Carrier 19XR installation instructions Manufacturer Cable no

Page 34

Connect Power Wires to Oil Heater Contactor Ð Connect control power wiring between the oil heater contactor ter- minals and terminals LL1 and LL2 on the ®eld wiring strip in the compressor motor starter. Refer to Fig. 31 and wiring label on the machine power panel.

Voltage to terminals LL1 and LL2 comes from a con- trol transformer in a starter built to Carrier speci®ca- tions. Do not connect an outside source of control power to the compressor motor starter (terminals LL1 and LL2). An outside power source will produce dangerous volt- age at the line side of the starter, because supplying volt- age at the transfomer secondary terminals produces in- put level voltage at the transformer primary terminals.

Connect Wiring from Starter to Power Panel Ð Connect con- trol wiring from main motor starter to the machine power panel. All control wiring must use shielded cable. Also, con- nect the communications cable. Refer to the job wiring dia- grams for cable type and cable number. Make sure the con- trol circuit is grounded in accordance with applicable electrical codes and instructions on machine control wiring label.

LEGEND

Factory Wiring

Field Wiring

Oil Pump Terminal

Power Panel Component Terminal

Fig. 30 Ð Oil Pump Wiring

LEGEND

Field Wiring

Power Panel Component Terminal

NOTE: The voltage selector switch in the machine power panel is factory set for 115 v control power source. When a 230 v control power source is used, set the voltage selector switch at 230 v.

Fig. 31 Ð Oil Heater and Control Power Wiring

CARRIER COMFORT NETWORK INTERFACE Ð The Carrier Comfort Network (CCN) communication bus wiring is supplied and installed by the electrical contractor. It con- sists of shielded, 3-conductor cable with drain wire.

The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it.

The negative pins must be wired to the negative pins. The signal ground pins must be wired to the signal ground pins. See Fig. 24 for location of the CCN network connector (COMM1) on the processor module.

NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. In- dividual conductors must be insulated with PVC, PVC/ nylon, vinyl, Te¯on, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Te¯on with a minimum operating tempera- ture range of −4 F to 140 F (−20 C to 60 C) is required. See table below for cables that meet the requirements.

MANUFACTURER

CABLE NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

 

 

When connecting the CCN communication bus to a sys- tem element, a color code system for the entire network is recommended to simplify installation and checkout. The fol- lowing color code is recommended:

SIGNAL TYPE

CCN BUS CONDUCTOR

COMM1 PLUG

INSULATION COLOR

PIN NO.

 

+

Red

1

Ground

White

2

Black

3

If a cable with a different color scheme is selected, a simi- lar color code should be adopted for the entire network.

At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. See Fig. 25. If the communication bus cable exits from one build- ing and enters another, the shields must be connected to ground at the lightening suppressor in each building where the cable enters or exits the building (one point only).

To connect the 19XR chiller to the network, proceed as follows (Fig. 24 and 25):

1.Cut power to the PIC control panel.

2.Remove the COMM1 plug from the processor module.

3.Cut a CCN wire and strip the ends of the RED, WHITE, and BLACK conductors.

4.Using a wirenut, connect the drain wires together.

5.Insert and secure the RED wire to Terminal 1 of the COMM1 plug.

6.Insert and secure the WHITE wire to Terminal 2 of the COMM1 plug.

7.Insert and secure the BLACK wire to Terminal 3 of the COMM1 plug.

8.Mount a terminal strip in a convenient location.

9.Connect the opposite ends of each conductor to separate terminals on the terminal strip.

10.Cut another CCN wire and strip the ends of the conductors.

11.Connect the RED wire to the matching location on the terminal strip.

12.Connect the WHITE wire to the matching location on the terminal strip.

13.Connect the BLACK wire to the matching location on the terminal strip.

34

Image 34
Contents Installation Instructions Contents Model Number Identication Front TOP View Frame Size Compressor Cooler Maximum VesselChain Length LengthMachine Rigging Guide Cooler Size 70 Through DIM. ``A DIM. ``B DIM. ``CHeat Exchanger Size19XR Nozzle Size 19XR Dimensions Marine WaterboxFrame English 19XR Compressor Weights19XR Component Weights Code19XR Heat Exchanger Data 19XR Additional Data for Marine Waterboxes Heat Waterbox Frame Exchanger Description Ð 19XR Waterbox Cover WeightsCondenser SI kg Cooler, Side View 19XR Chiller Top View Chiller End View 20-22 Dimensions ft-in15-17 30-32Standard Isolation Typical Nozzle Piping COM Ð CommonPiping Flow Data NIH, Frames 1 Through Frames 1, 2, Frames 4, 5,Condenser Waterboxes OutOut Arrangement Marine Waterboxes Frames 2Code Piping Flow Data MWB, Frames 4 Through Marine Waterboxes Frames 4, 5,Nominal Pipe Size Actual Pipe ID 19XR Waterbox Nozzle SizesFrame Pressure Pass Psig kPa Cooler Condenser0452 Tank Size0428 QTY Trade Size LocationMaximum Refrigerant Capacity lb Weight Size ANSI/ASHRAETank Tank OD DRY Maximum Refrigerant Capacity kgOptional Pumpout System Piping Schematic with Storage Tank Quantity Relief Valve ConnectorRelief Device Locations Outlet SizeCarrier Comfort Network Communication Bus Wiring 19XR with Optional Unit-Mounted Starter 19XR with Free-Standing Starter RLA 19XR Typical Field Wiring with Free-Standing Starter Manufacturer Cable no Install Field Insulation Page Page Copyright 1997 Carrier Corporation Installation START-UP Request Checklist Testing YES/NO Date to be Completed
Related manuals
Manual 140 pages 13.24 Kb

19XR specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.