Heater Will Not Fire - B

Start

Is red “SERVICE HEATER” LED “on”

YES

NO

Is red “SERVICE SYSTEM” LED on?

YES

Verify that pump is on, filter is not blocked, and the water flow is above the minimum requirement.

YES

NO

NO

Increase POOL/SPA tempera- ture setting on Membrane Pad above actual water tem- perature. Heater should fire on demand for heat. If not, and no other red LED’s light, replace Control Board.

Service pump/filter and elimi-

CONTINUE

With pump running, adjust Water Pressure Switch to lower pressure until ‘SER- VICE SYSTEM” LED goes out. Then verify that “SER- VICE SYSTEM” LED goes on with pump off.

NO

Check that water pressure is within the adjustment range of the Pressure Switch (0-5 psig)

YES

Verify that switch wiring is OK and sensing tube is not blocked, and replace water Pressure Switch.

YES

NO

nate other flow obstructions.

Heater should fire on call for heat. Re-verify that water flow is above minimum requirement.

Minimum Flow Requirements

ModelFlow

20020 GPM

33330 GPM

40040 GPM

If water pressure is outside of adjustment range that will open switch with pump off and close switch with pump on, replace with flow switch set above minimum flow requirement.

Minimum Flow Requirements

ModelFlow

20020 GPM

33330 GPM

40040 GPM

Check whether any of the red diagnostic LED’s on back of board (AGS, AFS, SFS, HLS or PS) are “on”

NO

GO TO

“HEATER WILL NOT FIRE - C”

Page 26

YES

Go to “Diagnostic LED’s”, (Pages 28 and 29)

25

Page 25
Image 25
Five Star Sr200na, Sr200lp,, Sr333na, Sr333lp,, Sr400na, Sr400lp owner manual Heater Will Not Fire B, Continue