Carrier 13 50XP manual 50XP048 Cooling Performance Table, 50XP060 Cooling Performance Table

Page 13
t ldb = t edb

Performance data (cont)-Standard ECM Indoor Motor

COOLING CAPACITIES

50XP048 COOLING PERFORMANCE TABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Evaporator Air—CFM/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1260/0.06

 

 

1400/0.06

 

 

 

1600/0.08

 

 

 

Outdoor Air

 

 

 

 

 

 

 

 

 

 

Entering

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

63*

 

67

72

62

 

63*

67

 

72

62

63*

67

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

45.0

45.8

 

49.6

54.7

46.7

 

47.3

51.2

 

56.3

48.1

48.7

52.5

57.8

 

 

75

 

SHC

39.3

32.0

 

33.4

27.2

42.6

 

34.3

35.8

 

28.9

45.8

36.8

38.4

30.6

 

 

 

 

kW

3.4

3.4

 

3.4

3.4

3.4

 

3.4

3.4

 

3.5

3.4

3.4

3.4

3.5

 

 

 

 

TC

42.8

43.6

 

47.2

52.1

44.3

 

44.9

48.6

 

53.5

45.6

46.1

49.9

54.8

 

 

85

 

SHC

38.2

30.9

 

32.3

26.2

41.3

 

33.2

34.7

 

27.7

44.3

35.5

37.3

29.4

 

 

 

 

kW

3.7

3.7

 

3.8

3.8

3.7

 

3.7

3.8

 

3.8

3.8

3.8

3.8

3.8

 

50XP

 

 

TC

40.6

41.3

 

44.7

49.4

41.8

 

42.4

46.0

 

50.7

44.2

43.7

47.0

51.8

 

95

 

SHC

36.9

29.8

 

31.2

25.2

39.9

 

32.0

33.6

 

26.7

43.0

34.6

36.1

28.3

 

 

 

kW

4.1

4.1

 

4.2

4.2

4.1

 

4.1

4.2

 

4.2

4.2

4.1

4.2

4.2

 

 

105

 

TC

38.2

38.9

 

42.1

46.4

39.6

 

39.8

43.1

 

47.6

41.5

40.8

44.0

48.5

 

 

 

SHC

35.7

28.7

 

30.1

24.0

38.3

 

30.7

32.3

 

25.5

40.0

33.2

34.8

27.0

 

 

 

 

kW

4.6

4.6

 

4.6

4.6

4.6

 

4.6

4.6

 

4.7

4.6

4.6

4.6

4.7

 

 

115

 

TC

35.7

36.3

 

39.3

43.3

38.2

 

37.1

40.1

 

44.2

38.7

37.9

40.8

45.0

 

 

 

SHC

34.4

27.5

 

28.9

22.9

35.7

 

29.5

31.0

 

24.3

38.2

31.8

33.5

25.8

 

 

 

 

 

kW

5.0

5.0

 

5.1

5.1

5.1

 

5.0

5.1

 

5.1

5.1

5.1

5.1

5.1

 

 

125

 

TC

33.4

33.4

 

36.2

39.4

34.6

 

34.1

36.9

 

40.5

36.1

34.8

37.5

41.2

 

 

 

SHC

32.1

26.2

 

27.6

21.5

33.8

 

28.2

29.7

 

22.9

35.6

30.2

31.9

24.4

 

 

 

 

kW

5.6

5.6

 

5.6

5.7

5.6

 

5.6

5.6

 

5.6

5.6

5.6

5.6

5.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50XP060 COOLING PERFORMANCE TABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Evaporator Air—CFM/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500/0.004

 

 

1750/0.007

 

 

 

2000/0.01

 

 

 

Outdoor Air

 

 

 

 

 

 

 

 

 

 

Entering

 

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

63*

 

67

72

62

 

63*

67

 

72

62

63*

67

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

57.2

58.2

 

62.4

68.1

58.8

 

59.7

64.0

 

69.8

60.0

60.8

64.9

70.8

 

 

75

 

SHC

49.4

47.9

 

41.6

33.8

53.6

 

51.8

44.5

 

35.4

57.6

55.4

47.1

36.8

 

 

 

 

kW

4.1

4.1

 

4.2

4.2

4.2

 

4.3

4.3

 

4.4

4.4

4.4

4.5

4.6

 

 

 

 

TC

54.7

55.6

 

59.7

65.2

56.2

 

57.0

61.1

 

66.6

57.4

58.1

61.9

67.4

 

 

85

 

SHC

48.2

46.7

 

40.4

32.6

52.4

 

50.5

43.2

 

34.2

56.3

54.2

45.8

35.6

 

 

 

 

kW

4.5

4.5

 

4.6

4.7

4.7

 

4.7

4.8

 

4.9

4.8

4.9

5.0

5.0

 

 

 

 

TC

52.2

53.0

 

56.9

62.0

53.5

 

54.3

58.0

 

63.2

55.0

55.3

58.7

64.1

 

 

95

 

SHC

47.0

45.4

 

39.2

31.4

51.1

 

49.2

41.9

 

32.9

55.0

52.9

44.5

34.4

 

 

 

 

kW

5.0

5.0

 

5.1

5.2

5.1

 

5.2

5.3

 

5.3

5.2

5.3

5.5

5.5

 

 

105

 

TC

49.4

50.2

 

53.8

58.7

50.7

 

51.4

54.8

 

59.6

52.5

52.4

55.4

60.2

 

 

 

SHC

45.7

44.1

 

37.9

30.1

49.8

 

47.9

40.6

 

31.6

52.5

51.6

43.2

33.0

 

 

 

 

kW

5.5

5.6

 

5.6

5.7

5.7

 

5.7

5.8

 

5.9

5.8

5.8

6.0

6.1

 

 

115

 

TC

46.5

47.2

 

50.5

55.0

48.1

 

48.3

51.3

 

56.8

49.7

49.7

51.8

57.0

 

 

 

SHC

44.3

42.7

 

36.4

28.7

48.1

 

46.6

39.2

 

30.6

49.7

49.7

41.8

31.7

 

 

 

 

kW

6.1

6.2

 

6.2

6.3

6.2

 

6.3

6.4

 

6.4

6.4

6.4

6.6

6.6

 

 

125

 

TC

43.3

43.9

 

46.7

52.2

45.2

 

45.1

47.4

 

52.5

46.4

46.4

47.9

52.2

 

 

 

SHC

42.8

41.2

 

34.9

27.8

45.2

 

45.1

37.6

 

28.9

46.4

46.4

40.2

29.7

 

 

 

 

kW

6.7

6.8

 

6.8

6.8

6.8

 

6.9

7.0

 

7.0

7.0

7.0

7.2

7.2

 

 

 

 

LEGEND

BF

Bypass Factor

Ewb

Entering Wet-Bulb

kW

— Total Unit Power Input

SHC

— Sensible Heat Capacity (1000 Btuh)

TC

— Cooling Capacity (1000 Btuh)

ECM

Electronic Computated Motor

*— TVA Conditions (75°F Entering Dry Bulb)

NOTES:

1.Ratings are net; they do account for the effects of the evaporator-fan motor power and heat.

2.Direct interpolation is permissible. Do not extrapolate.

3.The following formulas may be used:

sensible capacity (Btuh) 1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

 

Where: hewb =

Enthalpy of air entering evaporator coil

4.The SHC is based on 80°F Edb (Entering dry bulb) air temperature through Evaporator coil. Below 80°F Edb, subtract (Correction Factor x CFM) from SHC. Above 80°F Edb, add (Correction Factor x CFM) to SHC. Correction Factor = 1.10 x (1 – BF) x (Edb – 8)

13

Image 13
Contents Product Data Table of contents ARI* capacities Model number nomenclatureUnit Nominal Standard NET Cooling Sound EER@APhysical data ODS Catalog Nominal Capacity Used with Sizes Ordering no Options and accessoriesUnit AirflowEconomizer Filter Rack Manual Outside AIR Damper Electrical Unit Weight Unit Height Base unit dimensions-50XP024-036Characteristics In. mmBase unit dimensions-50XP042-060 Unit Size ODS Catalog Number Accessory dimensionsSelection Procedure 50XP Corner weights In PoundsSmall Base Large Base SHC 50XP024 Cooling Performance Table50XP030 Cooling Performance Table 1100/0.06 50XP036 Cooling Performance Table1400/0.08 Outdoor Air Entering Condenser1260/0.06 1400/0.06 1600/0.08 Outdoor Air Entering 50XP048 Cooling Performance Table50XP060 Cooling Performance Table 1500/0.004 1750/0.007 2000/0.01 Outdoor Air EnteringPerformance data Size CFM Adjust LO PIN NOM PIN HI PIN Unit024 Unit Standard CFM SizeTypical piping and wiring Application data 187 253 13.5 Electrical dataFLA Typical wiring schematic- 208/230-1-60 Typical wiring schematic- 208/230-3-60 Operating sequence ControlsPackaged Electric Cooling Units Constant Volume Application Guide specificationsCatalog No 50XP-4PD Replaces 50XP-3PD

13 50XP specifications

The Carrier 13 50XP is a central air conditioning unit known for its reliability, efficiency, and advanced technology features. Designed for residential and light commercial applications, this system stands out in the HVAC market for its performance and durability.

One of the primary features of the Carrier 13 50XP is its high energy efficiency. The unit has a SEER (Seasonal Energy Efficiency Ratio) rating of up to 14, making it a cost-effective option for homeowners looking to reduce energy consumption. This efficiency is crucial as it translates to lower utility bills and a reduced carbon footprint.

The Carrier 13 50XP incorporates the innovative WeatherShield cabinet, which enhances durability against the elements. This robust housing protects internal components from harsh weather conditions, ensuring reliable performance over time. The all-aluminum coil design further enhances its resistance to corrosion while maximizing heat exchange efficiency.

In terms of comfort control, the system is compatible with various thermostat options, including smart thermostats, providing homeowners with the convenience of monitoring and adjusting temperatures from anywhere. The multi-speed blower provides an added layer of comfort by optimizing humidity control and air distribution throughout the space.

The unit is equipped with sound-dampening technology, which minimizes operational noise, making it a quiet choice for residential areas. This feature is essential for maintaining a peaceful home environment, particularly in bedrooms or family rooms.

Additionally, the Carrier 13 50XP utilizes R-410A refrigerant, which is designed to be environmentally friendly. R-410A is less harmful to the ozone layer than older refrigerants, complying with current environmental regulations and contributing to sustainable living practices.

The installation process for the Carrier 13 50XP is straightforward, thanks to its compact design and flexible configurations. The unit is also backed by Carrier's reliable warranty options, providing peace of mind for consumers.

In summary, the Carrier 13 50XP is a well-rounded air conditioning solution that combines energy efficiency, durability, and advanced technology features. Its commitment to environmental responsibility and user comfort makes it a valuable addition to any home or small commercial setting, ensuring reliable cooling performance for years to come.