3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM
1.When replacing a refrigeration component, be sure to discharge the refrigerant system by using a refrigerant recovery system.
2.After discharging the unit completely, remove the desired component, and unbraze the
3.Solder service valves into the
4.Solder the
5.After doing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.
6.Evacuate as follows.
1)Connect the vacuum pump, as illustrated in Figure 31A.
2)Start the vacuum pump, slowly open manifold valves A and B two full turns counterclockwise and leave the valves open.
The vacuum pump is now pulling through valves A and B to valve C by means of the manifold and entire system.
CAUTION
If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.
3)Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum are obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.
4)Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 31B. Open valve C.
Discharge the line at the manifold connection.
5)The system is now ready for final charging.
7.Recharge as follows :
1)Refrigeration cycle systems are charged from the
in the
2)Connect the charging cylinder as shown in Figure 31B.
With valve C open, discharge the hose at the manifold connection.
3)Open valve A and allow the proper charge to enter the system. Valve B is still closed.
4)If more charge is required, the
5)With the unit running, open valve B and add the balance of the charge.
a.Do not add the liquid refrigerant to the Low- side.
b.Watch the
c.Turn off valve B and allow pressure to drop.
d.Repeat steps B and C until the balance of the charge is in the system.
6)When satisfied the unit is operating correctly, use the