A.O. Smith 650A, 740A warranty Hard Water, Clearances, AIR Requirements, Venting, Confined Space

Page 6

Units, which are to be installed on combustible flooring, must be supported by a full layer of hollow concrete blocks, from 8” (203.2 mm) to 12” (304.8 mm) thick and extending 12” (304.8 mm) minimum beyond the heater in all directions. The concrete blocks must provide an unbroken concrete surface under the heater with the hollows running continuously and horizontally. A 3/16-inch steel plate must cover the concrete blocks, see Figure 2.

NOTE: If electrical conduits run under the floor of the proposed heater location, insulate the floor as recommended above.

For appliances installation locations with elevations above 2000 feet (609.6 m), refer to HIGH ALTITUDE INSTALLATIONS section.

PROPER INSTALLATION ON COMBUSTIBLE FLOORING

FIGURE 2.

HARD WATER

Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwasher, Coffee urns, water heaters, water piping and other equipment.

See MAINTENANCE section for details of tank cleanout procedure.

CLEARANCES

These heaters are designed for installation on non-combustible flooring in an alcove with clearances to combustible construction of 6” (152.4 mm) from the sides and rear, 24” (610 mm) from the top with a 6” (152.4 mm) minimum between vent pipe and ceiling. Minimum clearance from flue pipe to combustible material is 6” (152.4 mm), see Figure 3.

PROPER INSTALLATION CLEARANCES

FIGURE 3.

A clearance of 30” (762 mm) shall be maintained from serviceable parts, such as power burners, relief valves flue baffles, thermostats or drain valves.

AIR REQUIREMENTS

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS,GASOLINEANDOTHERFLAMMABLEVAPORSAND LIQUIDS.

DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR VENTILATING AIR.

WARNING

FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION AND VENTILATION. AN INSUFFICIENT SUPPLY OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN AIR CONTAMINATION THAT MAY BE HAZARDOUSTO LIFE. SUCH A CONDITION OFTENWILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING CARBONING OR SOOTING OF THE COMBUSTION CHAMBER, BURNERS AND FLUE TUBES AND CREATES A RISK OF ASPHYXIATION.

Where an exhaust fan is installed in the same room with a heater, sufficient openings for air must be provided in the walls.

UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION. SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE HEATER AND RISK OF FIRE OR EXPLOSION.

UNCONFINED SPACE

In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion and ventilation.

If the unconfined space is within a building of tight construction, (building using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion and ventilation must be obtained from outdoors or spaces freely communicating with the outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.

CONFINED SPACE

When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE IN OR WITHIN 12 INCHES (304.8 mm) OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES (304.8 mm) OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btuh of the total input of all appliances in the enclosure, but not less than 100 square inches.

If the confined space is within a building of tight construction, air for combustion and ventilation must be obtained from outdoors. When directly communication with the outdoors through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btuh of the total input of all appliances in the enclosure.

VENTING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

6

Image 6
Contents Installation Operation Maintenance Limited Warranty Models BTPV-540A, 650A and 740AROUGH-IN Dimensions ForewordTable of Contents General Safety InformationFeatures Extended NON-USE PeriodsRequired Ability Installation InstructionsDishwashing Machine Requirement UncratingAIR Requirements Hard WaterClearances VentingHorizontal SIDE-WALL Venting For Btpv Models Barometric Draft Control AssemblyVertical Venting for BTP Models Vent ConnectionsVent System Installation Vent Terminal LOCATIONS-EXHAUSTDirect Venting for Btpv Models Vent Terminal LOCATIONS-INTAKEDirect Vent System Installation Drain Valve and Access Panels GAS PipingGAS Pressure Regulation ANY Supply Pressure Testing Exceeding 1/2 PSIG. GASGAS Meter Size City Gases only GAS ValvesWater Line Connections Relief ValveSystem Connections Installation Diagrams Circulating Pump Wiring DiagramWiring Diagram for Tempered Water Loop if Used Circulating Pump Wiring Diagram Page Manifold Kits Purging Heater WiringStart UP FillingPage Page For Your Safety Read Before Lighting Sequence of Operation Adjustment for High Elevation Application Premix LOW NOx Burner Exploded View for BTP Models Premix LOW NOx Burner Exploded View for Btpv Models Maintenance General InformationDraining Sediment RemovalLime Scale Removal Checklist and Service Water Heater Makes Sounds TroubleshootingWater is TOO HOT HOT Water OdorMotor will not RUN Burner Lockout Once in a WhileNoisy Burner Operation GAS Fails to Shut OFFModel Btpv Limited Warranty Page Page Replacement Parts

BTP(V)-540A, 650A, 740A specifications

A.O. Smith is renowned for its innovative water heating solutions, and the 650A, 740A, and BTP(V)-540A models exemplify this legacy. These water heaters are designed with advanced technology and feature a range of specifications tailored to meet diverse heating needs.

The A.O. Smith 650A model stands out with its efficient design and high-capacity heating capabilities. It is equipped with a powerful heating element that ensures rapid water heating, allowing consumers to enjoy hot water without long waits. The unit's tank is insulated with durable materials, which minimizes heat loss and enhances energy efficiency. Additionally, it incorporates a glass-lined tank that resists corrosion and extends the lifespan of the water heater, making it a reliable choice for households.

Moving on to the 740A model, this unit is designed for larger applications and can accommodate significant hot water demands. Its advanced heating technology includes an impressive recovery rate, which enables it to supply hot water even during peak usage times. The 740A is also equipped with smart diagnostics that monitor the system's performance, ensuring optimal operation and identifying potential issues before they escalate. This feature enhances user convenience and reduces maintenance costs.

The BTP(V)-540A takes efficiency one step further with its unique heat pump technology. It captures ambient heat from the surroundings to heat water, significantly reducing energy consumption compared to traditional electric water heaters. This eco-friendly model is ideal for those looking to lower their energy bills without sacrificing performance. The BTP(V)-540A also features a user-friendly digital display that allows users to easily adjust settings and monitor performance.

In summary, the A.O. Smith 650A, 740A, and BTP(V)-540A models showcase the brand's commitment to quality, efficiency, and innovation. Each model comes with distinct features tailored to different household requirements. With advanced heating technologies, robust construction, and user-friendly interfaces, these water heaters represent some of the best options available in the market for ensuring a reliable hot water supply. A.O. Smith continues to set the bar high in the water heating industry, making these models a smart investment for any home.