2.Drill a pilot hole approximately 1/4" (6 mm) outside of the marked circle. This pilot hole is used as a starting point for a saws- all or sabre saw blade. Cut around the marked circle staying approximately one quarter inch outside the line. (This will allow the vent pipe to easily slide through the opening). The resulting gap will be covered by the roof boot/flashing.
3.Suspend the pipe through center of hole using proper support.
4.Slide roof boot or equivalent flashing over pipe and secure roof boot equivalent flashing to roof.
5.Seal around flashing.
6.Terminate intake terminal and exhaust vent terminal facing down.
See Figure 11.
FIGURE 11.
INSTALLATION OF VENT SYSTEM
WARNING
THE OPTIONAL INTAKE VENTING ARRANGEMENT AND THE EXHAUST VENTING ARRANGEMENT MUST BE INSTALLED TO RUN DIRECTLY TO THE OUTDOORS AND NOT IN ANY WAY BE CONNECTED TO ANOTHER VENTING SYSTEM (I.E. FURNACE, DRYERS OR SPACE HEATERS). IT IS CRUCIAL THAT THE VENTING ARRANGEMENT BE KEPT SEPARATE FROM OTHER VENTING SYSTEMS. IF THIS WARNING IS IGNORED, AND THE SYSTEM IS VENTED INCORRECTLY, IT MAY CAUSE IMPROPER OPERATION, FIRE, EXPLOSION, OR ASPHYXIATION.
1.Plan the route of the vent system from the vent termination to the planned location of the appliance. Layout the total vent system to use the minimum of vent pipe and elbows possible.
2.This unit is certified for the use of
Table 2. VENT LENGTH TABLE
Number |
| 4" PVC | |
of 90° | Maximum |
| Maximum |
Elbows | Feet. of Pipe |
| Meters of Pipe |
ONE (1) | 65' |
| 19.7 m |
TWO (2) | 60' |
| 18.2 m |
THREE (3) | 55' |
| 16.7 m |
FOUR (4) | 50' |
| 15.2 m |
FIVE (5) | 45' |
| 13.6 m |
SIX (6) | 40' |
| 12.1 m |
3.The unit is certified to a minimum amount of
IMPORTANT
When multiple units are direct vented through a wall
NOTE: This unit can be vented using only PVC (Class 160, ASTM
NOTE: for Water Heaters in locations with high ambient temperatures (above 100°F or 38°C) and/or insufficient dilution air, it is recommended that CPVC or ABS pipe and fittings (MUST USE
SUPPLIED VENT TERMINAL) be used.
5.It is important that condensate not be allowed to buildup in the exhaust vent pipe. To prevent this from happening the pipe should be installed with a slight, 1/8 inch (3mm) per 5 feet (152 cm) of pipe maximum downward slope.
6.The vent system should be supported every 5 feet (152 cm) of vertical run and every 3 feet (91cm) of horizontal run of vent pipe length.
NOTE: Stress levels in the pipe and fittings can be significantly increased by improper installation. If rigid pipe clamps are used to hold the pipe in place, or if the pipe cannot move freely through a wall penetration, the pipe may be directly stressed, or high thermal stresses may be formed when the pipe heats up and expands. Install accordingly to minimize such stresses.
INLET VIEW
OUTLET VIEW
FIGURE 12.
13