VI. Service Instructions

A.The Alliance™ is intended to provide a service life of many years. Components that require service, however, may be subject to failure. Failure to use the correct procedures or parts in these circumstances may make the water heater unsafe.

The owner should arrange to have the following inspections and simple maintenance procedures performed by qualified service personnel at the frequencies suggested.

1.Boiler and Domestic Water Piping (Annual) Check all piping for signs of leakage at joints, unions, and shut-off valves. Repair as needed.

2.Temperature-Pressure Relief Valve (Annual) Follow instructions packed with valve.

3.Sediment (Annual, but harsh water quality may dictate more frequent service)

Depending on water conditions, a varying amount of sediment may collect in the tank. Levels requiring service are indicated by a small temperature difference in the supply and return lines. (See also "Scale" below.) Repeated flushing usually clears such material. As a preventive measure, water should be drawn from the tank at the drain valve until it runs clear.

4.Scale (Annual)

Hard water may cause scale to build-up on the outside of the heat exchanger coil. A water softener will prevent this problem. (See also "Sediment" above.) Symptoms would be reduced recovery capacity or reduced temperature differential between boiler supply and return lines. Repeated flushing should resolve the problem. If not, proceed to B.

B. Chemical cleaning of heat exchanger coil

1.To avoid water damage to nearby areas in subsequent steps, shut off the cold water supply to the water heater.

2.Make a note of the temperature control setting on the water heater, then turn the unit off.

3.Relieve the water pressure in the tank by opening a hot water faucet. This will reduce the risk of scald injury.

4.Remove the relief valve from the water heater taking care to avoid contact with the hot water

which may drain out of the lines leading to the domestic uses.

5.Drain the water heater until the water within the tank is even with the top of the heat exchanger coil. The water heater cover plate should be removed from the tank to view the inside of the tank and assure the coil is just covered with water.

6.Using a funnel, pour one gallon of commercial ice maker cleaning solution into the tank through the cover plate opening. Follow solution manufacturer's instructions, cautions and warnings.

7.Set the water heater's temperature control to its highest setting and operate the system until the control is satisfied. Boiler may cycle on its high limit several times during this period. If the tank temperature setting has not been satisfied after 45 minutes of boiler operation, turn aquastat to the lowest setting to stop boiler operation.

8.Allow heated solution to set in tank for 30 minutes.

9.Drain tank completely using fittings and hose, as required, to reach a floor drain.

10.Fill the water heater's tank with fresh, cold, conditioned water and drain completely at least two

(2) times to flush all cleaning solution from the tank.

11.Reinstall the relief valve, cover plate, and piping.

12.Open the cold water supply and fill the tank with water. Then purge air from lines and tank by operating hot and cold water faucets in the house.

13.Return the temperature control to the setting noted in Step 2.

C. Alternate heat exchanger coil cleaning methods

The chemical cleaning process is most effective if done properly. Other methods may also give satisfactory results including, high velocity water wash using a wand through the cover plate.

17

Image 17
Contents INDIRECT-FIRED Water Heaters For Single Water Heater InstallationsT IC E General Information Table of ContentsAlliance Water Heater Dimension Inches Important Decisions Required Before Installation II. Pre-InstallationDomestic Hot Water Priority Two options are Removal of Existing Domestic Water Heating System Hot Water and Relief Valve Piping III. PipingCold Water Supply Piping Water Boiler Piping with Zone Valves and a Boiler Bypass Page Page Page Page IV. Electrical Operation VI. Service Instructions Problem Cause Solution VII. Trouble ShootingVIII. Repair Parts Urnham Corporation Regional Offices Inspection / Service Schedule

53A, 40A, 79A, AL-26A specifications

The Burnham line of engineering includes several models known for their efficiency, advanced technology, and adaptability to various applications. Notably, the Burnham 40A, 53A, AL-26A, and 79A are among the most respected in the industry, each offering distinct features tailored to meet the needs of residential and commercial users.

The Burnham 40A is a versatile boiler designed for small to medium-sized applications. One of its main features is its efficient heat exchange system, which maximizes the transfer of heat while minimizing energy consumption. This model incorporates advanced burners that provide uniform heating and enhanced fuel efficiency, ensuring lower operational costs for users. Additionally, it is engineered to be compatible with different fuel types including natural gas and propane, providing versatility and flexibility for installations.

The Burnham 53A, on the other hand, emphasizes durability and reliability. This model is built with a robust steel construction, designed to withstand harsh conditions while maintaining a low maintenance profile. The hybrid design allows for a more significant heat output, making it suitable for larger spaces. Moreover, its integrated control system offers precise temperature management, essential for both comfort and energy savings.

In the portfolio, the AL-26A stands out due to its advanced automation technology. This model features smart control mechanisms that facilitate easy monitoring and adjustments. Users can optimize performance through a user-friendly interface, attracting those who value convenience. Furthermore, the AL-26A has enhanced safety features that ensure reliable operation, reducing the risk of malfunctions.

Finally, the Burnham 79A is a powerhouse, specifically engineered for heavy-duty commercial applications. With high-capacity output, it is capable of meeting demanding heating requirements without sacrificing efficiency. This model incorporates sophisticated insulation technologies that reduce heat loss, thus promoting energy conservation. Its design ensures ease of access for maintenance, thereby extending the lifecycle of the boiler.

In conclusion, the Burnham 40A, 53A, AL-26A, and 79A are exemplary models that reflect the brand's commitment to quality and innovation. Each model boasts unique features and advanced technologies, allowing users to select the best fit for their specific heating needs. As industry leaders, Burnham products continue to set the standard for performance and efficiency in the boiler market.