To avoid water damage or scalding from operation of the relief valve, install a drain pipe in the outlet of the pressure relief valve that will direct water discharging from the

To High Side of Differential Pressure Gauge

valve to a safe place for disposal. Do not install any reduc- ing couplings or valves in the drain pipe. The drain pipe must be installed so as to allow complete drainage from the valve and drain line. The relief valve should be tested at least once a year by lifting the valve lever.

Explosion hazard. Any heater installed with restrictive devices in the piping system downstream from the heater (including check valves, isolation valves, flow nozzles, or therapeutic pool valving) must have a relief valve installed as described above. See Page 16.

ON

CAUTION

PILOT

VENT

PRESS

TAP

Connection for

 

Test

 

To Low Side of Diff.

 

Pressure Gauge

 

 

To Air Flow

 

Switch

 

NOTICE: The gas

 

piping and unions

 

are not shown

Connection for

for clarity; make

this test with all

Service

gas piping

 

connected (as for

 

normal service).

2788 0397

FIGURE 21: Connect Gas Valve to End Cap Air Orifice

Instructions For Checking the Gas Pressure

Through the Combination Gas Control Valve

Risk of fire and explosion. Improper installation, adjustment, alteration, service, or main- tenance of the Combination Gas Control Valve can lead to fire or explosion, causing loss of life, per- sonal injury, or property damage.

These instructions are for the use of qualified service technicians only!

Do not attempt this procedure unless you have been trained and certified in the care and repair of gas-fired appliances!

Do not attempt this procedure if the following instructions are confusing!

This appliance is equipped with an unconventional gas control valve that is factory set with a manifold pressure of –.2” wc. Installation or service must be performed by a qualified installer, service agency, or the gas supplier. If this control valve is replaced, it must be replaced with an identical control.

The combination gas valve incorporates dual shut-off valves and a negative-pressure regulator. For proper operation, the regulated pressure at the outlet manifold of the valve must be 0.2” wc below the reference pres- sure at the blower mixer inlet, and the gas valve ‘VENT’ tap must be connected to the endcap air orifice as shown in Figure 21 (above).

Do not attempt to adjust the gas input by adjusting the regulator setting. The correct gas regulator setting is required to maintain proper combustion and must not be altered.

To check that the gas pressure setting is correct, use the following procedure:

1.Turn off the heater and remove the top covers for access to the Combination Gas Control Valve.

2.Use a 3/16” hex key to remove the plug from the ‘PRESSURE TAP’ port on the outlet side of the

Combination Gas Control Valve.

3.Install a 1/8” NPT barbed fitting into the ‘PRESSURE TAP’ port. Use a flexible tube to connect it to the low side of a differential pressure gauge or a slope gauge.

NOTICE: If you are using a slope gauge or a differ- ential pressure gauge of less than 3” capacity, close the shutoff valve of the gauge to avoid pulling the liq- uid out of the gauge when the blower starts.

4.Disconnect the tube from the Gas Valve ‘VENT’ port. Connect it to a tube with a tee running to the high side of a differential pressure gauge and to the blow- er’s air orifice grille (See Figure 21, above).

5.Turn on the heater and verify the gas supply pres- sure (Page 20).

6.After the burner ignites, open the shutoff valve of the gauge. The pressure gauge should then read 0.2” wc ±0.1” wc (0.0” to 0.1” wc = rich mixture; 0.3” to 0.5” wc = lean mixture). (Since the pressure tap is con- nected to the low side of the gauge, the pressure is actually negative.)

Risk of fire or explosion if Combination Gas Control Valve is incorrectly adjusted. If it is necessary to adjust the gas valve, this must be done only by a qualified service agency.

7.Turn off the heater.

8.Replace the plastic hose between the ‘VENT’ port and the inlet of blower mixer. Remove the barbed fit- ting and replace the plug in the ‘PRESSURE TAP’ port of the gas valve, using a thread sealant approved for use with natural gas and LPG.

9.Replace the heater covers and cycle the heater to check for proper operation.

19

Page 19
Image 19
Five Star Sr200na, Sr200lp,, Sr333na, Sr333lp,, Sr400na, Sr400lp owner manual Connect Gas Valve to End Cap Air Orifice