A.O. Smith 650A, 740A, BTP(V)-540A Vent Terminal LOCATIONS-EXHAUST, Vent System Installation

Page 8

Refer to Table 2 for limitations of venting system design for horizontal venting.

TABLE 2

 

 

 

BTPV-540A-740A

Flue Outlet Dia. (Inches/mm)

 

9” (228.6)

Flue Reducer

 

9” x 8”

Dimensions -Supplied (Inches/mm)

228.6 x 203.2

Minimum Outlet Vent Dia. (Inches/mm)

8” (203.2)

Maximum Number

 

90°

4

Of Elbows

 

45°

8

Maximum Total Vent System

 

75

Length, Equiv. Feet/Meters

 

(23 m)

 

 

 

 

When calculating the equivalent length of a venting system each 90° elbow is equivalent to 10 feet (3 m) of straight pipe. In no case 45° elbow is equivalent to 5 feet (1.5 m) of straight pipe. In no case may the sum of the straight pipe lengths and the equivalent length of the elbows exceeds 80 feet (24.3 m).

Note the minimum vent diameter in Table 2.

Refer to Table 3 for the correct vent terminal size for each heater. The dimensions noted in Table 3 refer to Figure 5.

TABLE 3

Heater

Terminal

 

 

 

 

Rough-In

Model

Model

A

B

C

D

Dimensions

BTPV

 

 

 

 

 

 

540A-

VH-1-8”

19-7/8”

13”

10-9/16”

8-5/8”

11-1/16”

740A

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE5

Use only the sidewall vent terminal supplied with the heater. These terminals are specifically listed for use on these A.O. Smith heaters.

VENT TERMINAL LOCATIONS-EXHAUST

When considering location for sidewall vent terminals refer to the latest edition of the National Fuel Gas Code which recommends that vent terminals:

1.Shall be located not less than 12” (304.8 mm) above grade.

2.Shall be located not less than 7 feet (2.1 m) above grade when adjacent to a public walkway.

3.Shall terminate at least 3 feet (0.9 m) above any forced air inlet within 10 feet (3 m).

4.Shall terminate at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from or 1 foot above any door, window or gravity air inlet into any building.

5.Shall not be closer than 3 feet (0.9 m) from the inside corner of an L- shaped structure.

6.Shall be located above the snow line in geographical areas where snow accumulates.

VENT SYSTEM INSTALLATION

This heater is a category III appliance when horizontally vented through a wall using the supplied sidewall vent terminal. All national and local codes pertaining to the installation of such venting systems must be followed.

Horizontal portions of the vent system must be installed with a minimum upward slope of 1/4” per foot of length.

All joints and seams in the venting system must be sealed gas tight. If a silicone sealer is used, it must have a continuous temperature rating of at least 500°F (260°C); Dow Corning 736 or equivalent must be used.

CAUTION

Use only the vent hood supplied with this kit. Only supplied hood provides required clearances from combustibles, both through the wall and the exterior siding. Termination of a sidewall vent system with a device other than the supplied vent hood could affect system performance and result in a safety hazard.

IMPORTANT

Plan the layout of the vent system backward from the vent termination to the water heater.

1.Use the layout of the vent system backward from the vent termination to the water heater.

BEWARE OF CONCEALED WIRING AND PIPING INSIDE OF WALL. REFER TO TABLE 5 FOR THE MAXIMUM WALL THICKNESS “B” FOR EACH MODEL.

2.Slide hood through opening from outside. Fasten hood to exterior wall with anchors and screws supplied.

3.Install covers plate and fasten to inside wall with 4 screws.

4.Attach a seal ring (Meltalbestos SR or equivalent) to the vent hood collar, see Figure 7. Attach Selkirk Metalbestos model PS or model G venting to the seal ring following the venting manufacturer’s instructions. For total safety, it is recommended that only venting listed for use with category III appliances (positive vent pressure, non-condensing) should be used between the heater and the vent hood, even through national or local codes may allow the use of type B or single- wall vent.

5.Install the remaining vent sections back to the heater, following the venting manufacturer’s instructions on assembling and sealing joints. Follow good venting practice regarding properly supporting vent system and keeping the number of offsets to a minimum. See Table 2 for the maximum allowable number of elbows in venting system.

6.Install the flue reducer included with the exhaust hood between the vent system and the heater.

7.Seal all vent connections and venting with sealants supplied by vent pipe manufacturer or with a high-temperature silicone sealant suitable for continuous temperatures of 500°F (260°C). Acceptable sealant include Dow Corning 736 or equivalent.

8

Image 8
Contents Installation Operation Maintenance Limited Warranty Models BTPV-540A, 650A and 740AROUGH-IN Dimensions ForewordTable of Contents General Safety InformationFeatures Extended NON-USE PeriodsInstallation Instructions Dishwashing Machine RequirementRequired Ability UncratingHard Water ClearancesAIR Requirements VentingBarometric Draft Control Assembly Vertical Venting for BTP ModelsHorizontal SIDE-WALL Venting For Btpv Models Vent ConnectionsVent System Installation Vent Terminal LOCATIONS-EXHAUSTDirect Venting for Btpv Models Vent Terminal LOCATIONS-INTAKEDirect Vent System Installation Drain Valve and Access Panels GAS PipingANY Supply Pressure Testing Exceeding 1/2 PSIG. GAS GAS Meter Size City Gases onlyGAS Pressure Regulation GAS ValvesSystem Connections Water Line ConnectionsRelief Valve Installation Diagrams Circulating Pump Wiring DiagramWiring Diagram for Tempered Water Loop if Used Circulating Pump Wiring Diagram Page Manifold Kits Heater Wiring Start UPPurging FillingPage Page For Your Safety Read Before Lighting Sequence of Operation Adjustment for High Elevation Application Premix LOW NOx Burner Exploded View for BTP Models Premix LOW NOx Burner Exploded View for Btpv Models Maintenance General InformationLime Scale Removal DrainingSediment Removal Checklist and Service Troubleshooting Water is TOO HOTWater Heater Makes Sounds HOT Water OdorMotor will not RUN Burner Lockout Once in a WhileNoisy Burner Operation GAS Fails to Shut OFFModel Btpv Limited Warranty Page Page Replacement Parts

BTP(V)-540A, 650A, 740A specifications

A.O. Smith is renowned for its innovative water heating solutions, and the 650A, 740A, and BTP(V)-540A models exemplify this legacy. These water heaters are designed with advanced technology and feature a range of specifications tailored to meet diverse heating needs.

The A.O. Smith 650A model stands out with its efficient design and high-capacity heating capabilities. It is equipped with a powerful heating element that ensures rapid water heating, allowing consumers to enjoy hot water without long waits. The unit's tank is insulated with durable materials, which minimizes heat loss and enhances energy efficiency. Additionally, it incorporates a glass-lined tank that resists corrosion and extends the lifespan of the water heater, making it a reliable choice for households.

Moving on to the 740A model, this unit is designed for larger applications and can accommodate significant hot water demands. Its advanced heating technology includes an impressive recovery rate, which enables it to supply hot water even during peak usage times. The 740A is also equipped with smart diagnostics that monitor the system's performance, ensuring optimal operation and identifying potential issues before they escalate. This feature enhances user convenience and reduces maintenance costs.

The BTP(V)-540A takes efficiency one step further with its unique heat pump technology. It captures ambient heat from the surroundings to heat water, significantly reducing energy consumption compared to traditional electric water heaters. This eco-friendly model is ideal for those looking to lower their energy bills without sacrificing performance. The BTP(V)-540A also features a user-friendly digital display that allows users to easily adjust settings and monitor performance.

In summary, the A.O. Smith 650A, 740A, and BTP(V)-540A models showcase the brand's commitment to quality, efficiency, and innovation. Each model comes with distinct features tailored to different household requirements. With advanced heating technologies, robust construction, and user-friendly interfaces, these water heaters represent some of the best options available in the market for ensuring a reliable hot water supply. A.O. Smith continues to set the bar high in the water heating industry, making these models a smart investment for any home.