 

06

 

Static pressure

circuit/misconnection or when the sensor value is in the error range

CH

17

01

Air flow sensor error

RA

Air flow sensor (RA, SA) disconnection/short circuit/misconnection

 

 

02

 

SA

or when the sensor value is in the error range

 

 

 

 

 

 

32AHU CONTROL KIT

Image 32
Contents AHU Control KIT Table of Contents Safety Precautions Meanings of symbols used in this manual are as shown belowIt can cause a fire or problem to the product It can cause a fire or an electric shockIt can cause an explosion or a fire If not, it can cause a fire or an electric shockInjured It can cause vibration or leakage You can get injured by doing soNecessary sensor by operating mode Name and Function of Remote Controller Part DescriptionBasic operation of wired remote controller Main function of wired remote controller Current humidity / CO2 level Supplementary function of wired remote controller HumidifierDesired humidity control Auto ventilaton Default humidity is set to 1000ppm Desired CO2 Level controlSetting AM / PM value by Changing Current TimeAHU Control KIT Press button to finish setting Programming Setting Simple ReservationSegment flashing Ex Setting Simple Reservation time as Programming Setting on Reservation Programming Setting OFF Reservation Programming Weekly Reservation Action Start Time FrontProgramming Holiday Reservation Release a selected day asHow to start installation setting mode Setting function by code Central control address setting Damper opening setting 1Enter the Installation Setting modeFlashes Press the Right button to move to ‘Setting of 1’ Cooling mode ‘01’ OA /‘02’ EA / ‘03’ MixingEnglish Remote control Master/Slave setting Manual operating mode Remote controllerSA fan operation RA fan operationCheck before requesting for service Once you resolve the error, the error code will disappear Test runSelf diagnosis function Detail descriptionRemote controller to the AHU controller ErrorSensor value is in the error range Indoor unitExample of error SituationAHU Control KIT No. MFL62171702