AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) x 20 = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

____________________ Btu/Hr

 

 

 

 

Gas water heater*

____________________ Btu/Hr

Example:

 

 

 

Gas furnace

____________________ Btu/Hr

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

____________________ Btu/Hr

 

Vent-free heater

+

30,000

Btu/Hr

Gas fireplace logs

____________________ Btu/Hr

 

 

 

 

Total

=

70,000

Btu/Hr

Other gas appliances*

+ ___________________ Btu/Hr

 

 

 

 

Total

= ___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3 or applicable local codes.

Continued

104461

5

Image 5
Contents What to do if YOU Smell GAS VENT-FREE Natural GAS Stove HeaterDesa International VENT-FREE Natural GAS Stove Heater Safety InformationLocal Codes Product FeaturesProduct Identification Providing Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsCheck GAS Type InstallationClearances to Combustibles Vent-Free Operation OnlyUse an adjustable wrench or Stove Cavity AssemblySheraton Models Amity and Townsend ModelsAttaching Stove Door Appearance May Vary Depending on Model Fastening Heater Base to Stove Drop Bottom Installing GAS LOG Heater Into StoveInstallation Items Needed Connecting to GAS SupplyChecking GAS Connections Pressure Testing Heater Gas ConnectionsPressure Testing Gas Supply Piping System Operating Heater For Your Safety Read Before LightingLighting Instructions SVYD18NR and FSVYD18NR Remote-Ready ModelsOptional Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance SVYD18N and FSVYD18N Manual-Variable Control Models Variable Control OperationPilot Flame Pattern Inspecting BurnersBurner Primary AIR Holes Main BurnerSpecifications Cleaning and MaintenanceTechnical Service Cleaning Burner Injector Holder and Pilot AIR Inlet HoleObserved Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Top SVYD18NR FSVYD18NR Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListSVYD18N FSVYD18N KEY Part Description QTY Indicates Color Suffix Designation Amity SCIVF* Series PSCIVF* SeriesTouch-up Paint Bottle with Brush Porcelain Enamel Teal Green Sheraton NSCIVF* Series Parts List Series TownsendFC* and PFC* Series *Indicates Color Suffix Designation Service Hints Replacement PartsWiring Diagram Parts Under WarrantyAccessories Warranty Information

(F)SVYD18N, (F)SVYD18NR specifications

Desa (F)SVYD18NR and (F)SVYD18N are advanced models in the range of valves designed to serve various industrial and residential applications. Known for their reliability and efficiency, these valves are engineered to meet the demanding needs of modern fluid control systems.

One of the main features of the Desa (F)SVYD18NR and (F)SVYD18N is their robust construction. They are made from high-quality materials that ensure durability and longevity, even in harsh operating conditions. The valves are resistant to corrosion, making them suitable for handling aggressive fluids without compromising their integrity. This characteristic is essential for industries such as chemicals, oil and gas, and water treatment, where exposure to different substances is inevitable.

The valves are also equipped with advanced sealing technologies which prevent leaks and ensure optimal performance. The precision-engineered seals provide a barrier against contaminants while maintaining efficient fluid flow. This not only enhances the reliability of the system but also contributes to reduced maintenance costs and downtime.

Another significant advantage of the Desa (F)SVYD18NR and (F)SVYD18N is their versatility. They are designed to accommodate a wide range of fluid types, including gases, liquids, and slurries. This adaptability makes them ideal for various applications, from HVAC systems to industrial manufacturing processes.

In terms of operation, these valves utilize a user-friendly design that facilitates ease of installation and adjustment. They come with standardized connections that fit a variety of piping systems, simplifying the integration process. Additionally, the models have a responsive actuator mechanism that ensures precise control over fluid flow, enhancing operational efficiency.

Moreover, Desa (F)SVYD18NR and (F)SVYD18N are designed with energy efficiency in mind. Their advanced aerodynamic design minimizes pressure drops and energy consumption, making them an environmentally friendly choice. This aligns with the growing trend of sustainable practices in industrial operations.

Finally, both models are subject to rigorous testing to ensure they meet industry standards and regulations. This commitment to quality assurance guarantees that users can trust the performance and safety of these valves in their operations.

In conclusion, the Desa (F)SVYD18NR and (F)SVYD18N valves stand out for their durability, versatility, easy installation, and commitment to energy efficiency. These characteristics make them an excellent choice for anyone seeking reliable fluid control solutions in various applications.