A.O. Smith BTX-80 SERIES 100 instruction manual Insulation Blankets, Air REQUIREMENTs

Page 12

in an alcove or closet, the entire floor must be covered by the panel. Failure to heed this warning may result in a fire hazard.

Minimum clearances between water heater and combustible construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the front and 12” (30.5 cm) from top. (Standard clearance.) If clearances stated on the heater differ from standard clearances, install water heater according to clearances stated on the heater.

Adequate clearance 24” (61.0 cm) for servicing this appliance should

be considered before installation, such as changing the anodes, etc.

A minimum clearance of 5.5” (14.0 cm) must be allowed for access to replaceable parts such as thermostats, drain valve, relief valve and condensate drain.

When installing the heater, consideration must be given to proper location. Location selected should be as close to the wall as practicable and as centralized with the water piping system as possible.

FIGURE 4.

A gas water heater cannot operate properly without the correct amount

of air for combustion. Do not install in a confined area such as a closet,

unless you provide air as shown in the “Locating The New Water

Heater” section. Never obstruct the flow of ventilation air. If you have

any doubts or questions at all, call your gas supplier. Failure to provide

the proper amount of combustion air can result in a fire or explosion

and cause death, serious bodily injury, or property damage.

FIGURE 5.

If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry cleaning equipment, it is imperative that the water heater or water heaters be installed so that combustion and ventilation air be taken from outside these areas.

Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine based chemicals, refrigerants, etc.) in addition to being highly flammable in many cases, will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure.

INSULATION BLANKETS

Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce standby heat loss encountered with storage tank heaters. Your water heater meets or exceeds the Energy Policy Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.

Should you choose to apply an insulation blanket to this heater, you should follow these instructions (For identification of components mentioned below, see Figure 1). Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death.

Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the blower assembly.

Do not cover the outer door, thermostat or temperature & pressure relief valve.

Do not allow insulation to come within 2” (5.1 cm) of the floor to prevent blockage of combustion air flow to the burner.

Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.

Do obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels.

Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow.

Air REQUIREMENTs

For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided.

An insufficient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life.

12

Image 12
Contents Power Vented GAS Models W/HOT Surface Ignition Whenever maintenance adjustment or service is requiredPrinted 197086-004Safe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Information General Safety Information Table of Contents IntroductionInstallation of Carbon Monoxide Detectors Approved Carbon Monoxide DetectorsSignage ExemptionsTypical Installation Replacement Parts and Deliming ProductsElbow Access Door Condensate Hose and Drain PAN Mixing Valves ROUGH-IN-DIMENSIONS Rough-In-DimensionsCapacity and Gas and Electrical Characteristics Recovery capacity based on 90% thermal efficiencyLocating the NEW Water Heater Facts to Consider About the LocationInsulation Blankets Air REQUIREMENTsUnconfined Space Confined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsOutdoor AIR Through TWO Horizontal Ducts Outdoor AIR Through TWO Vertical DuctsAIR from Other Indoor Spaces Installing the NEW Water Heater Chemical Vapor CorrosionWater Piping Space Heating and Potable Water SystemTemperature-Pressure Relief Valve Thermal ExpansionValve and Pipe Insulation if supplied High Altitude Installation Contact qualified installer or service agencyGas Piping Sediment Traps Filling the Water HeaterPer square inch 3.5 kPa Vent Pipe Assembly VentingTermination Clearances Sidewall Power Vent Vent Pipe TerminationPlanning the Vent System CondensateBreathing Hazard Carbon Monoxide Gas Blower Assembly Installation Installation of Vent SystemVent Terminal INSTALLATION, Sidewall Power Vent Wiring Schematic Figure Chisel an opening approximately one half inch 1.3 cm largerThan the marked circle Pointed in the correct position, see FigureInstallation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemVent Attenuation Assembly Installation Vent attenuation assembly Flexible tubing Instruction sheetVertical VAA Installations Recommended Inch vent Vertical VAA Installations Vent Pipe Preparation Recommended BRUSH* Size for Primer Cement ApplicationsStep B Step EStep F Step GPower Before Servicing Do not try to light the burner by handWhat to do if YOU Smell GAS Do not TRY to Light the Burner by HandTemperature Regulation Temperature Indicators Temperature Adjustment ButtonsDisplay D E FFor Your Information Start UP ConditionsOperational Conditions Periodic Maintenance Anode ROD InspectionTemperature-Pressure Relief Valve Test Keep hands clear of drainTo Flush the Water Heater Storage Tank Open the water heater drain valve to flush the storage tankService Leakage CheckpointsTroubleshooting Guidelines Trouble ShootingEnsure the flame sensor is clean use ultra fine steel Turn off power to the water heaterAssembly if damaged or defective Unplug ignitor assembly plug from control. Check resistanceUnplug the ignitor assembly plug from the control. Check Resistance of the black resistor wire between pinsAssembly .2 If the reading taken is less than 100,000 Check vent temperature limit switch if it is determinedTroubleshooting Guidelines Service and Repair Expenses Claim ProcedureTank ALL Other Parts

BTX-80 SERIES 100 specifications

The A.O. Smith BTX-80 Series 100 is a cutting-edge heating solution designed for effective and efficient water heating. This model is particularly well-suited for residential applications, offering an impressive balance of performance and energy efficiency.

One of the standout features of the BTX-80 Series 100 is its innovative design, which incorporates a high-efficiency condensing technology. This allows the unit to capture and utilize heat that would otherwise be lost in traditional systems, thereby maximizing energy usage and reducing overall operating costs. With an impressive energy factor (EF) rating, this water heater contributes to lower utility bills while promoting environmental sustainability.

The BTX-80 is equipped with a powerful 80-gallon tank, providing ample hot water for households of varying sizes. Its large capacity ensures that multiple appliances can operate simultaneously without running out of hot water, making it an ideal choice for families with high demand. The model also incorporates a robust heating element that ensures rapid recovery and maintains consistent water temperatures.

Safety and convenience are paramount in the design of the BTX-80. It features a comprehensive digital control system that allows users to set precision temperature settings according to their needs. The intuitive interface simplifies adjustments and monitoring, while safety mechanisms like temperature and pressure relief valves provide peace of mind during operation.

A.O. Smith has also prioritized quality and durability in the construction of the BTX-80 Series 100. The tank is made from high-quality materials and comes with a robust enamel coating that resists corrosion and extends its lifespan. Additionally, the unit is backed by a lengthy warranty, reflecting the manufacturer's confidence in its longevity.

Installation and maintenance are straightforward with the BTX-80, as it is designed to fit seamlessly into existing plumbing configurations. Furthermore, the unit operates quietly, ensuring minimal disruption in the home environment.

In conclusion, the A.O. Smith BTX-80 Series 100 stands out in the market as a reliable, energy-efficient, and user-friendly water heating solution. With its advanced technologies and emphasis on safety and durability, it proves to be a smart investment for any household looking to improve their hot water system.