AquaStar LP, 125HXNG GAS Connections, GAS Line Sizing, Adaptor Used on High Altitude, 10.5

Page 9

draft diverter outlet must be connected to an unobstructed vent of the same size, or larger.

In Canada, CAN/CGA-B149 Installation Code for detailed requirements

In U.S.A., ANSI Z223.1 - NFPA 54, National Fuel Gas Code for detailed requirements.

The vent connection for the 125 HX is 5 inches. However, for installations at high altitude (over 2000 feet above sea level) a six inch vent is required. A 5" by 6" vent adaptor must be affixed to the flue collar of the 125 HX with at least two screws. See fig. 4.

WARNING: Failure TO INCREASE THE VENT SIZE TO SIX INCHES AND/or assure that the manifold pressure

is set to proper value listed for applications at high altitudes will cause unsafe venting, asphyxiation, and will void CSA Certification.

5” X 6” ADAPTOR

USED ON HIGH ALTITUDE

Fig. 4 - Vent Adaptor for High Altitude Installations

GAS CONNECTIONS

NOTE: The 125 HX is supplied with a gas pressure regulator that must be installed on the heater before attaching the gas supply line. See fig. 5. Failure to install the gas regulator as shown in figure 5 will be a violation of CSA certification of the unit. The regulator supplied with the heater is preset for the gas shown on the rating plate to the correct pressure. It is an appliance level regulator designed for (low inlet) pressure (less than 1/ 2 Psig or 15” W.C.)

DO NOT connect to an unregulated or high pressure propane line or to a high pressure commercial natural gas line.

GAS INLET PIPE

PRESSURE TAP

PLASTIC VENT CAP

PRESSURE REGULATOR (with directional arrow on reverse side pointing upward)

Fig. 5 - Installation of Gas Pressure Regulator

The pressure regulator provided with the heater is adjusted to deliver the proper gas pressure (as indicated on the rating plate and in the manual for altitude up to 2000 feet (660 meters) above sea level. On appliances being installed above 2000 ft (660 meters) elevation, the inlet gas pressure should be set at installation to the value shown below.

NOTE: The gas pressures specified below refer to pressures taken at the pressure tap on the gas inlet pipe just above the regulator (See Fig 5). These readings should be taken while the heater is operating at full input

i.e. maximum water flow with the temperature dial selector turned all the way clockwise.

MAXIMUM INLET GAS FLOW PRESSURE SETTING

Altitude

Natural Gas

Liquid Propane

 

inches W.C:

inches W.C:

0' - 2.000 ft

5.7"

10.5"

2.000 ft - 4.500 ft

4.6"

8.4"

Above 4.500 ft consult your local gas provider.

GAS LINE SIZING

-It is strongly recommended that the Natural Gas pipe be Black Iron pipe the entire distance from the outside meter to the inlet of the 125 HX regulator. 1/2” Black Iron pipe up to 10 feet, 3/4” Black Iron pipe up to 40 feet and 1” Black Iron pipe up to 150 feet distances. Flex line tubing is NOT recommended, but if used then oversize it.

-It is strongly recommended that the LP Gas pipe be semi-rigid copper or Black Iron pipe from the outside regulator to the inlet of the 125 HX regulator. For semi- rigid copper piping: 5/8” up to 20 feet and 3/4” up to 60 feet distances. For Black Iron piping: 1/2” up to 45 feet and 3/4” up to 160 feet distances. Flex line tubing is NOT recommended, but if used then oversize it.

THESE FIGURES ARE FOR 125 HX SUPPLY ONLY, ALL OTHER APPLIANCES IN THE BUILDING WILL NEED TO BE INCLUDED IN THE PIPE SIZING.

National Fuel Gas Code requires that a sediment trap (drip leg) be installed on gas appliances not so equipped. The drip leg must be accessible and not subject to freezing conditions. Install in accordance with the recommendations of the serving gas supplier.

WARNING: The heater must be disconnected from the gas supply piping system during any pressure testing of

that system at test pressures in excess of 0.5 psig.

The water heater must be isolated from the gas supply piping system by closing the manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or more than 0.5 psig.

The water heater, including the pressure regulator provided with it, must not be operated at gas supply pressures in excess of 0.5 psig. If overpressure has occurred, such as through improper testing of the gas lines or malfunction of the supply system, the gas valve and regulator must be checked for safe operation. Make sure that the regulator vent is protected against blockage.

When your connections are made, check for gas leaks at all joints (not just the ones you made). Apply some soapy water to all gas fittings and gas valve. Soap bubbles are a sign of a leak.

NOTE: Do not apply soap solution to the pilot or pilot orifice area. If you have a leak, shut off the gas. After verifying that required gaskets are in place, tighten appropriate fittings to stop leak. Turn the gas on and check again with a soapy solution. Never test for gas leaks using a match or flame.

6 720 606 804

9

Image 9
Contents For Your Safety Table of ContentsWhat to do if YOU Smell GAS 720 606 Unpacking the 125 HX Heater FeaturesPrinciple of Operation Required Natural Gas Pressure at inletTOP a Front B Back Sides Floor C Vent Diameter Front View Side ViewGeneral Rules to Follow For Safe Operation Proper Location for Installing Your HeaterMounting Installation Combustion AIR RequirementsClearances Venting Plasterboard, can cause failure of mountingVent pipe connection Masonry Chimneys Existing Interior Masonry ChimneyTile Lined Interior Masonry Chimney GAS Line Sizing GAS Connections6 Adaptor Used on High Altitude 10.5For Natural GAS For LP GASSource National Fuel Gas Code Nfpa 54, Ansi Z223.1 For Your Safety Read Before Operating Your HOT Water Heater Water ConnectionsOperating Instructions Setting the Water Temperature Lighting and Operating InstructionsTo Turn OFF GAS to Appliance Trouble Shooting Maintenance and ServiceReview Maintenance Table on the Back of this Manual Not enlarge the orificeNo Spark AT the Pilot Pilot Lights but Burners will not Come on Ground water temperature is very warmMain Burners GO OUT During HOT Water USE Water is TOO HOTHOT Water Temperature Fluctuates / Unit Deactivated Diagram of 125 HX Interior Components Diagram and Parts List Interior Components Diagram Parts List 125 HX Flow chart of 125 HX General Twelve Year Limited Warranty720 606 720 606 Controlled Energy Corp Maintenance Table see