Bradford-White Corp Understanding Bradford White Water Heater Wiring Diagrams and Error Codes Including Code 62

Page 15

For models with Honeywell Integrated Control

System w/ Direct Spark Ignition

Serial Numbers including and AFTER GB13006174 and ALL EFR models

Lockout Conditions

The system will go into lock out mode for the following reasons:

1.ERROR CODE 62 or 63

Control board will go into “Soft Lockout” if the main burner cannot be lit or fails to prove flame after 3 ignition trials. The water heater display indicates a lockout condition by showing an error code number (62 or 63) with “Service Needed” in the control display window. Refer to error codes in the diagnostic section of this Service Manual. In a “Soft Lockout” condition, the control will wait for 60 minutes and then make 3 more attempts to light the main burners. Soft lockout reset is accomplished by depressing the lower right button under “Reset” for 3 seconds.

2.ERROR CODE 65

If the top of the tank should exceed 200°F, then the high limit control will shut off the burner and the water heater will go into a “Hard Lockout”. Error code 65 will be shown in the water heater display. The control can only be reset in the “Service Mode”, which is detailed in the “Troubleshooting” section of this Service Manual.

3.ERROR CODE 29

If the exhaust terminal becomes blocked or the condensate elbow fails to drain condensate, the normally closed exhaust pressure switch will open, the gas valve closes, and error code 29 will appear on the control display. When the condition is corrected, the error code will disappear and the water heater will resume normal operation. No resetting of the control display is needed for the pressure switch error code.

4.ERROR CODE 26

If the vent safety switch located near the exhaust pressure switch should open, the gas valve will close, the blower will post-purge and error code 26 will appear on the display. The lockout condition will reset once the problem is corrected and the switch reset. Refer to “Vent Safety Switch Testing and Replacement” in this Service Manual.

CONNECTION/WIRING DIAGRAM

CONNECTION DIAGRAM

 

 

 

 

 

 

 

 

 

 

 

BR

MV

 

 

LOWER

CONTROL

 

 

 

 

 

 

 

 

 

 

7

8

9

 

 

24V

 

 

 

 

 

 

SENSOR

 

 

 

 

BL

PV/MV

 

 

& ECO

 

 

 

 

 

 

 

 

 

 

 

4

5

6

 

 

 

 

 

 

 

 

 

 

BK

 

 

 

 

 

 

 

 

 

 

 

Y

1

2

3

 

 

 

 

 

 

GAS VALVE

 

 

BK

R GY

 

 

 

 

 

1 2 3

 

R

 

24V

 

 

R

 

P.S. (N.C.)

 

 

 

 

 

 

 

 

 

R

 

 

 

GY

 

 

 

 

 

 

 

 

 

SENSOR 1

 

 

 

GY

 

 

GY GY

COLL HIGH-LIMIT

 

 

 

 

E-COM

 

6 PIN CONNECTOR

 

LIMIT (N.C.)

 

 

 

 

 

1

 

 

TO PRESSURE

 

 

 

 

 

24V

 

 

 

 

SWITCH HARNESS

 

 

 

 

1

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

 

2

 

 

 

 

 

 

120V

 

 

O

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

3

 

4

1

 

GN

 

SENSE

 

 

 

 

 

 

 

BK

 

 

 

 

 

 

W

 

1

 

5

2

M

 

 

 

 

CONTROL

 

 

 

 

W

 

 

 

 

 

 

 

6

3

 

 

 

 

 

 

 

R

 

2

 

 

COMBUSTION HIGH VOLTAGE

 

DISPLAY

 

BK

 

3

INDUCER

 

 

1

 

E-COM

BLOWER

 

SPARK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL BOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

TOGGLE SWITCH

 

 

2

 

 

LINE IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BK LIGHT

 

 

SECONDARY

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BK

 

 

G

W

BL

Y

 

 

 

2

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

L1

 

24V

 

 

3

 

 

GN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOAD

2

 

GN

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

W

 

 

 

 

 

LINE

3

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

120V

 

 

 

 

 

 

 

 

 

 

 

 

 

PRIMARY

 

 

 

 

 

 

 

 

 

120 VOLTS AC

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

BLACK GROUND

WIRING DIAGRAM

WHITE

 

 

 

 

120 VOLTS

 

 

BLOWER MOTOR 120 VOLTS

 

 

 

 

M

 

BLOWER RELAY

120 VAC

 

 

 

 

 

 

Y

 

 

 

W

 

 

 

 

24 V.

 

P.S. TSTAT ECO

NC

 

 

 

 

COLLECTOR

 

 

 

 

 

LIMIT

 

 

 

 

 

 

DISPLAY

 

 

 

 

 

GAS VALVE

 

2

 

 

R

PV

 

5

 

 

R

MV

 

 

M

 

 

 

 

BLOWER RELAY COIL (BOARD CIRCUIT)

SENSE

W

O

HIGH VOLTAGE

SPARK

NOTE:

IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED. IT MUST BE REPLACED WITH 18. GA STRANDED 105°C WIRE OR ITS EQUIVALENT.

SI UN DES CONDUCTEURS D'ORIGINE FOURNI AVEC L'APPAREIL DOIT ETRE REMPLACE UTILISER UN CONDUCTEUR 18 GA STRANDED 105°C OU L'EQUIVALENT.

15

15

Image 15
Contents Service Manual Bradford White Page Page Page Dimensions Inches Page Page PVC, Cpvc For models prior to CF serial numbers Wiring Diagram Ignition Module For models starting with CF serial numbers and later Wiring Diagram Ignition Module Page CONNECTION/WIRING Diagram Light burned out Replace switchRepair/replace wire Harness to switchPressure Switch See Blower Testing Only power light Is on and water heater Will not functionSwitch. see Exhaust Pressure Switch See Thermostat CircuitDisplay System Observation For models with Direct Spark IgnitionSection Combustion System From previousReplace blower Blower. Is 110-120 VAC present?Pressing Select button will change display to next mode Max Setpoint value Water Heater Display Setpoint Display/Change Software Version Display only Max Setpoint continues to flash while making adjustments ExitingSELECTServiceSETMode To Display Flame Sense Current of the Pilot Flame Sensor Select SET Setpoint Idle Status Operational Idle Status Operational Error Codes and Error History Display To view previous error codes ExitingSELECTServiceSETMode Honeywell Integrated Control Error Code Resetting Error Codes in Hard Lockout Condition Next Unplug or disconnect electrical power to the water heaterDo not operate water heater without See Thermostat Potentiometer OK, thermostat is Calling for heatSee Thermostat Sensor Replace harnessAppendix a Refer to ignition module Red Wires Temperature SensorWiring Diagram Thermostat Board Replacement Procedure Hot Surface IgnitionDisconnected using a multi-meter Thermostat Potentiometer Replacement ProcedureVolt potential exposure. Isolate Thermostat Sensor Thermister Replacement ProcedureHeater not running See illustrations at right Venturi Adjustment Inlet gas Pressure tapSupply piping Gas pressure. Is it stableClear obstruction See Ignition ModuleMinimum ¾ NPT. Schedule 40 black Iron Pipe RecommendedLight? Control Board Refer to control board illustrationGas Connection PVC vent connection Combustion System Removal ProcedureGas valve Wire harness Burner mounting Screw TotalGas Combustion System Replacement ProcedureBurner Tube Removal Procedure Burner Tube Inspection Burner Tube Replacement ProcedureGas Valve Replacement Procedure Black & White Wires For Direct Spark Black wires atBlack wire leading to Is collector high limit switch Control boardBlower Replacement Procedure See photo below Check Purge LED status On ignition module Only power LED is on, or Purge LED flashingReset button Refer to Check Collector Pressure See next Is there continuity Through REDEF60T150,EF100T250 +1.22 EF60T125 +2.08 EF100T300 +0.55 Check Collector PressureCheck exhaust collector pressure at the exhaust EF60,100T199 +2.58 EF100T150 +1.50Exhaust Pressure Switch Replacement Procedure Exhaust collectorExhaust pipe Pressure tap location Energize? Switch operationError code 29 again? Support Reset buttonPressure tap location Exhaust tube At bottom of heater Check Exhaust Tube PressureIs value negative or Vent tablesExhaust Tube Pressure tap location Hot surface Igniter Testing Procedure Check during igniter warm up periodCheck harness Connection from igniter To ignition module Screws Hot surface Igniter Replacement ProcedureSensor Flame Sensor Testing ProcedureGasket Check continuity from tip of flame sensor NFlame Sensor Replacement Procedure Spark Rod Gap Inspection and Adjustment Spark Rod Replacement Procedure Ignition Module Located on control panel Ignition Module Replacement ProcedureIdentify wires for Transformer Replacement Procedure StepStep Disconnect harness P1 & P2 From ignition module Does Blower Energize? Or more?Pressure tap Call for technical support Intake Pressure Switch Replacement Procedure Step Disconnect red wiresStep Remove Mounting screws Button on high System OK Reset buttonVent Safety Switch Replacement Procedure Disassembly Procedure for Access to Anodes & Flue Baffles Anode inspection and replacement Flue baffle inspection and replacement Powered Anode Replacement EF100T399 models only Collector Cover Installation Procedure Vent tables Spark Gap Gas Line Gas Pressure VenturiModels prior to CF serial number Latch Assy Electronic Control Module For models with CF serial or later Combustion Surround Assy. specify Electronic Control Module For models with Direct Spark Ignition Honeywell Control Display 10C 11C 12C 13C BTU/H Page Page Parts@bradfordwhite.com Techserv@bradfordwhite.com

EFR160T120*(EN, EF100T250(E)*(N, EF100T399(E)*(N, EF100T300(E)*(N, EF60T125(E)*(N specifications

Bradford-White Corporation is a leading manufacturer of water heating solutions, known for its high-quality and durable products. Among its extensive product lineup, the EF60T150(E)*(N), EF100T150(E)*(N), EF60T199(E)*(N,X)(A)(2), and EF100T199(E)*(N) models stand out for their impressive features and technologies that cater to both residential and commercial water heating needs.

The EF60T150(E)*(N) model is designed for medium to large households, providing a reliable hot water supply. It features a 60-gallon tank with a first-hour delivery rate that ensures ample hot water, making it ideal for simultaneous usage in multiple applications. This water heater operates on natural gas, boasting high energy efficiency ratings due to its advanced burner technology. The environmentally friendly design reduces greenhouse gas emissions while delivering consistent performance.

Similarly, the EF100T150(E)*(N) model provides an even larger capacity of 100 gallons, addressing the hot water demands of larger families or commercial establishments. It employs Bradford-White's Hydrojet Total Performance System, which minimizes sediment buildup and optimizes hot water output. This model also features a patented Vitraglas lining that protects the tank from corrosion, extending its lifespan and enhancing reliability.

On the other hand, the EF60T199(E)*(N,X)(A)(2) and EF100T199(E)*(N) models offer advanced technology with their unique "N" designation, indicating that they are equipped to handle more extensive heating requirements efficiently. The EF60T199 model, with its 60-gallon capacity, and the EF100T199, with 100 gallons, incorporate enhanced insulation to reduce heat loss and improve energy efficiency. Both models are designed for easy installation and maintenance, making them user-friendly for both homeowners and technicians.

Additionally, these water heaters feature advanced electronic ignition and controls that allow for precise temperature regulation and easy monitoring. The intuitive user interface simplifies operation, while built-in safety features ensure reliable and secure hot water delivery.

Overall, Bradford-White's EF series of water heaters, including the EF60T150(E)*(N), EF100T150(E)*(N), EF60T199(E)*(N,X)(A)(2), and EF100T199(E)*(N), exemplify the company's commitment to quality and innovation. With their robust performance, energy efficiency, and advanced technologies, these models offer dependable hot water solutions tailored to meet the diverse needs of today's consumers. Whether for residential or commercial use, Bradford-White continues to set the standard for excellence in water heating technology.