Carrier 19XR installation instructions Rla

Page 32

IMPORTANT: Wiring shown is typical and not intended to show detail for a speci®c installation. Refer to certi®ed ®eld wiring diagrams.

 

 

LEGEND

AWG Ð American Wire Gage

N.C.

Ð

Normally Closed

N.O.

Ð

Normally Open

PR

Ð Pilot Relay

RLA

Ð Rated Load Amps

ST

Ð Shunt Trip

TB

Ð Terminal Block

Required Power Wiring

Required Control Wiring

Options Wiring

NOTES:

I.GENERAL

1.0Starters shall be designed and manufactured in accordance with Carrier Engineering Requirement Z-375.

1.1All ®eld-supplied conductors, devices, ®eld-installation wiring, and ter- mination of conductors and devices must be in compliance with all ap- plicable codes and job speci®cations.

1.2The routing of ®eld-installed conduit and conductors and the location of ®eld-installed devices must not interfere with equipment access or the reading, adjusting, or servicing of any component.

1.3Equipment, installation, and all starting and control devices must com- ply with details in equipment submittal drawings and literature.

1.4Contacts and switches are shown in the position they would assume with the circuit deenergized and the chiller shut down.

1.5WARNING Ð Do not use aluminum conductors.

1.6Installer is responsible for any damage caused by improper wiring be- tween starter and machine.

II.POWER WIRING TO STARTER

2.0Power conductor rating must meet minimum unit nameplate voltage and compressor motor RLA.

When (3) conductors are used:

Minimum ampacity per conductor = 1.25 x compressor RLA

When (6) conductors are used:

Minimum ampacity per conductor = 0.721 x compressor RLA

2.1Lug adapters may be required if installation conditions dictate that con- ductors be sized beyond the minimum ampacity required. Contact starter supplier for lug information.

2.2Compressor motor and controls must be grounded by using equip- ment grounding lugs provided inside starter enclosure.

III.CONTROL WIRING

3.0Field supplied control conductors to be at least 18 AWG or larger.

3.1Chilled water and condenser water ¯ow switch contacts, optional re- mote start device contacts, and optional spare safety device contacts must have 24 vdc rating. Max current is 60 mA; nominal current is 10 mA. Switches with gold plated bifurcated contacts are recommended.

3.2Remove jumper wire between 12A and 12B before connecting auxil- iary safeties between these terminals.

3.3Pilot relays can control cooler and condenser pump and tower fan mo- tor contactor coil loads rated 10 amps at 115 vac up to 3 amps at 600 vac. Control wiring required for Carrier to start pumps and tower

fan motors must be provided to assure machine protection. If primary pump and tower fan motor are controlled by other means, also provide a parallel means for control by Carrier. Do not use starter control transformer as the

power source for pilot relay loads.

3.4Do not route control wiring carrying 30 v or less within a conduit which has wires carrying 50 v or higher or alongside wires carrying 50 v or higher.

3.5Voltage selector switch in machine power panel is factory set for 115 v control power source. When 230 v control power source is used, set switch to 230 v position.

3.6Control wiring cables between starter and power panel must be shielded with minimum rating of 600 v, 80 C. Ground shield at starter.

3.7If optional oil pump circuit breaker is not supplied within the starter enclo- sure as shown, it must be located within sight of the machine with wiring routed to suit.

IV. POWER WIRING BETWEEN STARTER AND COMPRESSOR MOTOR

4.0Low voltage (600 v or less) compressor motors have (6) 3¤4 in. terminal studs (lead connectors not supplied by Carrier). Either 3 or 6 leads must be run between compressor motor and starter, depending on type of motor starter employed. If only 3 leads are required, jumper motor terminals as follows: 1 to 6, 2 to 4, 3 to 5. Center to center distance between terminals is 215¤16 inches. Compressor motor starter must have nameplate stamped as conforming with Carrier requirement Z-375.

4.1When more than one conduit is used to run conductors from starter to compressor motor terminal box, one conductor from each phase must be in each conduit to prevent excessive heating. (e.g., conductors to motor terminals 1, 2 & 3 in one conduit, and those to 4, 5 & 6 in another.)

4.2Compressor motor power connections can be made through top, top rear, or sides of compressor motor terminal box using holes cut by con- tractor to suit conduit. Flexible conduit should be used for the last few feet to the terminal box for unit vibration isolation. Use of stress cones or 12 conductors larger than 500 MCM may require an oversize (spe- cial) motor terminal box (not supplied by Carrier). Lead connections between 3-phase motors and their starters must not be insulated until Carrier personnel have checked compressor and oil pump rotations.

4.3Compressor motor frame to be grounded in accordance with the Na- tional Electrical Code (NFPA-70) and applicable codes. Means for ground- ing compressor motor is a pressure connector for No. 4 to 500 MCM wire, supplied and located in the back lower left side corner of the com- pressor motor terminal box.

4.4Do not allow motor terminals to support weight of wire cables. Use cable supports and strain reliefs as required.

4.5Use backup wrench when tightening lead connectors to motor terminal studs. Torque to 45 lb-ft max.

Fig. 28 Ð 19XR Typical Field Wiring with Optional Unit-Mounted Starter

32

Image 32
Contents Installation Instructions Contents Model Number Identication Front TOP View Compressor Cooler Maximum Vessel Chain LengthFrame Size LengthMachine Rigging Guide Cooler Size 70 Through DIM. ``A DIM. ``B DIM. ``CHeat Exchanger SizeFrame 19XR Dimensions Marine Waterbox19XR Nozzle Size 19XR Compressor Weights 19XR Component WeightsEnglish Code19XR Heat Exchanger Data 19XR Additional Data for Marine Waterboxes Condenser Ð 19XR Waterbox Cover WeightsHeat Waterbox Frame Exchanger Description SI kg Cooler, Side View 19XR Chiller Top View Chiller End View Dimensions ft-in 15-1720-22 30-32Standard Isolation Typical Nozzle Piping COM Ð CommonPiping Flow Data NIH, Frames 1 Through Frames 1, 2, Frames 4, 5,Condenser Waterboxes OutCode Marine Waterboxes Frames 2Out Arrangement Piping Flow Data MWB, Frames 4 Through Marine Waterboxes Frames 4, 5,19XR Waterbox Nozzle Sizes Frame Pressure PassNominal Pipe Size Actual Pipe ID Psig kPa Cooler CondenserTank Size 04280452 QTY Trade Size LocationWeight Size ANSI/ASHRAE Tank Tank OD DRYMaximum Refrigerant Capacity lb Maximum Refrigerant Capacity kgOptional Pumpout System Piping Schematic with Storage Tank Connector Relief Device LocationsQuantity Relief Valve Outlet SizeCarrier Comfort Network Communication Bus Wiring 19XR with Optional Unit-Mounted Starter 19XR with Free-Standing Starter RLA 19XR Typical Field Wiring with Free-Standing Starter Manufacturer Cable no Install Field Insulation Page Page Copyright 1997 Carrier Corporation Installation START-UP Request Checklist Testing YES/NO Date to be Completed
Related manuals
Manual 140 pages 13.24 Kb

19XR specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.