AquaStar LP Pilot Lights but Burners will not Come on, Main Burners GO OUT During HOT Water USE

Page 15

PILOT LIGHTS BUT BURNERS WILL NOT COME ON

1.Confirm water valve assembly is working properly. See Water Valve under MAINTENANCE AND SERVICE.

2.Confirm the flame sensor is in its proper position and clean, lightly wipe clean if dirty. See Fig. 10

3.Confirm the burner electrovalve switch is functioning properly.

Measure milivoltage at burner electrovalve (see Fig. 13).

4.The Electronic Control Box (Fig. 13) may need to be replaced.

Check wire connections and test operation of electronic control box (see Fig. 13).

Fig. 13 - Electrical wiring diagram

1

burner electrovalve

8

electronic control box

2

gas control valve

9

LED failure indicator

3

pilot electrovalve

10

LED indicator main

4

flame sensor

 

burner operation

5

pilot electrode

11

on/off switch

6

overheat sensor

12

hydro-generator

7

temperature limiter

13

flue gas safety device

MAIN BURNERS GO OUT DURING HOT WATER USE

1.Flow rate diminished below activation rate Increase hot water flow rate.

2.Unbalanced pressure in the water lines

The added restriction caused by the 125 HX in the hot water system can result in uneven pressures between the cold and the hot. In such cases when mixing cold water at the tap, the lower hot water pressure may be overpowered by a much higher cold water pressure, which may cause the 125 HX burners to shut down. Make sure faucet aerators and showerheads are free of minerals and dirt. Do not add any flow restrictor to the shower head.

3.Minimum inlet pressure on well is inadequate Check the inlet water pressure. On a private well, raise the minimum pressure setting to 30 psi. Confirm that the pressure tank is not water logged.

4.ECO (overheat sensor) tripped due to overheating re-ignite the appliance 10 minutes later. If it happens again, contact your service person.

5. Flue gas safety device tripped

Ventilate the room and operate the appliance 10 minutes later. Provide more combustion air to the room and/or inspect and correct venting system. Afterwards, if it happens again, contact your service person.

WATER IS TOO HOT

1. Temperature Selection too high

Turn the temperature adjustment knob counter-clockwise (to the left) to lower the maximum water temperature. Note: This will increase the activation flow rate.

2.Inlet water temperature is too hot (as with solar preheated water or high ground water temperatures)

Decrease gas pressure. Note: Only the model 125B LPS or 125B NGS should be used if the inlet water is preheated.

3. Ground water temperature is very warm

Reduce inlet gas supply to heater when inlet water temperature is very warm (60-70 F). See also HOT WATER TEMPERATURE FLUCTUATES / UNIT DEACTIVATED.

WATER IS NOT HOT ENOUGH

1. Temperature selection too low.

Change the setting. Turn the temperature adjustment knob clockwise (to the right).

Note: This will decrease the activation flow rate.

2.Btu input is too low due to insufficient gas pressure It is extremely important for a tankless instantaneous water heater to have the right size gas line to obtain

the correct gas pressure

See specifications on page 3. Unlike storage tank water heaters, the burners of a tankless water heater must be very powerful to heat water instantaneously since they do this only at the time hot water is actually being used. It is therefore imperative that the gas pressure requirement be met exactly. Insufficient gas pressure will directly affect the water temperature at the time of usage. See page 3 for correct gas pressure settings and fig. 5 for locations where gas pressures are taken.

3.Btu input is too low due to insufficient gas supply Make sure your main gas line is fully opened. If using LP gas, be sure that the size of the propane tank is adequate to supply the required gas pressure.

4.Cold water is mixing with the hot water between the

125HX and the outlet

Compare water temperature at outlet of the 125 HX (hold the 125 HX outlet pipe with your hand) and at the tap. If these two are very different, check for mixing valve or plumbing crossover (see “NO SPARK AT THE PILOT” paragraph #2).

5.Parts in water valve are dirty or damaged, which will prevent the gas valve from being fully opened.

Water valve maintenance needs to be performed, see #6 under NO SPARK AT THE PILOT

6 720 606 804

15

Image 15
Contents For Your Safety Table of ContentsWhat to do if YOU Smell GAS 720 606 Required Natural Gas Pressure at inlet FeaturesUnpacking the 125 HX Heater Principle of OperationTOP a Front B Back Sides Floor C Vent Diameter Front View Side ViewGeneral Rules to Follow For Safe Operation Proper Location for Installing Your HeaterMounting Installation Combustion AIR RequirementsClearances Venting Plasterboard, can cause failure of mountingVent pipe connection Masonry Chimneys Existing Interior Masonry ChimneyTile Lined Interior Masonry Chimney 10.5 GAS ConnectionsGAS Line Sizing 6 Adaptor Used on High AltitudeFor Natural GAS For LP GASSource National Fuel Gas Code Nfpa 54, Ansi Z223.1 For Your Safety Read Before Operating Your HOT Water Heater Water ConnectionsOperating Instructions Setting the Water Temperature Lighting and Operating InstructionsTo Turn OFF GAS to Appliance Not enlarge the orifice Maintenance and ServiceTrouble Shooting Review Maintenance Table on the Back of this ManualNo Spark AT the Pilot Water is TOO HOT Ground water temperature is very warmPilot Lights but Burners will not Come on Main Burners GO OUT During HOT Water USEHOT Water Temperature Fluctuates / Unit Deactivated Diagram of 125 HX Interior Components Diagram and Parts List Interior Components Diagram Parts List 125 HX Flow chart of 125 HX General Twelve Year Limited Warranty720 606 720 606 Controlled Energy Corp Maintenance Table see