GE HG Series, SG Series Inspect Shipment, Combustion and Ventilation Air, Corrosive Atmospheres

Page 8

Safety Instructions

Installing the water heater.

Inspect Shipment

Inspect the water heater for possible damage. Check the markings on the rating plate of the water heater to be certain the type of gas supplied corresponds to the water heater requirements.

Combustion and Ventilation Air

Troubleshooting Tips Care and Cleaning Operating Instructions Installation Instructions

Proper operation of the water heater requires air for combustion and ventilation. Provisions for combustion and ventilation air must comply with referenced codes and standards.

When installed in a closet, DO NOT block or obstruct any of the combustion air inlet openings located around the perimeter of the water heater. A minimum of 1” is required between these combustion air inlet openings and any obstruction.

NOTICE: If the water heater is installed in an unconfined space within a building of conventional frame, masonry or metal construction, infiltration air is normally adequate for proper combustion and ventilation. If the water heater is installed in a confined space, provisions for combustion and ventilation air must be made.

A confined space is one having a volume of less than 50 cubic feet per 1000 Btuh of the aggregate input of all appliances within that space.

The air must be supplied through two permanent openings of equal area. One is to be located within 12” above the floor and the other is to be located within 12” from the ceiling.

The minimum net free area of each opening must not be less than one square inch per 1000 Btuh of the total input rating of all

the appliances in the enclosure (but not less than 100 square inches), if each opening communicates with other unconfined areas inside the building.

Buildings of unusually tight construction shall have the combustion and ventilation air supplied from outdoors, or a freely ventilated attic or crawl space.

If air is supplied from outdoors, directly or through vertical ducts, there must be two openings located as specified above and each must have a minimum net free area of not less than one square inch per 4000 Btuh of the total input rating of all the appliances in the enclosure.

If horizontal ducts are used to communicate with the outdoors, each opening must have a minimum net free area of not less than one square inch per 2000 Btuh of the total input rating of all the appliances in the enclosure. If ducts are used, the minimum dimensions of rectangular air ducts shall not be

less than 3”.

NOTICE: If the duct openings which supply combustion and ventilation air are to be covered with a protective screen or grill, the net free area (openings in the material) of the covering material must be used in determining the size of the openings. Protective screening for the openings MUST NOT be smaller then 1/4” mesh to prevent clogging by lint or other debris.

Customer Service

NOTICE: The water heater should not be installed near an air supply containing halogenated hydrocarbons.

Corrosive Atmospheres

The air in beauty shops, dry cleaning establishments, photo processing labs, and storage areas for liquid and powdered bleaches or swimming pool chemicals often contain such halogenated hydrocarbons.

An air supply containing halogenated hydrocarbons may be safe to breathe, but when it passes through a gas flame corrosive elements are released that will shorten the life of any gas burning appliance.

Propellants from common spray cans or gas leaks from A/C and refrigeration equipment are highly corrosive after passing through a flame.

The water heater warranty is voided when failure of the heater is due to operation in a corrosive atmosphere.

8

Image 8
Contents Part No. AP13204-4 01/05 Pub. No -50103 JR To do so may result in an explosion or fireDo not try to light any appliance Safety Information Installation InstructionsCare and Cleaning Troubleshooting TipsInstall the Draft Hood and Properly Vent the Water HEATER… Time/Temperature Relationship in Scalds At its lowest settingWas set Was shipped fromSafety Instructions Installation Care and Cleaning Customer Service Troubleshooting TipsInstalling the water heater Safety InstructionsTop View Alcove Top View ClosetCustomer Service Inspect ShipmentCombustion and Ventilation Air Corrosive AtmospheresTypical Installation Troubleshooting Tips CustomerThermal Expansion Water Supply ConnectionsCare and Cleaning Operating Relief ValveTo Fill the Water Heater CondensationLeak Testing Pressure Testing the Gas Supply SystemGas Supply High AltitudeInstructions VentingInsulation Blankets Hot and Cold Pipe Insulation Installation During Installation of this water heater…Care and Cleaning Troubleshooting Tips Customer Service Heat TrapsWater Supply Installation checklistWater Heater Location Combination Potable and Space Heating Application Requires water for space heating atLighting the water heater. With SmartWater Ignition System Safety Precautions Water Temperature SettingTime/Temperature Relationship in Scalds Operating the water heaterCustomer Water Temperature Setting…Service Troubleshooting Tips Care and cleaning of the water heater Routine Preventative MaintenanceSafety Draining the Water HeaterVenting System Inspection Burner InspectionVacation and Extended Shut-Down Anode RodBefore you call for service… Problem Possible Causes What To DoScale and sediment Clean tank Tank Troubleshooting Tips Installation Instructions Instructions For Placing a Parts Order Replacement partsBurner Assembly Kit If you need service… Please place in envelope and mail to Model Number Serial Number Water Heater Model Number Serial Number