Burner Troubleshooting

SYMPTOM

CAUSE

REMEDY

 

 

 

Loud, high-pitched whine

Flame is too rich.

Verify pressure tap between gas valve

 

 

and blower inlet.

 

 

Turn to Page 19 and verify that the gas

 

 

regulator setting is 0.2”wc below the

 

 

blower inlet pressure.

 

 

Replace gas orifice with smaller size.

 

 

 

Flame is “fluttery.”

Flame is too lean.

Turn to Page 19 and verify that the gas

Exhaust may have acrid

 

regulator setting is 0.2”wc below the

smell or burner may fail

 

blower inlet pressure.

to stay lit.

 

Replace gas orifice with larger size.

 

 

 

Burner pulsates or

Exhaust vent is too long.

Reduce length of exhaust vent and/or

surges, especially on

 

number of elbows.

ignition.

 

 

 

 

 

Combustion appears

Flame current is not

Check for wet or damaged igniter with

normal, but flame does

being sensed.

low resistance to ground. Replace with

not stay lit.

 

new igniter.

 

 

Verify burner flameholder is properly

 

 

grounded.

 

 

Replace Ignition Control Module.

 

 

 

Heat Exchanger Troubleshooting

SYMPTOM

CAUSE

REMEDY

 

 

 

Boiling in heat exchanger.

Low water flow to heater.

Service pump and or filter.

May be accompanied by

Heat exchanger plugged.

Service heat exchanger. Correct water

“bumping” sounds.

 

chemistry.

 

 

 

Bypass valve stuck open.

Service bypass valve.

 

Thermal governor stuck

Replace thermal governor.

 

closed.

 

 

 

 

Sweating.

Thermal governor failed.

Replace thermal governor.

 

 

 