3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM

1.When replacing a refrigeration component, be sure to discharge the refrigerant system by using a refrigerant recovery system.

2.After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with service valves.

5.After doing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.

6.Evacuate as follows.

1)Connect the vacuum pump, as illustrated in Figure 31A.

2)Start the vacuum pump, slowly open manifold valves A and B two full turns counterclockwise and leave the valves open.

The vacuum pump is now pulling through valves A and B to valve C by means of the manifold and entire system.

CAUTION

If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

3)Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum are obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

4)Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 31B. Open valve C.

Discharge the line at the manifold connection.

5)The system is now ready for final charging.

7.Recharge as follows :

1)Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put

in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

2)Connect the charging cylinder as shown in Figure 31B.

With valve C open, discharge the hose at the manifold connection.

3)Open valve A and allow the proper charge to enter the system. Valve B is still closed.

4)If more charge is required, the high-side will not take it. Close valve A.

5)With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the Low- side.

b.Watch the Low-side gauge; allow pressure to rise to 30 lbs.

c.Turn off valve B and allow pressure to drop.

d.Repeat steps B and C until the balance of the charge is in the system.

6)When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

—18—

Image 18
Contents Dehumidifier Contents Safety Precautions Features and DimensionsFeatures Specifications Model NamesControl Type Mechanical typeHOW does the Dehumidifier WORK? HOW to Operate DehumidifierMicro Switch Location for the DehumidifierMechanical Type Electronic TypeModel DH305Y5, DH300MY5 DescriptionDH305Y5,DH300MY5 Model DH300EY5 DH300EY5Model DH400MY5/LD40Y5 DH400MY5/LD40Y5Model DH404EY5/DH400EY5/LD40EY5 DH404EY5/DH400EY5LD40EY5 Model DH504ELY5/LD50ELY5/LD65ELY5 DH504ELY5/LD50ELY5 LD65ELY5Front Case and Rear Grille Mechanical PartsBucket and AIR Filter Cabinet and Control BOXPower Cord Assembly Control PartsCoil ASSEMBLY, Solenoid DH504ELY5, LD50ELY5, LD65ELY5 Control PanelFAN and Motor Shroud and Drain PANRefrigerating Cycle CONDENSER, Evaporator and Capillary TubeHOW to Replace the Refrigeration System Pulling Vacuum Troubleshooting Guide Condition Cause Remedy Water dripsExploded Views Model DH305Y5/DH300MY5Model DH300EY5 346811 249950 435300 264110 131400 135312 165010 238310 Model DH404EY5/DH400EY5/LD40EY5 Model DH504ELY5/LD50ELY5 Model LD65ELY5 Remark DH305Y5/DH300MY5Drier Assembly BLG/EGoldstar Model DH404E Y5/DH400EY5/LD40EY5 DH404EY5/DH400EY5/LD40EY5Model DH504ELY5/LD50ELY5 Description DH504ELY5/LD50ELY5Model LD65ELY5 Description LD65ELY5January