6. Reinstall and bolt up the jacket halves.
The fuse for the Fireman’s Switch is 1.25 amp
MAXIMUM TEMPERATURE SET POINT
1.Unbolt and remove upper jacket halves (see Figure 3, Page 5).
2.Depress clips and remove control board assembly dome (see Figure 9, Page 10).
3.Push the Max. Temp. Set Point button on the back of the control board (see Figure 26). The following sequence should happen:
SET MAX
S1
SET MAX
S1
FIGURE 26: Max Temperature Set Point Controls
A. The unit will come on and the POOL ON light will come on.
B. Press the ▼Temp or ▲Temp pad (on TOP of the panel) to set maximum pool temperature.
C. Wait 30 seconds; the POOL ON light will go off and the SPA ON light will come on.
D. Press the ▼Temp or ▲Temp pad (on TOP of the panel) to set maximum spa temperature (set temper- ature to 104° F or less).
E.Wait 30 seconds; the SPA ON light will go off and the unit will shut down.
4.Reinstall and bolt up the jacket halves.
22