Bradford-White Corp UTW465S60FR*N, UTW450S60FR*N, U2TW50T*FRN, U2TW65T*FRN Sequence of Operation

Page 15

Sequence of Operation

Abnormal Operation (cont’d)

B)Pressure switch or blower temperature switch failed to close: The gas control runs the blower for 30 seconds waiting for the pressure switch and/or the blower temperature switch to close. If either switch does not close in 30 seconds, the blower turns off and the control flashes 3 times with a 3 second pause. The gas control waits 2 minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as there is a call for heat or until the circuit closes.

C)Pressure switch or blower temperature switch opens during operation: The gas control turns off the pilot and main valve, runs the blower for 15 seconds (inter-purge) waiting for the pressure switch and/or the blower temperature switch to close. If either switch fails to close, the gas control proceeds as described in 3b above. If the circuit closes again by the end of the inter-purge, the recycle counter is incre- mented, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times, then 2 times with a 3 second pause. The gas control waits 5 minutes before repeating ig- nition sequence.

4.Trial for Ignition Fault:

A)Pressure switch opens during trial: The gas control turns off the ig- niter and pilot valve. The gas control proceeds as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with a trial for ignition starting at blower pre-purge.

B)Flame Not Sensed: The gas control energizes the spark igniter at- tempting to light the pilot and prove flame. If flame is not sensed within 90 seconds, the spark igniter turns off, the pilot valve is closed. The gas control LED flashes 6 times then 1 time with 3 sec- ond pause. The control waits 5 minutes before repeating the ignition sequence.

Page 15

15

Image 15
Contents Service Manual Table of Contents Page Page Bradford White ECO-DEFENDER Safety System IntroductionIntroduction How to Use this Manual How the Safety System WorksHow to Use this Manual Tools Required Tools Required for ServiceSpecifications Gallon-40,000 BTU/hr Gallon-42,000 BTU/hr Vent TablesGallon-60,000 BTU/hr Wiring Diagram Control TimingsIgnition State Timing Power Up Sequence Sequence of OperationNormal Heating Sequence Abnormal Operation Normal Heating Sequence cont’dAbnormal Operation cont’d Sequence of Operation Sequence of Operation Probable Cause Service Procedure TroubleshootingLED Status Control Status Probable Cause Service Procedure Troubleshooting Burner Maintenance Burner Cleaning ProcedureBurner Inspection Burner Cleaning Procedure cont’d Pilot Inspection, Testing and Replacement Pilot MaintenancePilot Inspection, Testing and Replacement cont’d Page Pressure Switch Testing Pressure Switch TestingPressure Switch Testing cont’d Pressure Switch Replacement Pressure Switch ReplacementBlower Testing Blower TestingBlower Testing Blower Replacement Blower InstallationBlower Removal Blower Temperature Switch Testing Blower Installation cont’dBlower Temperature Switch Testing Blower Temperature Switch Testing cont’d Switch SettingCommon causes for high Exhaust temperature Blower Temperature Switch Replacement Blower Temperature Switch ReplacementThermal Well Testing Thermal Well TestingDetermine Tank Temperature Thermal Well Testing cont’dDetermine Water Temperature Inside Tank Component Disassembly Sensor Resistance at Various TemperaturesGas Control & Thermal Well Removal From Water Heater Gas Control Removal Gas Control & Thermal Well Removal From Water Heater cont’dGas Control Removal From Thermal Well Gas Control Assembly Gas Control Assembly to the Thermal WellGas Control Removal From Thermal Well cont’d Gas Control Assembly to the Thermal Well cont’d Flammable Vapor Sensor Testing Flammable Vapor Sensor TestingVAC Circuit Trace VAC Circuit Trace Safety Circuit Voltage Trace Safety Circuit Voltage TraceBlower Removal Remove the Blower to Gain Access to the Flue BaffleRemove the Blower to Gain Access to the Flue Baffle cont’d Dip Tube Inspection and ReplacementDip Tube Inspection Anode Inspection Anode Inspection and ReplacementInner Door Removal Inner Door Removal ProcedureInner Door Gasket Replacement Inner Door Removal Procedure cont’dInner Door Gasket Replacement Procedure Inner Door Installation with Gasket Inner Door InstallationScreenLok Flame Arrestor Cleaning Procedure Arrestor CleaningCommon Terms Common TermsPart Name and Description Parts ListParts@bradfordwhite.com Techserv@bradfordwhite.com

U1TW40S*FRN, U2TW65T*FRN, UTW450S60FR*N, U1TW60T*FRN, UTW465S60FR*N specifications

Bradford-White Corp has long been a reputable manufacturer in the water heating industry, known for delivering high-quality and reliable products. Among their diverse range of water heaters, the U1TW40S*FRN, U1TW50S*FRN, U1TW60T*FRN, UTW465S60FR*N, and UTW450S60FR*N models stand out for their advanced features and technologies designed to meet varying hot water demands.

The U1TW series, including the U1TW40S*FRN, U1TW50S*FRN, and U1TW60T*FRN models, are well-suited for residential applications. Each model provides different capacities, with the numbers referring to the gallon capacities. The U1TW40S*FRN offers 40 gallons, the U1TW50S*FRN 50 gallons, and the U1TW60T*FRN 60 gallons, making them ideal for households varying in size and hot water requirements.

These models are equipped with Bradford-White's advanced Vitraglas® tank lining, a unique feature that provides superior protection against corrosion and extends the unit's lifespan by ensuring the inner tank remains free from damage. Additionally, their efficient heating elements and optimal insulation minimize heat loss, enhancing energy savings.

The UTW series, specifically the UTW465S60FR*N and UTW450S60FR*N, feature innovative technologies such as a durable stainless steel construction that offers robust performance while resisting the harmful effects of rust and degradation. This is particularly beneficial in areas with hard water, where mineral buildup can be problematic.

Each unit incorporates Bradford-White's signature HydroBurner® technology, which enhances combustion efficiency, ensuring that the water is heated quickly and consistently. This technology also helps in reducing greenhouse gas emissions, addressing environmental concerns while maintaining optimal performance.

In terms of ease of use, all models come with user-friendly controls that allow for easy temperature adjustments and monitoring, ensuring that users can customize their hot water needs conveniently. Additionally, features such as intuitive diagnostics enable quick troubleshooting, reducing downtime and maintenance efforts.

In conclusion, Bradford-White’s U1TW and UTW series water heaters are engineered to offer efficiency, durability, and user-friendly operation. With their advanced technology, excellent insulation, and robust construction, these models are a solid choice for anyone looking to invest in reliable hot water solutions for their home. Whether for a busy family or more modest hot water needs, these units provide peace of mind and consistent performance.