Desa VYM27NRPR Providing Adequate Ventilation, Determining FRESH-AIR Flow for Heater Location

Page 5

AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation Determining Fresh-Air Flow For Heater Location

5

AIR FOR COMBUSTION AND VENTILATION

Continued

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 4 through 6 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6x10-11kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable win- dows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Heater Loca- tion, column 2.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. See next page for your options.

For morevisit www..com

110398-01A

Image 5
Contents FLAME-MAX OWNER’S Operation and Installation ManualVYM27NR/PR FVFM27NR/PR What to do if YOU Smell GASSafety Information Table of ContentsProduct Identification Product IdentificationRemote Control Accessories Product FeaturesLocal Codes UnpackingDetermining FRESH-AIR Flow for Heater Location Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined SpaceVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation and Clearances InstallationCheck GAS Type Minimum Fireplace Clearance to Combustible MaterialsMinimum Noncombustible Material Clearances If Using MantelMantel Clearances Determining Minimum Mantel Clearance When using a HoodFloor Clearances Determining Minimum Mantel ClearanceInstallation Items Needed Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Attaching Base Assembly to Fireplace Floor Connecting to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Heater Gas Connections Checking Gas Joints for Natural Gas Installing LogsLighting Instructions For Your Safety Read Before LightingOperating Heater Optional Remote Operation Manual Lighting ProcedureTo Turn OFF GAS to Appliance Pilot Flame Pattern Inspecting BurnersBurner Flame Pattern Ghrcta Series OperationCleaning Burner Injector Holder and Pilot AIR Inlet Hole Cleaning MaintenanceBurner Primary AIR Holes Main BurnerObserved Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Top Gas leak. See Warning statement atSpecifications Wiring DiagramService Hints Technical ServiceVYM27NR, VYM27PR FVFM27NR, FVFM27PR Illustrated Parts BreakdownVYM27NR VYM27PR FVFM27NR FVFM27PR Parts ListWALL-MOUNT Thermostat Switch GWMT1 Receiver and HAND-HELD Remote Control KIT GhrcWALL-MOUNT ON/OFF Switch GWMS2 Cleaning KIT GCKOwners Registration Form Tape 110398-01A Warranty Information

VYM27NRPR specifications

Desa VYM27NRPR is a highly advanced imaging device designed for a multitude of applications, from medical diagnostics to industrial inspections. This remarkable equipment integrates cutting-edge technologies to provide exceptional image quality and versatility.

One of the primary features of the VYM27NRPR is its high-resolution imaging capability. With an advanced sensor that supports multiple resolutions, users can capture stunning images with clarity, revealing intricate details that are crucial for accurate assessments. The device supports a wide range of imaging modes, including grayscale, color, and infrared, allowing users to choose the most suitable option for their specific needs.

Incorporating state-of-the-art image processing technologies, the VYM27NRPR utilizes sophisticated algorithms to enhance the quality of captured images. Features such as noise reduction, contrast enhancement, and edge detection ensure that users receive optimized images, which are vital in fields like medical diagnostics where precise evaluation is essential.

Moreover, the VYM27NRPR comes equipped with advanced connectivity options. Its compatibility with various interfaces, including USB, HDMI, and Wi-Fi, allows for seamless integration with other devices and systems. This connectivity is crucial for data sharing, enabling users to quickly transfer images and collaborate with other professionals in real-time.

The device is designed with user experience in mind. Its intuitive interface offers easy navigation through various settings and modes, ensuring that users can operate it effortlessly. Additionally, the VYM27NRPR features customizable settings, allowing professionals to tailor the device according to their preferences and specific workflows.

Durability is another hallmark of the VYM27NRPR. Built with robust materials, the device is designed to withstand harsh environments, making it suitable for fieldwork in diverse conditions. Furthermore, it has a lightweight design, enabling portability without compromising on performance.

In summary, Desa VYM27NRPR stands out for its high-resolution imaging, advanced processing capabilities, seamless connectivity, user-friendly interface, and durability. This comprehensive suite of features makes it an invaluable tool for professionals across various sectors, revolutionizing how images are captured, processed, and analyzed. As technology continues to evolve, devices like the VYM27NRPR will play a pivotal role in enhancing the accuracy and efficiency of imaging tasks, setting new standards in the industry.