Installing the water heater:

Proper operation of the water heater requires air for combustion and ventilation. Provisions for combustion and ventilation air must comply with referenced codes and standards.

Combustion and Ventilation Air (Indoor Water Heater Only)

Air Openings

Min. 200 Sq. In.

(1290 cm2 )

Min. 3" (7.6 cm)

DANGER: OUTDOOR water heaters must not be installed indoors or in a confined space. Install outdoor water heaters outdoors only.

NOTICE: If the water heater is installed in an unconfined space within a building of conventional frame, masonry or metal construction, infiltration air is normally adequate for proper combustion and ventilation. If the water heater is installed in a confined space, provisions for combustion and ventilation air must be made.

A confined space is one having a volume of less than 50 cubic feet (1.4 cubic meters) per 1000 Btuh of the aggregate input of all appliances within that space.

The air must be supplied through two permanent openings of equal area. One is to be located within 12” (30 cm) above the floor and the other is to be located within 12” (30 cm) below the ceiling.

The minimum net free area of each opening must not be less than one square inch (6.5 sq cm) per 1000 Btuh of the total input rating of all the appliances in the enclosure (but not less than 100 square inches (650 cm2),) if each opening communicates with other unconfined areas inside the building.

Buildings of unusually tight construction shall have the combustion and ventilation air supplied from outdoors, or a freely

ventilated attic or crawl space.

If air is supplied from outdoors, directly or through vertical ducts, there must be two openings located as specified above and each must have a minimum net free area of not less than one square inch

(6.5 sq cm) per 4000 Btuh of the total input rating of all the appliances in the enclosure.

If horizontal ducts are used to communicate with the outdoors, each opening must have a minimum net free area of not less than one square inch

(6.5 sq cm) per 2000 Btuh of the total input rating of all the appliances in the enclosure. If ducts are used, the minimum dimensions of rectangular air ducts shall not be less than 3” (7.6 cm).

NOTICE: If the duct openings which supply combustion and ventilation air are to be covered with a protective screen or grill, the net free area (openings in the material) of the covering material must be used in determining the size of the openings. Protective screening for the openings MUST NOT be smaller than 1/4” (0.64 cm) mesh to prevent clogging by lint or other debris.

NOTICE: The water heater should not be installed near an air supply containing halogenated hydrocarbons.

Corrosive Atmospheres

The air in beauty shops, dry cleaning establishments, photo processing labs, and storage areas for liquid and powdered bleaches or swimming pool chemicals often contain such halogenated hydrocarbons.

An air supply containing halogenated hydrocarbons may be safe to breathe, but when it passes through a gas flame corrosive elements are released that will shorten the life of any gas burning appliance.

Propellants from common spray cans or gas leaks from A/C and refrigeration equipment are highly corrosive after passing through a flame.

The water heater warranty is voided when failure of the heater is due to operation in a corrosive atmosphere.

Inspect Shipment

Inspect the water heater for possible damage. Check the markings on the rating plate of the water heater to be certain the type of gas supplied corresponds to the water heater requirements. Verify all included parts are present (see below).

 

Certificate of

Use & Care Manual

 

 

Residential Gas

 

 

Warranty

Tankless Water Heaters

 

 

Limited

 

 

PRIORITY

COMMERCIAL

 

 

°F

Wood Screw x 5pcs.

 

 

 

!

 

 

 

!

 

POWER

 

!

 

 

 

 

ON/OFF

 

 

 

 

Warranty

 

 

Remote Control

Washer x 4 pcs.

 

Manual Appliance

Assembly Kit

 

 

Use & Care Manual

Gas Shut-off Valve

 

 

9

Image 9
Contents Tankless Water Heater You can find them on a label on the appliance That will result in death or seriousInjury Installand Properly Vent the Water HEATER… N G E R Natural GAS and Liquefied Petroleum Models Read and Follow this Safety Information Carefully Location of Indoor Water Heater Installing the Indoor water heaterLocation of the Outdoor water heater Installing the Outdoor water heaterCombustion and Ventilation Air Indoor Water Heater Only Installing the water heaterCorrosive Atmospheres Inspect ShipmentWater Supply Connections Mounting the Water HeaterLines.Relief Relief ValvePressure Testing the Gas Supply System Leak TestingGas Supply High AltitudeVenting Lengths VentingMaximum Vent Length Minimum Vent LengthVenting Through Closed Spaces Vent AdapterDraining the Condensate Horizontal Vent Terminal Location US InstallationsAdditional Considerations Indoor Water HeaterVent Horizontal Wall Thimble Installation Vertical Vent Termination Location Vertical Vent InstallationRemote Control Remote Control InstallationAvailability Model Number DescriptionConnecting the remote control to the water heater Installing the Main Remote ControlElectrical Connection Power Cord Indoor water heaters onlyNot Supplied Typical Installation of Indoor Water HeaterTypical Installation of Outdoor Water Heater Installing the water heaterDuring Installation of this water heater Hot and Cold Pipe Insulation InstallationInsulation Blankets Do’sInstallation Check List To Turn OFF GAS to Appliance Lighting the water heaterWater Temperature Setting Safety PrecautionsTime/Temperature Relationship in Scalds Operating the water heaterWater Temperature Setting… Routine Preventative Maintenance HousekeepingDrain heater. See Draining The Water Heater section on Venting System Inspection Burner InspectionVacation and Extended Shut-Down Freeze Protection Draining the Water HeaterBefore You Call For Service… Outdoor Water Heater Only Indoor Water Heater OnlyInstructions For Placing a Parts Order Replacement PartsTemperature Setting DIP Switch Adjustment If YOU Need Service