Desa CGD3924N installation manual Pressure Testing Heater Gas Connections

Page 18

INSTALLING

Continued

18

3.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Re-connect heater and manual shutoff valve to gas supply. Check re-connected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Figure 14).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.Open manual shutoff valve (see Figure 14).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 20 through 22). Check all other internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 21).

Open

Manual

Shutoff

Valve

Closed

Figure 14 - Manual Shutoff Valve

Manual

 

Shutoff

Control Valve Location

Valve

 

Gas Meter

 

Figure 15 - Checking Gas Joints

102828

Image 18
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety Information Burner patterns can cause sooting Operation Local Codes Unpacking Product FeaturesSafety Device Piezo Ignition SystemAIR for VentilationProviding Adequate Ventilation AIR for Combustion and Ventilation Determining AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRTion and ventilation air by one of the methods described Ventilation Air From OutdoorsInstalling Check GAS TypeLOG Sizing Requirements Minimum Fireplace ClearanceTo Combustible Materials Minimum Wall and Ceiling Clearances see FigureMinimum Non Combustible Material Clearances Installing Minimum Non Combustible Material Clearances Log SetFloor Clearances Installing Damper Clamp Accessory for Vented Operation Attaching Damper ClampInstalling Heater Base Assembly Installation Items NeededMounting Bracket Connecting to GAS Supply Checking GAS Connections Gas ConnectionPressure Testing Heater Gas Connections Test Pressures Equal To or Less Than 1/2 PsigInstalling Installing LogsFor Your Safety Read Before Lighting Operating HeaterHeater OperatingOperating Heater Inspecting Burners Pilot Flame PatternTrouble Shooting CleaningMaintenance ODS/PILOT and BurnerMaintenance, TROUBLE- ShootingRefer to Air for Com Gas leak. See Warning Technical Service Service HintsModel Parts Under Warranty Parts Not Under WarrantyParts Central Hood GA6050 AccessoriesValve GA5010 Hood GA6052Illustrated Parts Breakdown Parts List KEY Part Number Description QTYWarranty Information Keep this Warranty