A.O. Smith 185363-001 ALL AIR from Inside Buildings See, ALL AIR from Outdoors See Figures 7, 8

Page 9

Chemical vapor corrosion of the flue, blower assembly and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive.

A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 5 and 6)

The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches (31 cm) of the top and one commencing within 12 inches (31 cm) of the bottom of the enclosures.

FIGURE6.

B. ALL AIR FROM OUTDOORS: (See Figures 7, 8 and 9)

The confined space shall be provided with two permanent openings, one commencing within 12 inches (31 cm) of the top and one commencing within 12 inches (31 cm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

1.When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 7.

FIGURE7.

2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 8.

3.When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment in the enclosure, see Figure 9.

FIGURE8.

4.When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than 3 inches (7.6 cm), see Figure 9.

FIGURE9.

5.Louvers and Grilles: In calculating free area, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller than 1/4 inch (6.4 mm) mesh. If the free area through a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will be 20-25 percent free area and metal louvers and grilles will have 60-75 percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

6.Special Conditions Created by Mechanical Exhausting or Fireplaces: operation of exhaust fans, ventilation systems, clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equipment.

9

Image 9
Contents Division OFA. O. Smith Corporation Residential GAS Water HeatersImportant Definitions Safe INSTALLATION, USE and ServiceGeneral Safety Introduction Table of ContentsTypical Installation Natural HOT Surface Igniter & Main BurnerPropane HOT Surface Igniter & Main Burner Hotterwatercanscald Mixing Valve UsageFacts to Consider about the Location Locating the NEW Water HeaterInsulation Blankets ALL AIR from Outdoors See Figures 7, 8 ALL AIR from Inside Buildings SeeInstalling the NEW Water Heater Water PipingHotter Water can Scald Valve and Pipe Insulation if supplied TEMPERATURE-PRESSURE Relief ValveGAS Piping GAS Piping with FlexibleconnectorSequenceofinstallation Blower Assembly InstallationSediment Traps Filling the Water HeaterVenting and Installation Vent Connections to Blower AssemblyMaximum and Minimum Vent Lengths CondensateVenting Vent Terminal InstallationMasonry Side Walls Wooden Side WallsVertical Vent Termination Restrictions Vertical Vent Through RoofRecommended BRUSH* Size for Primer Cement Applications Vent Pipe PreparationStepe StepbStepf StepgPowerbeforeservicing WatertemperatureadjustmentDo not try to light the burner by hand What to do if YOU Smell GASTemperature Setting Burns on Adult Skin Temperature RegulationFor Your Information Start UP ConditionsOperational Conditions Burner Cleaning Periodic MaintenanceVenting System Inspection Burner Operation and InspectionDrain Valve Washer Replacement TEMPERATURE-PRESSURE Relief Valve OperationAnode ROD Inspection DrainingLeakage Checkpoints ServiceRepair Parts List Burner Assembly Drain PAN Outer Door AlternateNot Shown Optional Trouble Shooting Troubleshooting GuidelinesTroubleshooting Guidelines Page Page Claim Procedure Service and Labor ResponsibilityConditions and Exceptions Limitation on Implied WarrantiesTH STREET, ALSIP, IL Phone 1-800-433-2545 FAX

185363-001 specifications

A.O. Smith is renowned for producing high-quality water heating solutions, and the model 185363-001 stands as a testament to the company’s commitment to innovation and efficiency. This water heater is designed to provide reliable hot water for residential and commercial applications, ensuring that users enjoy consistent performance throughout its lifespan.

One of the standout features of the A.O. Smith 185363-001 is its impressive energy efficiency. The unit is built with advanced insulation that minimizes heat loss, thus allowing it to achieve a higher Energy Factor (EF) rating. This efficiency not only contributes to reduced energy bills but also aligns with modern environmental standards, making it a responsible choice for eco-conscious consumers.

The 185363-001 model utilizes a robust tank design that ensures durability and optimal performance. Made from high-grade materials, the tank is resistant to corrosion and wear, extending the heater's lifecycle. Additionally, the unit's glass-lined interior offers added protection against rust and mineral buildup, promoting effective heat transfer and consistent hot water supply.

In terms of capacity, the A.O. Smith 185363-001 is designed to meet the demands of various households. It comes in multiple sizes, catering to different needs, whether for a smaller apartment or a larger family home. This versatility makes it a popular option for installers and homeowners alike.

The water heater is also equipped with advanced safety features, including a temperature and pressure relief valve, which prevents potential hazards by protecting the tank from excessive heat or pressure. Furthermore, the control system includes an adjustable thermostat, allowing users to set their preferred water temperature efficiently.

Another important characteristic of the A.O. Smith 185363-001 is its user-friendly design. The unit is straightforward to operate, which simplifies maintenance and reduces downtime. For technicians, the heater features a modular design that facilitates servicing and replacement of components, ensuring quick repairs when needed.

Overall, the A.O. Smith 185363-001 embodies reliability, efficiency, and ease of use, making it a superb choice for anyone in need of a dependable water heating solution. Its combination of innovative technology and user-centric design ensures that it not only meets but exceeds the expectations of customers, solidifying A.O. Smith's reputation as a leader in the water heater market.