LG Electronics AMNC123APM0(LMAN120CNS), AMNH123DEA0(LMN120HE) Test Running, Split, Art Cool Type

Page 39

Test Running

Test Running

Split, Art Cool Type

1.Check that all tubing and wiring have been properly con- nected.

2.Check that the gas and liquid side service valves are fully open.

1) Prepare remote controller

Remove the battery cover by pulling it according to the arrow direction.

Insert new batteries making sure that the (+) and (–) of battery are installed correctly.

Reattach the cover by pushing it back into position.

NOTE:

Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.

Remove the batteries from the remote controller if the sys- tem is not going to be used for a long time.

2)Precautions in test run

The initial power supply must provide at least 90% of the rated voltage.

Otherwise, the air conditioner should not be operated.

For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compres- sor. Then attention must be paid.

Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later auto- matically)

The test run is started by pressing timer cancel button five times continuously. (Room type)

To cancel the test run, press any button.

3)Settlement of outdoor unit

Anchor the outdoor unit with a bolt and nut(ø 10mm) tightly and horizontally on a concrete or rigid mount.

When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.

In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration rubber.

Bolt

Tubing connection

4) Evaluation of the performance

Operate unit for 15~20 minutes, then check the system refrigerant charge:

1.Measure the pressure of the gas side service valve.

2.Measure the temperature of the intake and discharge of air.

3.Ensure the difference between the intake temperature and the discharge is more than 8°C(46°F) (Cooling) or reversely (Heating).

Refrigerant

Outside ambient

The pressure of the gas side

TEMP.

service valve.

 

R-410A

35°C (95°F)

8.5~9.5kg/cm2G(120~135 P.S.I.G.)

 

 

 

Intake temperature

Discharge air

Discharge temperature

Intake temperature

Discharge air

Discharge temperature

Service Manual 39

Image 39
Contents Outdoor Unit A3UH363FA0LMU360HE A3UC363FA0LMU360CE Indoor Unit Room Type Art Cool TypeTable of Contents Model Number Nomenclature Indoor UnitOutdoor Unit Combination table Symbols Used in this ManualControl box securely Cuit and breaker Safety PrecautionsInstallation Be sure not to do Be sure to follow the instructionOperation Do not place anything on the power cableBe cautious when unpacking Be sure the installation area does not deteriorate with ageHurricane arrives Nect the power supply cableDo not allow water to run into electric parts Smoke comes from productNot enter the product When the product is soakedInstall the drain hose to ensure that Keep level even when Installing the productNot use harsh detergents, sol OperationalAir flow Vents, etcDo not drink the water drained from the product Ly. Clean the filter every twoWhen cleaning or maintaining Do not step on or put anyting on the product. outdoor unitsDimensions Indoor UnitSplit Type Indoor Outdoor Unit Indoor Unit Product SpecificationsModel A3UC363FA0LMU360CE A3UH363FA0LMU360HE Outdoor Unit Multiple piping modelsInstallation Installation PartsInstallation Tools Rooftop Installations Select the best locationOutdoor unit Multi Piping Type Piping length and elevationFixing Installation PlateStandard Type Drain hose junction Preparing work for Installation Artcool Type OnlyOpen panel front Remove cover pipe and cover sideDrive the fore plastic anchors into drilled points Sticking the installation guide map and fixing Indoor unitPut an Installation Guide Map on the desired surface Drill a hole in the wallFlaring work Flaring Work and Connection of PipingConnecting the Piping CheckIndoor Wrap the insulation material around the connecting por- tion For left rear piping Plastic bands Insulation material Connection Indoor Drive two screws Panel AssemblyArt Cool Type onlyBad case Good caseRemote Control Preparationoptional Outdoor unit OutdoorConnect the cable to the Indoor unit Connecting the Cable between Indoor Unit and Outdoor UnitOutdoor unit Connect the cable to the Outdoor unitHow to connect wiring to the terminals Connection method of the connecting cableExampleConnect the cable to the indoor unit Checking the drainage To check the drainageDrain piping Forming the piping Leakage test Air Purging and Evacuation Checking method PreparationRepeat evacuation procedure for each indoor unit EvacuationFinishing the job Additional ChargingSplit, Art Cool Type Test RunningOperation Cooling Mode OperationSoft Dry Operation Mode Heating Mode OperationDefrost ControlHeating Fuzzy OperationFuzzy Operation for Cooling Fuzzy Operation for Dehumidification On-Timer OperationOff-Timer Operation Airflow Speed SelectionChaos Natural Wind Mode Off-Timer = On-Timer OperationSleep Timer Operation Chaos Swing ModeBuzzer Sounding Operation Forced OperationSplit Type Indoor Unit Function of Indoor UnitDefrostDeice control Heating IndicatorArt Cool Type Indoor Unit OperationFunction of Outdoor Unit Remote Control Operation Cooling Model , Heat Pump Model15 2nd F Button To remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover To remove the Control Box To remove the Evaporator Before removing the Turbo FanTo remove the Motor Schematic Diagram Electronic Control DeviceSplit Type Outdoor Outdoor Unit Schematic Diagram Art Cool Type Indoor Unit Wiring DiagramBottom View Components LocationsArt Cool Type Schematic Diagram Component side Solder side A3UC363FA0LMU360CE Troubleshooting GuideRefrigeration Cycle Diagram A3UH363FA0LMU360HESelf-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan are dont operateNector Trouble 4 When indoor Fan does not operateTroubleshooting Guide Indoor inlet pipe sensor Error CodeCheck Point Indoor air sensorCommunication line is shorted at GND Power input AC 230V.Outdoor, IndoorError Title Cause of error Check point & Normal condition Pipe sensor Title Cause of error Check point & Normal conditionOutdoor air sensor Condensor pipe sensorWay Valve Liguid Side Way, 3-way ValveSet the liquid side valve to the closed position ProcedurePumping down Air purging of the charge hoseMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Connect the gauge to the charging cylinder Mount the valve stem nuts and the service port nutGas Charging After EvacuationS4, SE chassis Exploded View & Replacement Parts ListParts List S4, SE chassis S4 chassis SE chassisLMN090HE SP3 Chassis Art Cool Type Filter ASSEMBLY,AIR Cleaner Parts List SP3 chassisA3UC363FA0LMU360CE Code Parts List A3UH363FA0LMU360HE, A3UC363FA0LMU360CEMay No A20474C