Necessary sensor by operating mode
Necessary sensor by operating mode
Operating mode | Necessary sensor | Function | |
|
|
| |
|
| - This runs indoor air conditioning. | |
Air conditioning | SA temperature sensor | - Initial external air inlet setting is 30% of the air | |
supply during the air conditioning and this can be | |||
RA temperature sensor | |||
| changed by the user. But, when the damper actuator | ||
|
| ||
|
| is installed on AHU, the setting can be changed. | |
|
|
| |
|
| - This runs the indoor heating. | |
Heating | SA temperature sensor | - Initial external air inlet setting is 30% of the air | |
RA temperature sensor | supply during the heating and this can be changed | ||
| |||
| by the user. But, when the damper actuator is | ||
|
| ||
|
| installed on AHU, the setting can be changed. | |
|
|
| |
|
| - This is the operating function to run indoor air | |
|
| conditioning by controlling multiple outdoor units by | |
| SA temperature sensor | comparing the enthalpy of the indoor/outdoor air. | |
| - During the power save operation, the operation switches | ||
Power save | RA temperature sensor | between partial air conditioning operation (Controlling | |
OA temperature/ | multiple outdoor units) and external air conditioning | ||
| humidity sensor | operation (Outdoor unit OFF, 100% external air flow). | |
| Damper actuator | - This is operating function is mainly used in between | |
| seasons. But if there is no OA temperature/humidity | ||
|
| ||
|
| sensor and RA temperature/humidity sensor on the | |
|
| AHU, the power save operation cannot be selected. | |
|
| - This is the operating function to remove the indoor | |
| SA temperature sensor | humidity when the humidity level indoor is excessive. | |
Dehumidify | RA temperature sensor | - During the dehumidifier operation, the set value is | |
50%RH and the user cannot change this setting. But | |||
OA temperature/ | |||
| if there is no OA temperature/humidity sensor and | ||
| humidity sensor | ||
| RA temperature/humidity sensor on the AHU, the | ||
|
| ||
|
| dehumidifier operation cannot be selected. | |
|
|
| |
|
| - This is the operating function to control the humidity to | |
| SA temperature sensor | the set value by detecting the indoor humidity level. | |
Humidification | - This can be selected during heating operation. | ||
RA temperature sensor | But if there is no humidifier/humidifying valve and | ||
| |||
|
| RA temperature/humidity sensor on the AHU, the | |
|
| humidifier operation cannot be selected. | |
|
|
| |
|
| - This is the operating function to control the amount of | |
|
| external air flow so that the CO2 level is controlled | |
| SA temperature sensor | within the set level by detecting the indoor CO2 level. | |
| - The initial CO2 level is set to 1000ppm, and can | ||
Auto ventilation | RA temperature sensor | be changed by the user. | |
CO2 sensor | - This function operates when auto ventilator | ||
| |||
| Damper actuator | (Additional operation) is selected during air | |
|
| conditioning or heating operation. But if there is no | |
|
| CO2 sensor and damper actuator on the AHU, the | |
|
| auto ventilator operation cannot be selected. | |
|
|
| |
| SA temperature sensor | - When the mixing temperature during the heating | |
| operation is below the set value (5°C), | ||
Preheating | RA temperature sensor | preheating device automatically operates. The | |
Mixing temperature/ | preheating device and mixing temperature | ||
| |||
| humidity sensor | sensor must be installed on AHU for this to | |
|
| operate automatically. | |
|
|
| |
|
|
|
6AHU CONTROL KIT