A.O. Smith BTX-80 SERIES 100 instruction manual High Altitude Installation, Gas Piping

Page 17

discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

CAUTION

Water Damage Hazard

Temperature-Pressure Relief Valve discharge pipe must terminate at adequate drain.

T&P Valve Discharge Pipe Requirements:

Should not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Should not be plugged or blocked.

Should not be exposed to freezing temperatures.

Should be of material listed for hot water distribution.

Should be installed so as to allow complete drainage of both the

Temperature-Pressure Relief Valve and the discharge pipe.

Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.

Should not have any valve or other obstruction between the relief valve and the drain.

HIGH ALTITUDE INSTALLATION

This heater is approved for operation up to 5,300 feet (1,615 m) without alteration. High altitude models are available from the factory for elevations between 5,300 feet (1,615 m) and 10,100 feet (3,079 m). For elevations above 10,100 feet (3,079 m) the input rating should be reduced at the rate of 4 percent for each 1,000 feet (305

m)above sea level which requires replacement of the burner orifice in accordance with National Fuel Gas Code (ANSI Z223.1/NFPA 54) or the Natural Gas and Propane Installation Code (CAN/CSA B149.1).

Contact your local gas supplier for further information.

Failure to replace standard orifice with a high altitude orifice when installed above 10,100 feet (3,079 m) could result in improper and inefficient operation of the appliance, producing carbon monoxide gas in excess of safe limits, which could result in serious injury or death. Contact your gas supplier for any specific changes which may be required in your area.

Gas Piping

DANGER

Burn hazard.

Hot water discharge.

Keep clear of Temperature- Pressure Relief Valve discharge outlet.

Fire and Explosion Hazard

Do not use water heater with any gas other than the gas shown on the rating plate.

Excessive pressure to gas control valve can cause serious injury or death

Turn off gas lines during installation.

The Temperature-Pressure Relief Valve must be manually operated at least twice a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions in this manual, and replace the Temperature-Pressure Relief Valve with a properly rated/sized new one.

Note: The purpose of a Temperature-Pressure Relief Valve is to prevent excessive temperatures and pressures in the storage tank. The T&P valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion, see Closed Water Systems and Thermal Expansion on page 15-16.

If you do not understand these instructions or have any questions regarding the Temperature-Pressure Relief Valve call the toll free number listed on the back cover of this manual for technical assistance.

Contact qualified installer or service agency.

Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 14 inch water column (3.5 kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure shown on the rating plate is that which will permit firing at rated input.

All gas piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSI Z223.1/ NFPA-54) or the Natural Gas and Propane Installation Code (CAN/CSA B149.1) whichever applies. Copper or brass tubing and fittings (except tin lined copper tubing) should not be used.

If the gas control valve is subjected to pressures exceeding 1/2 psi (3.5 kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used, also turn “off” the gas at each appliance. Leave all gas appliances shut “off” until the water heater installation is complete.

17

Image 17
Contents Whenever maintenance adjustment or service is required Power Vented GAS Models W/HOT Surface IgnitionPrinted 197086-004Important Definitions Safe INSTALLATION, USE and ServiceApprovals General Safety Information General Safety Information Introduction Table of ContentsApproved Carbon Monoxide Detectors Installation of Carbon Monoxide DetectorsSignage ExemptionsElbow Access Door Typical InstallationReplacement Parts and Deliming Products Condensate Hose and Drain PAN Mixing Valves Rough-In-Dimensions ROUGH-IN-DIMENSIONSCapacity and Gas and Electrical Characteristics Recovery capacity based on 90% thermal efficiencyFacts to Consider About the Location Locating the NEW Water HeaterAir REQUIREMENTs Insulation BlanketsConfined Space Unconfined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsAIR from Other Indoor Spaces Outdoor AIR Through TWO Horizontal DuctsOutdoor AIR Through TWO Vertical Ducts Chemical Vapor Corrosion Installing the NEW Water HeaterWater Piping Space Heating and Potable Water SystemValve and Pipe Insulation if supplied Temperature-Pressure Relief ValveThermal Expansion Gas Piping High Altitude InstallationContact qualified installer or service agency Per square inch 3.5 kPa Sediment TrapsFilling the Water Heater Venting Vent Pipe AssemblyVent Pipe Termination Termination Clearances Sidewall Power VentBreathing Hazard Carbon Monoxide Gas Planning the Vent SystemCondensate Vent Terminal INSTALLATION, Sidewall Blower Assembly InstallationInstallation of Vent System Chisel an opening approximately one half inch 1.3 cm larger Power Vent Wiring Schematic FigureThan the marked circle Pointed in the correct position, see FigureInstallation of Vertical Vent System Installation of Vent SYSTEM, SidewallVertical VAA Installations Recommended Vent Attenuation Assembly InstallationVent attenuation assembly Flexible tubing Instruction sheet Inch vent Vertical VAA Installations Recommended BRUSH* Size for Primer Cement Applications Vent Pipe PreparationStep E Step BStep F Step GDo not try to light the burner by hand Power Before ServicingWhat to do if YOU Smell GAS Do not TRY to Light the Burner by HandTemperature Indicators Temperature Adjustment Buttons Temperature RegulationDisplay D E FOperational Conditions For Your InformationStart UP Conditions Anode ROD Inspection Periodic MaintenanceKeep hands clear of drain Temperature-Pressure Relief Valve TestTo Flush the Water Heater Storage Tank Open the water heater drain valve to flush the storage tankLeakage Checkpoints ServiceTrouble Shooting Troubleshooting GuidelinesTurn off power to the water heater Ensure the flame sensor is clean use ultra fine steelAssembly if damaged or defective Unplug ignitor assembly plug from control. Check resistanceResistance of the black resistor wire between pins Unplug the ignitor assembly plug from the control. CheckAssembly .2 If the reading taken is less than 100,000 Check vent temperature limit switch if it is determinedTroubleshooting Guidelines Claim Procedure Service and Repair ExpensesTank ALL Other Parts

BTX-80 SERIES 100 specifications

The A.O. Smith BTX-80 Series 100 is a cutting-edge heating solution designed for effective and efficient water heating. This model is particularly well-suited for residential applications, offering an impressive balance of performance and energy efficiency.

One of the standout features of the BTX-80 Series 100 is its innovative design, which incorporates a high-efficiency condensing technology. This allows the unit to capture and utilize heat that would otherwise be lost in traditional systems, thereby maximizing energy usage and reducing overall operating costs. With an impressive energy factor (EF) rating, this water heater contributes to lower utility bills while promoting environmental sustainability.

The BTX-80 is equipped with a powerful 80-gallon tank, providing ample hot water for households of varying sizes. Its large capacity ensures that multiple appliances can operate simultaneously without running out of hot water, making it an ideal choice for families with high demand. The model also incorporates a robust heating element that ensures rapid recovery and maintains consistent water temperatures.

Safety and convenience are paramount in the design of the BTX-80. It features a comprehensive digital control system that allows users to set precision temperature settings according to their needs. The intuitive interface simplifies adjustments and monitoring, while safety mechanisms like temperature and pressure relief valves provide peace of mind during operation.

A.O. Smith has also prioritized quality and durability in the construction of the BTX-80 Series 100. The tank is made from high-quality materials and comes with a robust enamel coating that resists corrosion and extends its lifespan. Additionally, the unit is backed by a lengthy warranty, reflecting the manufacturer's confidence in its longevity.

Installation and maintenance are straightforward with the BTX-80, as it is designed to fit seamlessly into existing plumbing configurations. Furthermore, the unit operates quietly, ensuring minimal disruption in the home environment.

In conclusion, the A.O. Smith BTX-80 Series 100 stands out in the market as a reliable, energy-efficient, and user-friendly water heating solution. With its advanced technologies and emphasis on safety and durability, it proves to be a smart investment for any household looking to improve their hot water system.