Desa CGD3924N AIR for Combustion and Ventilation, Determining AIR Flow for Heater Location

Page 6

AIR FOR COMBUSTION AND VENTILATION

Continued

6

DETERMINING AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr

the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

___________________ Btu/Hr

Gas water heater*

 

___________________ Btu/Hr

Gas furnace

 

___________________ Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Other gas appliances*

+ ___________________ Btu/Hr

Total

= ___________________ Btu/Hr

Example: Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

39,000

Btu/Hr

Total

=

 

 

Btu/Hr

79,000

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________

Btu/Hr (maximum the space can support)

_________________

Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200

Btu/Hr (maximum the space can support)

79,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

102828

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety Information Burner patterns can cause sooting Operation Local Codes Unpacking Product FeaturesSafety Device Piezo Ignition SystemAIR for VentilationProviding Adequate Ventilation AIR for Combustion and Ventilation Determining AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRTion and ventilation air by one of the methods described Ventilation Air From OutdoorsInstalling Check GAS TypeLOG Sizing Requirements Minimum Fireplace ClearanceTo Combustible Materials Minimum Wall and Ceiling Clearances see FigureMinimum Non Combustible Material Clearances Installing Minimum Non Combustible Material Clearances Log SetFloor Clearances Installing Damper Clamp Accessory for Vented Operation Attaching Damper ClampInstalling Heater Base Assembly Installation Items NeededMounting Bracket Connecting to GAS Supply Checking GAS Connections Gas ConnectionPressure Testing Heater Gas Connections Test Pressures Equal To or Less Than 1/2 PsigInstalling Installing LogsFor Your Safety Read Before Lighting Operating HeaterHeater OperatingOperating Heater Inspecting Burners Pilot Flame PatternTrouble Shooting CleaningMaintenance ODS/PILOT and BurnerMaintenance, TROUBLE- ShootingRefer to Air for Com Gas leak. See Warning Technical Service Service HintsModel Parts Under Warranty Parts Not Under WarrantyParts Central Hood GA6050 AccessoriesValve GA5010 Hood GA6052Illustrated Parts Breakdown Parts List KEY Part Number Description QTYWarranty Information Keep this Warranty